What was found in Sellersville's water
The level at the city's main supplier, the highest level anywhere in the city, the EPA limit for each, and where every figure comes from.
| Contaminant | Level vs EPA limit | Suppliers | Source |
|---|---|---|---|
| Nitrate | 788 µg/L 7.9% of the EPA limit 10000 µg/L Main supplier: PERKASIE REGIONAL AUTHORITY · 15,000 people · 2019
Highest in the city: 1650 µg/L — HILLTOWN TWP WATER&SEWER AUTH · 5,770 people · 2019 | 2/3 | SYR4 |
| Fluoride | 943.2 µg/L 24% of the EPA limit 4000 µg/L Main supplier: PERKASIE REGIONAL AUTHORITY · 15,000 people · 2017 | 2/3 | SYR4 |
| Copper | 518.1 µg/L 40% of the EPA limit 1300 µg/L Main supplier: PERKASIE REGIONAL AUTHORITY · 15,000 people · 2019 | 3/3 | SYR4 |
| Barium | 106.92 µg/L 5.3% of the EPA limit 2000 µg/L Main supplier: PERKASIE REGIONAL AUTHORITY · 15,000 people · 2013
Highest in the city: 172 µg/L — HILLTOWN TWP WATER&SEWER AUTH · 5,770 people · 2018 | 2/3 | SYR4 |
| TTHM | 38.025 µg/L 48% of the EPA limit 80 µg/L Main supplier: PERKASIE REGIONAL AUTHORITY · 15,000 people · 2019
Highest in the city: 56.64 µg/L — RESERVE AND RIDGE AT HILLTOWN · 300 people · 2019 | 3/3 | SYR4 |
| Chloroform | 13.91 µg/L No EPA limit set Main supplier: PERKASIE REGIONAL AUTHORITY · 15,000 people · 2019
Highest in the city: 43.55 µg/L — RESERVE AND RIDGE AT HILLTOWN · 300 people · 2019 | 3/3 | SYR4 |
| Trichloroethylene | 38.475 µg/L 770% of the EPA limit, at the 95th percentile of samples — 5 µg/L Main supplier: PERKASIE REGIONAL AUTHORITY · 15,000 people · 2019 | 1/3 | SYR4 |
| Lithium | 19.5 µg/L No EPA limit set Main supplier: PERKASIE REGIONAL AUTHORITY · 15,000 people · 2024
Highest in the city: 22.7 µg/L — HILLTOWN TWP WATER&SEWER AUTH · 5,770 people · 2025 | 2/3 | UCMR-5 |
| Lead | 8.8 µg/L 59% of the EPA limit 15 µg/L Main supplier: PERKASIE REGIONAL AUTHORITY · 15,000 people · 2019
Highest in the city: 22.015 µg/L — HILLTOWN TWP WATER&SEWER AUTH · 5,770 people · 2019 | 3/3 | SYR4 |
| cis-1,2-Dichloroethylene | 15.9 µg/L 23% of the EPA limit 70 µg/L Main supplier: PERKASIE REGIONAL AUTHORITY · 15,000 people · 2019 | 1/3 | SYR4 |
| Arsenic | 15.7 µg/L 157% of the EPA limit, at the 95th percentile of samples — 10 µg/L Main supplier: PERKASIE REGIONAL AUTHORITY · 15,000 people · 2019 | 2/3 | SYR4 |
| Total Haloacetic Acids (HAA5) | 7.89 µg/L 13% of the EPA limit 60 µg/L Main supplier: PERKASIE REGIONAL AUTHORITY · 15,000 people · 2019
Highest in the city: 13.58 µg/L — RESERVE AND RIDGE AT HILLTOWN · 300 people · 2019 | 3/3 | SYR4 |
| Bromodichloromethane | 12.3 µg/L No EPA limit set Main supplier: PERKASIE REGIONAL AUTHORITY · 15,000 people · 2019
Highest in the city: 12.925 µg/L — HILLTOWN TWP WATER&SEWER AUTH · 5,770 people · 2019 | 3/3 | SYR4 |
| Combined Uranium | 5.97974 µg/L 20% of the EPA limit 30 µg/L Main supplier: PERKASIE REGIONAL AUTHORITY · 15,000 people · 2018
Highest in the city: 10.8365 µg/L — HILLTOWN TWP WATER&SEWER AUTH · 5,770 people · 2018 | 2/3 | SYR4 |
| Trichloroacetic Acid | 7.917 µg/L No EPA limit set Main supplier: PERKASIE REGIONAL AUTHORITY · 15,000 people · 2019
Highest in the city: 10.5 µg/L — RESERVE AND RIDGE AT HILLTOWN · 300 people · 2019 | 3/3 | SYR4 |
| Dichloroacetic Acid | 9.58 µg/L No EPA limit set Main supplier: PERKASIE REGIONAL AUTHORITY · 15,000 people · 2019 | 3/3 | SYR4 |
| Dibromochloromethane | 9.045 µg/L No EPA limit set Main supplier: PERKASIE REGIONAL AUTHORITY · 15,000 people · 2019 | 3/3 | SYR4 |
| Cyanide | 8 µg/L 4% of the EPA limit 200 µg/L Highest in the city: HILLTOWN TWP WATER&SEWER AUTH · 5,770 people · 2018 | 1/3 | SYR4 |
| 1,1-Dichloroethylene | 7.02 µg/L 100% of the EPA limit, at the 95th percentile of samples — 7 µg/L Main supplier: PERKASIE REGIONAL AUTHORITY · 15,000 people · 2019 | 1/3 | SYR4 |
| Tetrachloroethylene | 5.8 µg/L 116% of the EPA limit, at the 95th percentile of samples — 5 µg/L Main supplier: PERKASIE REGIONAL AUTHORITY · 15,000 people · 2019 | 1/3 | SYR4 |
| Selenium | 4.825 µg/L 9.7% of the EPA limit 50 µg/L Main supplier: PERKASIE REGIONAL AUTHORITY · 15,000 people · 2018 | 1/3 | SYR4 |
| 1,1,1-Trichloroethane | 3.84 µg/L 1.9% of the EPA limit 200 µg/L Main supplier: PERKASIE REGIONAL AUTHORITY · 15,000 people · 2019 | 1/3 | SYR4 |
| Chromium | 3.3 µg/L 3.3% of the EPA limit 100 µg/L Main supplier: PERKASIE REGIONAL AUTHORITY · 15,000 people · 2012 | 2/3 | SYR4 |
| Dibromoacetic Acid | 1.7065 µg/L No EPA limit set Main supplier: PERKASIE REGIONAL AUTHORITY · 15,000 people · 2019
Highest in the city: 2.95 µg/L — HILLTOWN TWP WATER&SEWER AUTH · 5,770 people · 2019 | 2/3 | SYR4 |
| Bromoform | 2.889 µg/L No EPA limit set Main supplier: PERKASIE REGIONAL AUTHORITY · 15,000 people · 2019 | 3/3 | SYR4 |
| Dichloromethane | 1.96 µg/L 39% of the EPA limit 5 µg/L Main supplier: PERKASIE REGIONAL AUTHORITY · 15,000 people · 2019 | 1/3 | SYR4 |
| Carbon Tetrachloride | 0.5000 µg/L 10% of the EPA limit 5 µg/L Main supplier: PERKASIE REGIONAL AUTHORITY · 15,000 people · 2019 | 1/3 | SYR4 |
| Thallium, Total | 0.2400 µg/L 12% of the EPA limit 2 µg/L Main supplier: PERKASIE REGIONAL AUTHORITY · 15,000 people · 2012 | 1/3 | SYR4 |
| Antimony, Total | 0.2255 µg/L 3.8% of the EPA limit 6 µg/L Main supplier: PERKASIE REGIONAL AUTHORITY · 15,000 people · 2012 | 1/3 | SYR4 |
| Cadmium | 0.1100 µg/L 2.2% of the EPA limit 5 µg/L Main supplier: PERKASIE REGIONAL AUTHORITY · 15,000 people · 2012 | 1/3 | SYR4 |
| Mercury | 0.0772 µg/L 3.9% of the EPA limit 2 µg/L Main supplier: PERKASIE REGIONAL AUTHORITY · 15,000 people · 2013 | 1/3 | SYR4 |
| Beryllium, Total | 0.0700 µg/L 1.8% of the EPA limit 4 µg/L Main supplier: PERKASIE REGIONAL AUTHORITY · 15,000 people · 2012 | 1/3 | SYR4 |
| PFOS | 0.0176 µg/L No EPA limit set Main supplier: PERKASIE REGIONAL AUTHORITY · 15,000 people · 2024 | 2/3 | UCMR-5 |
| PFOA | 0.0065 µg/L No EPA limit set Main supplier: PERKASIE REGIONAL AUTHORITY · 15,000 people · 2024
Highest in the city: 0.0080 µg/L — HILLTOWN TWP WATER&SEWER AUTH · 5,770 people · 2025 | 2/3 | UCMR-5 |
| Pfpea | 0.0066 µg/L No EPA limit set Highest in the city: HILLTOWN TWP WATER&SEWER AUTH · 5,770 people · 2025 | 1/3 | UCMR-5 |
| PFBS | 0.0049 µg/L No EPA limit set Main supplier: PERKASIE REGIONAL AUTHORITY · 15,000 people · 2024
Highest in the city: 0.0057 µg/L — HILLTOWN TWP WATER&SEWER AUTH · 5,770 people · 2025 | 2/3 | UCMR-5 |
| Pfhxa | 0.0055 µg/L No EPA limit set Highest in the city: HILLTOWN TWP WATER&SEWER AUTH · 5,770 people · 2025 | 1/3 | UCMR-5 |
| PFHXS | 0.0051 µg/L No EPA limit set Main supplier: PERKASIE REGIONAL AUTHORITY · 15,000 people · 2024 | 1/3 | UCMR-5 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L Main supplier: PERKASIE REGIONAL AUTHORITY · 15,000 people · 2025
Highest in the city: 0.0025 mg/L — HILLTOWN TWP WATER&SEWER AUTH · 5,770 people · 2025 | 2/3 | LCR |
Water suppliers serving Sellersville
| Supplier | Population served |
|---|---|
| PERKASIE REGIONAL AUTHORITY | 15,000 |
| HILLTOWN TWP WATER&SEWER AUTH | 5,770 |
| RESERVE AND RIDGE AT HILLTOWN | 300 |
Frequently asked questions about Sellersville tap water
Is Sellersville tap water safe to drink?
EPA testing detected 39 contaminants in the water serving Sellersville. A detection isn't the same as a violation — most detected levels are within federal limits. Check the level and source for each contaminant above, and your utility's annual Consumer Confidence Report for the official compliance status.
How many water suppliers serve Sellersville?
3 public water suppliers report drinking-water monitoring for Sellersville, Pennsylvania to the EPA. Each is listed above with its population served.
What contaminants are in Sellersville's water?
The contaminants EPA monitoring detected in Sellersville include Nitrate, Fluoride, Copper, Barium, TTHM. The full list, with the level at the main supplier and the data source, is in the table above.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.