← Pennsylvania

Tap water quality report

Wilkinsburg, PA

EPA monitoring detected 18 contaminants across the 1 water supplier serving Wilkinsburg. A detection doesn't automatically mean the water is unsafe — see the level at the main supplier for each below, with its EPA source and period.

1
water supplier
125,000
people served
18
contaminants found

What was found in Wilkinsburg's water

The level at the city's main supplier, the highest level anywhere in the city, the EPA limit for each, and where every figure comes from.

ContaminantLevel vs EPA limitSuppliersSource
Fluoride
889.2 µg/L 22%
of the EPA limit 4000 µg/L
Main supplier: WILKINSBURG-PENN JT WATER AUTH · 125,000 people · 2019
1/1 SYR4
Nitrate
750 µg/L 7.5%
of the EPA limit 10000 µg/L
Main supplier: WILKINSBURG-PENN JT WATER AUTH · 125,000 people · 2019
1/1 SYR4
Copper
150.4 µg/L 12%
of the EPA limit 1300 µg/L
Main supplier: WILKINSBURG-PENN JT WATER AUTH · 125,000 people · 2019
1/1 SYR4
Nitrite
120 µg/L 12%
of the EPA limit 1000 µg/L
Main supplier: WILKINSBURG-PENN JT WATER AUTH · 125,000 people · 2019
1/1 SYR4
TTHM
94.09 µg/L 118%
of the EPA limit, at the 95th percentile of samples — 80 µg/L
Main supplier: WILKINSBURG-PENN JT WATER AUTH · 125,000 people · 2019
1/1 SYR4
Chloroform
67.19 µg/L
No EPA limit set
Main supplier: WILKINSBURG-PENN JT WATER AUTH · 125,000 people · 2019
1/1 SYR4
Total Haloacetic Acids (HAA5)
42 µg/L 70%
of the EPA limit 60 µg/L
Main supplier: WILKINSBURG-PENN JT WATER AUTH · 125,000 people · 2019
1/1 SYR4
Barium
40.8 µg/L 2%
of the EPA limit 2000 µg/L
Main supplier: WILKINSBURG-PENN JT WATER AUTH · 125,000 people · 2019
1/1 SYR4
Bromodichloromethane
28.89 µg/L
No EPA limit set
Main supplier: WILKINSBURG-PENN JT WATER AUTH · 125,000 people · 2019
1/1 SYR4
Lead
27.2 µg/L 181%
of the EPA limit, at the 95th percentile of samples — 15 µg/L
Main supplier: WILKINSBURG-PENN JT WATER AUTH · 125,000 people · 2019
1/1 SYR4
Dibromochloromethane
20.8 µg/L
No EPA limit set
Main supplier: WILKINSBURG-PENN JT WATER AUTH · 125,000 people · 2019
1/1 SYR4
Trichloroacetic Acid
14.2 µg/L
No EPA limit set
Main supplier: WILKINSBURG-PENN JT WATER AUTH · 125,000 people · 2019
1/1 SYR4
Dichloroacetic Acid
13.7 µg/L
No EPA limit set
Main supplier: WILKINSBURG-PENN JT WATER AUTH · 125,000 people · 2019
1/1 SYR4
Monochloroacetic Acid
10.748 µg/L
No EPA limit set
Main supplier: WILKINSBURG-PENN JT WATER AUTH · 125,000 people · 2019
1/1 SYR4
Bromoform
7.8215 µg/L
No EPA limit set
Main supplier: WILKINSBURG-PENN JT WATER AUTH · 125,000 people · 2019
1/1 SYR4
Dibromoacetic Acid
1.19 µg/L
No EPA limit set
Main supplier: WILKINSBURG-PENN JT WATER AUTH · 125,000 people · 2019
1/1 SYR4
Mercury
0.3000 µg/L 15%
of the EPA limit 2 µg/L
Main supplier: WILKINSBURG-PENN JT WATER AUTH · 125,000 people · 2019
1/1 SYR4
Lead
0.0098 mg/L 65%
of the EPA limit 0.0150 mg/L
Main supplier: WILKINSBURG-PENN JT WATER AUTH · 125,000 people · 2025
1/1 LCR
Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of the system's samples — over 100% is worth reading, but is not by itself a violation. Formal violations are listed separately. These are the utilities' own EPA-reported results, not a city-wide average. A detection means the lab measured the substance — it isn't the same as exceeding a legal limit. Hover a source tag to see the EPA program and years behind each figure.

Water suppliers serving Wilkinsburg

SupplierPopulation served
WILKINSBURG-PENN JT WATER AUTH 125,000

Frequently asked questions about Wilkinsburg tap water

Is Wilkinsburg tap water safe to drink?

EPA testing detected 18 contaminants in the water serving Wilkinsburg. A detection isn't the same as a violation — most detected levels are within federal limits. Check the level and source for each contaminant above, and your utility's annual Consumer Confidence Report for the official compliance status.

How many water suppliers serve Wilkinsburg?

1 public water supplier report drinking-water monitoring for Wilkinsburg, Pennsylvania to the EPA. Each is listed above with its population served.

What contaminants are in Wilkinsburg's water?

The contaminants EPA monitoring detected in Wilkinsburg include Fluoride, Nitrate, Copper, Nitrite, TTHM. The full list, with the level at the main supplier and the data source, is in the table above.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.