← Oklahoma

Tap water quality report

Lawton

EPA monitoring tested this supplier for 112 contaminants and detected 23. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

112
contaminants tested
23
detected
92,757
people served
30
health-based violations
Water source
Surface water
Ownership
Local government
Counties served
Comanche

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

30
health-based violations
166
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2005-10-01 → 2005-12-31
MCL Health-based Resolved 2005-10-01 → 2005-12-31
MCL Health-based Resolved 2005-10-01 → 2005-12-31
MCL Health-based Resolved 2005-10-01 → 2005-12-31
MCL Health-based Resolved 2005-10-01 → 2005-12-31
TT Health-based Resolved 2005-07-01 → 2005-09-30
TT Health-based Resolved 2005-07-01 → 2005-09-30
TT Health-based Resolved 2005-07-01 → 2005-09-30
TT Health-based Resolved 2005-07-01 → 2005-09-30
TT Health-based Resolved 2005-04-01 → 2005-06-30

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
TTHM
28.805 µg/L 36%
of the EPA limit 80 µg/L
worst single sample: 46.2 µg/L
160/164 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
8.708 µg/L 15%
of the EPA limit 60 µg/L
worst single sample: 15.5 µg/L
147/164 SYR4 2012–2019
Copper
357.9 µg/L 28%
of the EPA limit 1300 µg/L
worst single sample: 1250 µg/L
119/125 SYR4 2012–2019
Dibromochloromethane
11.4 µg/L
No EPA limit set
worst single sample: 18.4 µg/L
107/114 SYR4 2012–2019
Bromodichloromethane
8.394 µg/L
No EPA limit set
worst single sample: 9.22 µg/L
105/114 SYR4 2012–2019
Bromoform
12.1 µg/L
No EPA limit set
worst single sample: 20.1 µg/L
104/114 SYR4 2012–2019
Dibromoacetic Acid
5.4395 µg/L
No EPA limit set
worst single sample: 6.33 µg/L
94/112 SYR4 2012–2019
Dichloroacetic Acid
6.302 µg/L
No EPA limit set
worst single sample: 9.82 µg/L
87/112 SYR4 2012–2019
Chloroform
6.532 µg/L
No EPA limit set
worst single sample: 7.74 µg/L
72/114 SYR4 2012–2019
Chlorite
183.7 µg/L 18%
of the EPA limit 1000 µg/L
worst single sample: 208 µg/L
59/227 SYR4 2012–2019
Monobromoacetic Acid
1.6585 µg/L
No EPA limit set
worst single sample: 1.69 µg/L
24/112 SYR4 2012–2019
Fluoride
681 µg/L 17%
of the EPA limit 4000 µg/L
worst single sample: 790 µg/L
23/28 SYR4 2012–2019
Bromate
42.97 µg/L 430%
of the EPA limit, at the 95th percentile of samples — 10 µg/L
worst single sample: 76 µg/L
22/190 SYR4 2012–2019
Lead
0.0020 mg/L 13%
of the EPA limit 0.0150 mg/L
18/18 LCR 2025
Nitrate-Nitrite
719 µg/L 7.2%
of the EPA limit 10000 µg/L
worst single sample: 940 µg/L
18/19 SYR4 2012–2019
Lead
29.45 µg/L 196%
of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 31.1 µg/L
16/125 SYR4 2012–2019
Barium
191.2 µg/L 9.6%
of the EPA limit 2000 µg/L
worst single sample: 194 µg/L
8/8 SYR4 2012–2019
Nitrate
620 µg/L 6.2%
of the EPA limit 10000 µg/L
4/8 SYR4 2014–2015
Combined Radium (-226 And -228)
0.0935 pCi/L 1.9%
of the EPA limit 5 pCi/L
worst single sample: 0.0970 pCi/L
2/2 SYR4 2015
Trichloroacetic Acid
1.66 µg/L
No EPA limit set
worst single sample: 1.67 µg/L
2/112 SYR4 2012–2019
Gross Alpha, Excl. Radon And U
1.7 pCi/L 11%
of the EPA limit 15 pCi/L
1/2 SYR4 2015
Gross Beta Particle Activity
3.54 pCi/L
No EPA limit set
1/2 SYR4 2015
Monochloroacetic Acid
3.49 µg/L
No EPA limit set
1/112 SYR4 2012–2019
89 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalArsenicAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumCombined UraniumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneGlyphosateHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorNetfosaaNfdhaNmefosaaOxamylPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneLithiumO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
LAWTON
Phone
580-581-3301
Email
[email protected]

Frequently asked questions about Lawton

Is Lawton tap water safe to drink?

EPA monitoring detected 23 contaminants in Lawton's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Lawton's water?

EPA monitoring detected TTHM, Total Haloacetic Acids (HAA5), Copper, Dibromochloromethane, Bromodichloromethane, and others. The full list with the level and data source for each is above.

How many people does Lawton serve?

Lawton reports serving 92,757 people in Oklahoma, per its EPA record.

Has Lawton had any water quality violations?

The EPA has 166 violations on file for Lawton, of which 30 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.