Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2015-07-01 → 2015-09-30 |
| MCL | Health-based | Resolved | 2015-07-01 → 2015-09-30 |
| MCL | Health-based | Resolved | 2015-07-01 → 2015-09-30 |
| MCL | Health-based | Resolved | 2015-07-01 → 2015-09-30 |
| MCL | Health-based | Resolved | 2015-04-01 → 2015-06-30 |
| MCL | Health-based | Resolved | 2015-04-01 → 2015-06-30 |
| MCL | Health-based | Resolved | 2015-04-01 → 2015-06-30 |
| MCL | Health-based | Resolved | 2015-04-01 → 2015-06-30 |
| MCL | Health-based | Resolved | 2014-07-01 → 2014-09-30 |
| MCL | Health-based | Resolved | 2014-07-01 → 2014-09-30 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Chloroform | 89.63 µg/L No EPA limit set
worst single sample: 138.3 µg/L | 58/58 | SYR4 | 2012–2019 |
| Dibromochloromethane | 2.8215 µg/L No EPA limit set
worst single sample: 4.28 µg/L | 58/58 | SYR4 | 2012–2019 |
| TTHM | 105.495 µg/L 132% of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 162 µg/L | 58/58 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 64.56 µg/L 108% of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 81 µg/L | 57/58 | SYR4 | 2012–2019 |
| Bromodichloromethane | 14.25 µg/L No EPA limit set
worst single sample: 20.5 µg/L | 56/58 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 28.975 µg/L No EPA limit set
worst single sample: 34 µg/L | 56/58 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 36.08 µg/L No EPA limit set
worst single sample: 43 µg/L | 53/58 | SYR4 | 2012–2019 |
| Copper | 141 µg/L 11% of the EPA limit 1300 µg/L
worst single sample: 374 µg/L | 40/40 | SYR4 | 2013–2019 |
| Lead | 0.0164 mg/L 109% above the EPA limit of 0.0150 mg/L | 20/20 | LCR | 2025 |
| Dibromoacetic Acid | 8.153 µg/L No EPA limit set
worst single sample: 18.1 µg/L | 15/58 | SYR4 | 2012–2019 |
| Lead | 22.79 µg/L 152% of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 41.9 µg/L | 15/40 | SYR4 | 2013–2019 |
| Monochloroacetic Acid | 4.8 µg/L No EPA limit set | 15/58 | SYR4 | 2012–2019 |
| Bromoform | 3.1 µg/L No EPA limit set | 7/58 | SYR4 | 2012–2019 |
| Monobromoacetic Acid | 17.185 µg/L No EPA limit set
worst single sample: 21.5 µg/L | 6/58 | SYR4 | 2012–2019 |
Utility contact
Frequently asked questions about Leetonia Village
Is Leetonia Village tap water safe to drink?
EPA monitoring detected 14 contaminants in Leetonia Village's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Leetonia Village's water?
EPA monitoring detected Chloroform, Dibromochloromethane, TTHM, Total Haloacetic Acids (HAA5), Bromodichloromethane, and others. The full list with the level and data source for each is above.
How many people does Leetonia Village serve?
Leetonia Village reports serving 1,833 people in Ohio, per its EPA record.
Has Leetonia Village had any water quality violations?
The EPA has 148 violations on file for Leetonia Village, of which 24 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.