← Oklahoma

Tap water quality report

Yukon, OK

EPA monitoring detected 24 contaminants across the 2 water suppliers serving Yukon. A detection doesn't automatically mean the water is unsafe — see the level at the main supplier for each below, with its EPA source and period.

2
water suppliers
22,848
people served
24
contaminants found

What was found in Yukon's water

The level at the city's main supplier, the highest level anywhere in the city, the EPA limit for each, and where every figure comes from.

ContaminantLevel vs EPA limitSuppliersSource
Nitrate-Nitrite
530 µg/L 5.3%
of the EPA limit 10000 µg/L
Main supplier: YUKON · 22,498 people · 2019
Highest in the city: 5960 µg/L — BLUE QUAIL ESTATES · 350 people · 2019
2/2 SYR4
Copper
100.02 µg/L 7.7%
of the EPA limit 1300 µg/L
Main supplier: YUKON · 22,498 people · 2018
Highest in the city: 806.3 µg/L — BLUE QUAIL ESTATES · 350 people · 2019
2/2 SYR4
Nitrate
630 µg/L 6.3%
of the EPA limit 10000 µg/L
Main supplier: YUKON · 22,498 people · 2012
1/2 SYR4
Fluoride
483 µg/L 12%
of the EPA limit 4000 µg/L
Main supplier: YUKON · 22,498 people · 2016
1/2 SYR4
Barium
181 µg/L 9%
of the EPA limit 2000 µg/L
Main supplier: YUKON · 22,498 people · 2014
Highest in the city: 240 µg/L — BLUE QUAIL ESTATES · 350 people · 2014
2/2 SYR4
TTHM
63.505 µg/L 79%
of the EPA limit 80 µg/L
Main supplier: YUKON · 22,498 people · 2019
2/2 SYR4
Chloroform
51.835 µg/L
No EPA limit set
Main supplier: YUKON · 22,498 people · 2019
2/2 SYR4
Total Haloacetic Acids (HAA5)
41.605 µg/L 69%
of the EPA limit 60 µg/L
Main supplier: YUKON · 22,498 people · 2019
2/2 SYR4
Lead
34.5 µg/L 230%
of the EPA limit, at the 95th percentile of samples — 15 µg/L
Main supplier: YUKON · 22,498 people · 2018
2/2 SYR4
Dichloroacetic Acid
25.21 µg/L
No EPA limit set
Main supplier: YUKON · 22,498 people · 2019
2/2 SYR4
Arsenic
17.125 µg/L 171%
of the EPA limit, at the 95th percentile of samples — 10 µg/L
Main supplier: YUKON · 22,498 people · 2019
1/2 SYR4
Trichloroacetic Acid
14.53 µg/L
No EPA limit set
Main supplier: YUKON · 22,498 people · 2019
1/2 SYR4
Bromodichloromethane
13.09 µg/L
No EPA limit set
Main supplier: YUKON · 22,498 people · 2019
2/2 SYR4
Lithium
11 µg/L
No EPA limit set
Main supplier: YUKON · 22,498 people · 2025
1/2 UCMR-5
Dibromochloromethane
6.495 µg/L
No EPA limit set
Main supplier: YUKON · 22,498 people · 2019
2/2 SYR4
Combined Uranium
4.135 µg/L 14%
of the EPA limit 30 µg/L
Main supplier: YUKON · 22,498 people · 2018
1/2 SYR4
Gross Alpha, Excl. Radon And U
3.8855 pCi/L 26%
of the EPA limit 15 pCi/L
Main supplier: YUKON · 22,498 people · 2018
2/2 SYR4
Combined Radium (-226 And -228)
3.42 pCi/L 68%
of the EPA limit 5 pCi/L
Main supplier: YUKON · 22,498 people · 2018
2/2 SYR4
Monochloroacetic Acid
2.77 µg/L
No EPA limit set
Main supplier: YUKON · 22,498 people · 2019
1/2 SYR4
Gross Beta Particle Activity
2.58 pCi/L
No EPA limit set
Main supplier: YUKON · 22,498 people · 2018
2/2 SYR4
Dalapon
2.57 µg/L 1.3%
of the EPA limit 200 µg/L
Main supplier: YUKON · 22,498 people · 2018
1/2 SYR4
Bromoform
1.985 µg/L
No EPA limit set
Main supplier: YUKON · 22,498 people · 2019
Highest in the city: 2.385 µg/L — BLUE QUAIL ESTATES · 350 people · 2019
2/2 SYR4
Dibromoacetic Acid
2.24 µg/L
No EPA limit set
Main supplier: YUKON · 22,498 people · 2019
2/2 SYR4
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
Main supplier: YUKON · 22,498 people · 2024
2/2 LCR
Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of the system's samples — over 100% is worth reading, but is not by itself a violation. Formal violations are listed separately. These are the utilities' own EPA-reported results, not a city-wide average. A detection means the lab measured the substance — it isn't the same as exceeding a legal limit. Hover a source tag to see the EPA program and years behind each figure.

Water suppliers serving Yukon

SupplierPopulation served
YUKON 22,498
BLUE QUAIL ESTATES 350

Frequently asked questions about Yukon tap water

Is Yukon tap water safe to drink?

EPA testing detected 24 contaminants in the water serving Yukon. A detection isn't the same as a violation — most detected levels are within federal limits. Check the level and source for each contaminant above, and your utility's annual Consumer Confidence Report for the official compliance status.

How many water suppliers serve Yukon?

2 public water suppliers report drinking-water monitoring for Yukon, Oklahoma to the EPA. Each is listed above with its population served.

What contaminants are in Yukon's water?

The contaminants EPA monitoring detected in Yukon include Nitrate-Nitrite, Copper, Nitrate, Fluoride, Barium. The full list, with the level at the main supplier and the data source, is in the table above.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.