← Ohio

Tap water quality report

New Waterford, OH

EPA monitoring detected 22 contaminants across the 2 water suppliers serving New Waterford. A detection doesn't automatically mean the water is unsafe — see the level at the main supplier for each below, with its EPA source and period.

2
water suppliers
3,071
people served
22
contaminants found

What was found in New Waterford's water

The level at the city's main supplier, the highest level anywhere in the city, the EPA limit for each, and where every figure comes from.

ContaminantLevel vs EPA limitSuppliersSource
Nitrate-Nitrite
4791 µg/L 48%
of the EPA limit 10000 µg/L
Highest in the city: NEW WATERFORD VILLAGE PWS · 1,238 people · 2018
1/2 SYR4
Nitrate
4552.5 µg/L 46%
of the EPA limit 10000 µg/L
Highest in the city: NEW WATERFORD VILLAGE PWS · 1,238 people · 2019
1/2 SYR4
Fluoride
350 µg/L 8.8%
of the EPA limit 4000 µg/L
Highest in the city: NEW WATERFORD VILLAGE PWS · 1,238 people · 2019
1/2 SYR4
Copper
141 µg/L 11%
of the EPA limit 1300 µg/L
Main supplier: LEETONIA VILLAGE PWS · 1,833 people · 2019
Highest in the city: 200.8 µg/L — NEW WATERFORD VILLAGE PWS · 1,238 people · 2019
2/2 SYR4
Barium
153.6 µg/L 7.7%
of the EPA limit 2000 µg/L
Highest in the city: NEW WATERFORD VILLAGE PWS · 1,238 people · 2019
1/2 SYR4
TTHM
105.495 µg/L 132%
of the EPA limit, at the 95th percentile of samples — 80 µg/L
Main supplier: LEETONIA VILLAGE PWS · 1,833 people · 2019
2/2 SYR4
Chloroform
89.63 µg/L
No EPA limit set
Main supplier: LEETONIA VILLAGE PWS · 1,833 people · 2019
2/2 SYR4
Total Haloacetic Acids (HAA5)
64.56 µg/L 108%
of the EPA limit, at the 95th percentile of samples — 60 µg/L
Main supplier: LEETONIA VILLAGE PWS · 1,833 people · 2019
2/2 SYR4
Dichloroacetic Acid
36.08 µg/L
No EPA limit set
Main supplier: LEETONIA VILLAGE PWS · 1,833 people · 2019
2/2 SYR4
Trichloroacetic Acid
28.975 µg/L
No EPA limit set
Main supplier: LEETONIA VILLAGE PWS · 1,833 people · 2019
2/2 SYR4
Lead
22.79 µg/L 152%
of the EPA limit, at the 95th percentile of samples — 15 µg/L
Main supplier: LEETONIA VILLAGE PWS · 1,833 people · 2019
2/2 SYR4
Monobromoacetic Acid
17.185 µg/L
No EPA limit set
Main supplier: LEETONIA VILLAGE PWS · 1,833 people · 2019
2/2 SYR4
Bromodichloromethane
14.25 µg/L
No EPA limit set
Main supplier: LEETONIA VILLAGE PWS · 1,833 people · 2019
2/2 SYR4
Bromoform
3.1 µg/L
No EPA limit set
Main supplier: LEETONIA VILLAGE PWS · 1,833 people · 2019
Highest in the city: 13.505 µg/L — NEW WATERFORD VILLAGE PWS · 1,238 people · 2019
2/2 SYR4
Dibromochloromethane
2.8215 µg/L
No EPA limit set
Main supplier: LEETONIA VILLAGE PWS · 1,833 people · 2019
Highest in the city: 9.125 µg/L — NEW WATERFORD VILLAGE PWS · 1,238 people · 2019
2/2 SYR4
Dibromoacetic Acid
8.153 µg/L
No EPA limit set
Main supplier: LEETONIA VILLAGE PWS · 1,833 people · 2019
2/2 SYR4
Chromium
5.594 µg/L 5.6%
of the EPA limit 100 µg/L
Highest in the city: NEW WATERFORD VILLAGE PWS · 1,238 people · 2019
1/2 SYR4
Monochloroacetic Acid
4.8 µg/L
No EPA limit set
Main supplier: LEETONIA VILLAGE PWS · 1,833 people · 2019
2/2 SYR4
Gross Beta Particle Activity
3.686 pCi/L
No EPA limit set
Highest in the city: NEW WATERFORD VILLAGE PWS · 1,238 people · 2019
1/2 SYR4
Arsenic
2.21 µg/L 22%
of the EPA limit 10 µg/L
Highest in the city: NEW WATERFORD VILLAGE PWS · 1,238 people · 2019
1/2 SYR4
Selenium
1.829 µg/L 3.7%
of the EPA limit 50 µg/L
Highest in the city: NEW WATERFORD VILLAGE PWS · 1,238 people · 2019
1/2 SYR4
Lead
0.0164 mg/L 109%
above the EPA limit of 0.0150 mg/L
Main supplier: LEETONIA VILLAGE PWS · 1,833 people · 2025
2/2 LCR
Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of the system's samples — over 100% is worth reading, but is not by itself a violation. Formal violations are listed separately. These are the utilities' own EPA-reported results, not a city-wide average. A detection means the lab measured the substance — it isn't the same as exceeding a legal limit. Hover a source tag to see the EPA program and years behind each figure.

Water suppliers serving New Waterford

SupplierPopulation served
LEETONIA VILLAGE PWS 1,833
NEW WATERFORD VILLAGE PWS 1,238

Frequently asked questions about New Waterford tap water

Is New Waterford tap water safe to drink?

EPA testing detected 22 contaminants in the water serving New Waterford. A detection isn't the same as a violation — most detected levels are within federal limits. Check the level and source for each contaminant above, and your utility's annual Consumer Confidence Report for the official compliance status.

How many water suppliers serve New Waterford?

2 public water suppliers report drinking-water monitoring for New Waterford, Ohio to the EPA. Each is listed above with its population served.

What contaminants are in New Waterford's water?

The contaminants EPA monitoring detected in New Waterford include Nitrate-Nitrite, Nitrate, Fluoride, Copper, Barium. The full list, with the level at the main supplier and the data source, is in the table above.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.