What was found in Weatherford's water
The level at the city's main supplier, the highest level anywhere in the city, the EPA limit for each, and where every figure comes from.
| Contaminant | Level vs EPA limit | Suppliers | Source |
|---|---|---|---|
| Nitrate | 209 µg/L 2.1% of the EPA limit 10000 µg/L Main supplier: CITY OF WEATHERFORD · 35,903 people · 2019
Highest in the city: 5655.5 µg/L — S-ESTATES WSC · 477 people · 2019 | 9/10 | SYR4 |
| Nitrate-Nitrite | 5076 µg/L 51% of the EPA limit 10000 µg/L Highest in the city: S-ESTATES WSC · 477 people · 2015 | 7/10 | SYR4 |
| Chlorite | 685.5 µg/L 69% of the EPA limit 1000 µg/L Main supplier: CITY OF WEATHERFORD · 35,903 people · 2019 | 1/10 | SYR4 |
| Fluoride | 592 µg/L 15% of the EPA limit 4000 µg/L Main supplier: CITY OF WEATHERFORD · 35,903 people · 2019 | 9/10 | SYR4 |
| Copper | 159.5 µg/L 12% of the EPA limit 1300 µg/L Main supplier: CITY OF WEATHERFORD · 35,903 people · 2019
Highest in the city: 374.6 µg/L — HARMONY WATER SYSTEM · 285 people · 2017 | 9/10 | SYR4 |
| Barium | 67.8 µg/L 3.4% of the EPA limit 2000 µg/L Main supplier: CITY OF WEATHERFORD · 35,903 people · 2019
Highest in the city: 170 µg/L — RIO BRAZOS WSC · 657 people · 2018 | 9/10 | SYR4 |
| Nitrite | 147.5 µg/L 15% of the EPA limit 1000 µg/L Highest in the city: WEST PARK ADDITION · 144 people · 2018 | 1/10 | SYR4 |
| Cyanide | 141.55 µg/L 71% of the EPA limit 200 µg/L Main supplier: CITY OF WEATHERFORD · 35,903 people · 2019 | 5/10 | SYR4 |
| TTHM | 81.86 µg/L 102% of the EPA limit, at the 95th percentile of samples — 80 µg/L Main supplier: CITY OF WEATHERFORD · 35,903 people · 2019 | 6/10 | SYR4 |
| Total Haloacetic Acids (HAA5) | 46.74 µg/L 78% of the EPA limit 60 µg/L Main supplier: CITY OF WEATHERFORD · 35,903 people · 2019 | 7/10 | SYR4 |
| Chloroform | 35.26 µg/L No EPA limit set Main supplier: CITY OF WEATHERFORD · 35,903 people · 2019 | 5/10 | SYR4 |
| Gross Alpha, Excl. Radon And U | 33.9 pCi/L 226% of the EPA limit, at the 95th percentile of samples — 15 pCi/L Highest in the city: HIGHLAND COURT · 90 people · 2019 | 5/10 | SYR4 |
| Dichloroacetic Acid | 32.3 µg/L No EPA limit set Main supplier: CITY OF WEATHERFORD · 35,903 people · 2019 | 3/10 | SYR4 |
| Bromodichloromethane | 28.82 µg/L No EPA limit set Main supplier: CITY OF WEATHERFORD · 35,903 people · 2019 | 6/10 | SYR4 |
| Bromoform | 8.13 µg/L No EPA limit set Main supplier: CITY OF WEATHERFORD · 35,903 people · 2019
Highest in the city: 28.72 µg/L — RIO BRAZOS WSC · 657 people · 2019 | 6/10 | SYR4 |
| Dibromochloromethane | 20.66 µg/L No EPA limit set Main supplier: CITY OF WEATHERFORD · 35,903 people · 2019
Highest in the city: 27.03 µg/L — RIO BRAZOS WSC · 657 people · 2019 | 7/10 | SYR4 |
| Monochloroacetic Acid | 6.34 µg/L No EPA limit set Main supplier: CITY OF WEATHERFORD · 35,903 people · 2019
Highest in the city: 16.1 µg/L — WEST PARK ADDITION · 144 people · 2019 | 4/10 | SYR4 |
| Gross Beta Particle Activity | 4.2 pCi/L No EPA limit set Main supplier: CITY OF WEATHERFORD · 35,903 people · 2017
Highest in the city: 15.93 pCi/L — HIGHLAND COURT · 90 people · 2019 | 6/10 | SYR4 |
| Lead | 4.51 µg/L 30% of the EPA limit 15 µg/L Main supplier: CITY OF WEATHERFORD · 35,903 people · 2019
Highest in the city: 12.8 µg/L — RIO BRAZOS WSC · 657 people · 2019 | 9/10 | SYR4 |
| Trichloroacetic Acid | 9.59 µg/L No EPA limit set Main supplier: CITY OF WEATHERFORD · 35,903 people · 2019 | 3/10 | SYR4 |
| Combined Radium (-226 And -228) | 9.56 pCi/L 191% of the EPA limit, at the 95th percentile of samples — 5 pCi/L Highest in the city: HIGHLAND COURT · 90 people · 2019 | 7/10 | SYR4 |
| Dibromoacetic Acid | 8.88 µg/L No EPA limit set Main supplier: CITY OF WEATHERFORD · 35,903 people · 2019 | 5/10 | SYR4 |
| Combined Uranium | 1.2 µg/L 4% of the EPA limit 30 µg/L Main supplier: CITY OF WEATHERFORD · 35,903 people · 2017
Highest in the city: 8.45 µg/L — HIGHLAND COURT · 90 people · 2019 | 6/10 | SYR4 |
| Chromium | 1.2 µg/L 1.2% of the EPA limit 100 µg/L Main supplier: CITY OF WEATHERFORD · 35,903 people · 2019
Highest in the city: 5.969 µg/L — ECHO VALLEY WSC · 66 people · 2019 | 8/10 | SYR4 |
| Selenium | 2.06 µg/L 4.1% of the EPA limit 50 µg/L Main supplier: CITY OF WEATHERFORD · 35,903 people · 2019
Highest in the city: 3.5805 µg/L — HIGHLAND COURT · 90 people · 2019 | 5/10 | SYR4 |
| Monobromoacetic Acid | 3.35 µg/L No EPA limit set Main supplier: CITY OF WEATHERFORD · 35,903 people · 2019 | 2/10 | SYR4 |
| Arsenic | 3.317 µg/L 33% of the EPA limit 10 µg/L Main supplier: CITY OF WEATHERFORD · 35,903 people · 2019 | 4/10 | SYR4 |
| Xylenes, Total | 2.908 µg/L 0% of the EPA limit 10000 µg/L Highest in the city: RIO BRAZOS WSC · 657 people · 2019 | 2/10 | SYR4 |
| Di(2-ethylhexyl) Phthalate | 0.6960 µg/L 12% of the EPA limit 6 µg/L Highest in the city: RIO BRAZOS WSC · 657 people · 2019 | 1/10 | SYR4 |
| Ethylbenzene | 0.6530 µg/L 0.1% of the EPA limit 700 µg/L Highest in the city: RIO BRAZOS WSC · 657 people · 2019 | 1/10 | SYR4 |
| Trichloroethylene | 0.5800 µg/L 12% of the EPA limit 5 µg/L Highest in the city: ECHO VALLEY WSC · 66 people · 2019 | 1/10 | SYR4 |
| Antimony, Total | 0.2120 µg/L 3.5% of the EPA limit 6 µg/L Highest in the city: HARMONY WATER SYSTEM · 285 people · 2015 | 1/10 | SYR4 |
| Pfba | 0.0120 µg/L No EPA limit set Main supplier: CITY OF WEATHERFORD · 35,903 people · 2024 | 1/10 | UCMR-5 |
| PFOS | 0.0054 µg/L No EPA limit set Main supplier: CITY OF WEATHERFORD · 35,903 people · 2024 | 1/10 | UCMR-5 |
| Pfpea | 0.0051 µg/L No EPA limit set Main supplier: CITY OF WEATHERFORD · 35,903 people · 2024 | 1/10 | UCMR-5 |
| PFBS | 0.0050 µg/L No EPA limit set Main supplier: CITY OF WEATHERFORD · 35,903 people · 2024 | 1/10 | UCMR-5 |
| Pfhxa | 0.0043 µg/L No EPA limit set Main supplier: CITY OF WEATHERFORD · 35,903 people · 2024 | 1/10 | UCMR-5 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L Main supplier: CITY OF WEATHERFORD · 35,903 people · 2025
Highest in the city: 0.0042 mg/L — HARMONY WATER SYSTEM · 285 people · 2024 | 10/10 | LCR |
Water suppliers serving Weatherford
| Supplier | Population served |
|---|---|
| CITY OF WEATHERFORD | 35,903 |
| RIO BRAZOS WSC | 657 |
| S-ESTATES WSC | 477 |
| BLUE RIDGE WATER SYSTEM | 285 |
| HARMONY WATER SYSTEM | 285 |
| OAK HILL MHP EAST | 216 |
| WEST PARK ADDITION | 144 |
| HIGHLAND COURT | 90 |
| FRYSINGER INVESTMENTS | 75 |
| ECHO VALLEY WSC | 66 |
Frequently asked questions about Weatherford tap water
Is Weatherford tap water safe to drink?
EPA testing detected 38 contaminants in the water serving Weatherford. A detection isn't the same as a violation — most detected levels are within federal limits. Check the level and source for each contaminant above, and your utility's annual Consumer Confidence Report for the official compliance status.
How many water suppliers serve Weatherford?
10 public water suppliers report drinking-water monitoring for Weatherford, Texas to the EPA. Each is listed above with its population served.
What contaminants are in Weatherford's water?
The contaminants EPA monitoring detected in Weatherford include Nitrate, Nitrate-Nitrite, Chlorite, Fluoride, Copper. The full list, with the level at the main supplier and the data source, is in the table above.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.