← Louisiana

Tap water quality report

Farmerville, LA

EPA monitoring detected 30 contaminants across the 6 water suppliers serving Farmerville. A detection doesn't automatically mean the water is unsafe — see the level at the main supplier for each below, with its EPA source and period.

6
water suppliers
12,303
people served
30
contaminants found

What was found in Farmerville's water

The level at the city's main supplier, the highest level anywhere in the city, the EPA limit for each, and where every figure comes from.

ContaminantLevel vs EPA limitSuppliersSource
Nitrate-Nitrite
1000 µg/L 10%
of the EPA limit 10000 µg/L
Main supplier: TOWN OF FARMERVILLE WATER SYSTEM · 5,352 people · 2019
6/6 SYR4
Copper
400 µg/L 31%
of the EPA limit 1300 µg/L
Main supplier: TOWN OF FARMERVILLE WATER SYSTEM · 5,352 people · 2019
Highest in the city: 890 µg/L — UNION PARISH WATERWORKS DISTRICT 1 · 1,626 people · 2019
6/6 SYR4
Fluoride
340 µg/L 8.5%
of the EPA limit 4000 µg/L
Main supplier: TOWN OF FARMERVILLE WATER SYSTEM · 5,352 people · 2018
Highest in the city: 816.5 µg/L — ROCKY BRANCH WATER SYSTEM · 1,650 people · 2017
6/6 SYR4
TTHM
257 µg/L 321%
of the EPA limit, at the 95th percentile of samples — 80 µg/L
Main supplier: TOWN OF FARMERVILLE WATER SYSTEM · 5,352 people · 2019
Highest in the city: 333.12 µg/L — UNION PARISH WATERWORKS DISTRICT 1 · 1,626 people · 2019
6/6 SYR4
Bromoform
196.5 µg/L
No EPA limit set
Main supplier: TOWN OF FARMERVILLE WATER SYSTEM · 5,352 people · 2019
Highest in the city: 250.25 µg/L — UNION PARISH WATERWORKS DISTRICT 1 · 1,626 people · 2019
6/6 SYR4
Dibromochloromethane
55.54 µg/L
No EPA limit set
Main supplier: TOWN OF FARMERVILLE WATER SYSTEM · 5,352 people · 2019
Highest in the city: 119.1 µg/L — WARDS CHAPEL WATER SYSTEM · 1,620 people · 2019
6/6 SYR4
Barium
13.5 µg/L 0.7%
of the EPA limit 2000 µg/L
Main supplier: TOWN OF FARMERVILLE WATER SYSTEM · 5,352 people · 2018
Highest in the city: 60.75 µg/L — TRI-WATER SYSTEM · 1,302 people · 2018
6/6 SYR4
Total Haloacetic Acids (HAA5)
37.045 µg/L 62%
of the EPA limit 60 µg/L
Main supplier: TOWN OF FARMERVILLE WATER SYSTEM · 5,352 people · 2019
Highest in the city: 59.6 µg/L — WARDS CHAPEL WATER SYSTEM · 1,620 people · 2019
6/6 SYR4
Dibromoacetic Acid
30.005 µg/L
No EPA limit set
Main supplier: TOWN OF FARMERVILLE WATER SYSTEM · 5,352 people · 2019
Highest in the city: 50.68 µg/L — WARDS CHAPEL WATER SYSTEM · 1,620 people · 2019
6/6 SYR4
Bromodichloromethane
12.45 µg/L
No EPA limit set
Main supplier: TOWN OF FARMERVILLE WATER SYSTEM · 5,352 people · 2019
Highest in the city: 26.475 µg/L — SALEM WATER SYSTEM · 753 people · 2019
6/6 SYR4
Monobromoacetic Acid
5.51 µg/L
No EPA limit set
Main supplier: TOWN OF FARMERVILLE WATER SYSTEM · 5,352 people · 2019
Highest in the city: 20.1 µg/L — WARDS CHAPEL WATER SYSTEM · 1,620 people · 2019
6/6 SYR4
Asbestos
14.465 MFL 207%
of the EPA limit, at the 95th percentile of samples — 7 MFL
Highest in the city: UNION PARISH WATERWORKS DISTRICT 1 · 1,626 people · 2019
1/6 SYR4
Monochloroacetic Acid
7.385 µg/L
No EPA limit set
Main supplier: TOWN OF FARMERVILLE WATER SYSTEM · 5,352 people · 2019
Highest in the city: 13.7 µg/L — TRI-WATER SYSTEM · 1,302 people · 2019
4/6 SYR4
Lead
6.25 µg/L 42%
of the EPA limit 15 µg/L
Main supplier: TOWN OF FARMERVILLE WATER SYSTEM · 5,352 people · 2019
Highest in the city: 13.5 µg/L — WARDS CHAPEL WATER SYSTEM · 1,620 people · 2019
6/6 SYR4
Dichloroacetic Acid
5.266 µg/L
No EPA limit set
Main supplier: TOWN OF FARMERVILLE WATER SYSTEM · 5,352 people · 2019
Highest in the city: 13.1 µg/L — WARDS CHAPEL WATER SYSTEM · 1,620 people · 2019
6/6 SYR4
Selenium
0.5800 µg/L 1.2%
of the EPA limit 50 µg/L
Main supplier: TOWN OF FARMERVILLE WATER SYSTEM · 5,352 people · 2018
Highest in the city: 10 µg/L — UNION PARISH WATERWORKS DISTRICT 1 · 1,626 people · 2019
2/6 SYR4
Chloroform
4.28 µg/L
No EPA limit set
Main supplier: TOWN OF FARMERVILLE WATER SYSTEM · 5,352 people · 2019
Highest in the city: 7.54 µg/L — SALEM WATER SYSTEM · 753 people · 2019
6/6 SYR4
Di(2-ethylhexyl) Phthalate
7.52 µg/L 125%
of the EPA limit, at the 95th percentile of samples — 6 µg/L
Main supplier: TOWN OF FARMERVILLE WATER SYSTEM · 5,352 people · 2018
6/6 SYR4
Cyanide
6.6 µg/L 3.3%
of the EPA limit 200 µg/L
Highest in the city: UNION PARISH WATERWORKS DISTRICT 1 · 1,626 people · 2019
1/6 SYR4
Trichloroacetic Acid
2.67 µg/L
No EPA limit set
Main supplier: TOWN OF FARMERVILLE WATER SYSTEM · 5,352 people · 2019
Highest in the city: 5.145 µg/L — SALEM WATER SYSTEM · 753 people · 2019
6/6 SYR4
Gross Alpha, Excl. Radon And U
4.96 pCi/L 33%
of the EPA limit 15 pCi/L
Highest in the city: UNION PARISH WATERWORKS DISTRICT 1 · 1,626 people · 2019
1/6 SYR4
Gross Beta Particle Activity
1.1245 pCi/L
No EPA limit set
Main supplier: TOWN OF FARMERVILLE WATER SYSTEM · 5,352 people · 2018
Highest in the city: 3.568 pCi/L — UNION PARISH WATERWORKS DISTRICT 1 · 1,626 people · 2019
4/6 SYR4
Arsenic
1 µg/L 10%
of the EPA limit 10 µg/L
Main supplier: TOWN OF FARMERVILLE WATER SYSTEM · 5,352 people · 2018
Highest in the city: 2.7 µg/L — TRI-WATER SYSTEM · 1,302 people · 2018
5/6 SYR4
Dalapon
2.24 µg/L 1.1%
of the EPA limit 200 µg/L
Highest in the city: ROCKY BRANCH WATER SYSTEM · 1,650 people · 2017
2/6 SYR4
Combined Radium (-226 And -228)
0.8495 pCi/L 17%
of the EPA limit 5 pCi/L
Main supplier: TOWN OF FARMERVILLE WATER SYSTEM · 5,352 people · 2018
Highest in the city: 1.0471 pCi/L — ROCKY BRANCH WATER SYSTEM · 1,650 people · 2017
5/6 SYR4
Xylenes, Total
0.6200 µg/L 0%
of the EPA limit 10000 µg/L
Highest in the city: SALEM WATER SYSTEM · 753 people · 2018
1/6 SYR4
Benzo(A)Pyrene
0.0710 µg/L 35%
of the EPA limit 0.2000 µg/L
Highest in the city: ROCKY BRANCH WATER SYSTEM · 1,650 people · 2017
1/6 SYR4
Pfpea
0.0048 µg/L
No EPA limit set
Main supplier: TOWN OF FARMERVILLE WATER SYSTEM · 5,352 people · 2023
1/6 UCMR-5
Pfhpa
0.0035 µg/L
No EPA limit set
Main supplier: TOWN OF FARMERVILLE WATER SYSTEM · 5,352 people · 2023
1/6 UCMR-5
Lead
0.0013 mg/L 8.7%
of the EPA limit 0.0150 mg/L
Main supplier: TOWN OF FARMERVILLE WATER SYSTEM · 5,352 people · 2025
Highest in the city: 0.0016 mg/L — ROCKY BRANCH WATER SYSTEM · 1,650 people · 2025
6/6 LCR
Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of the system's samples — over 100% is worth reading, but is not by itself a violation. Formal violations are listed separately. These are the utilities' own EPA-reported results, not a city-wide average. A detection means the lab measured the substance — it isn't the same as exceeding a legal limit. Hover a source tag to see the EPA program and years behind each figure.

Water suppliers serving Farmerville

Frequently asked questions about Farmerville tap water

Is Farmerville tap water safe to drink?

EPA testing detected 30 contaminants in the water serving Farmerville. A detection isn't the same as a violation — most detected levels are within federal limits. Check the level and source for each contaminant above, and your utility's annual Consumer Confidence Report for the official compliance status.

How many water suppliers serve Farmerville?

6 public water suppliers report drinking-water monitoring for Farmerville, Louisiana to the EPA. Each is listed above with its population served.

What contaminants are in Farmerville's water?

The contaminants EPA monitoring detected in Farmerville include Nitrate-Nitrite, Copper, Fluoride, TTHM, Bromoform. The full list, with the level at the main supplier and the data source, is in the table above.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.