← Wisconsin

Tap water quality report

Athens Waterworks

EPA monitoring tested this supplier for 74 contaminants and detected 18. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

74
contaminants tested
18
detected
1,025
people served
2
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Marathon

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

2
health-based violations
166
violations on file
3
still open
ViolationTypeStatusPeriod
TT Health-based Resolved 2018-05-02
TT Health-based Resolved 2018-05-02
MR Monitoring Archived 2025-01-01 → 2025-12-31
MR Monitoring Archived 2025-01-01 → 2025-12-31
MR Monitoring Archived 2025-01-01 → 2025-12-31
MR Monitoring Archived 2025-01-01 → 2025-12-31
MON Monitoring Resolved 2024-05-01 → 2024-05-31
MON Monitoring Resolved 2024-05-01 → 2024-05-31
MON Monitoring Resolved 2024-05-01 → 2024-05-31
MON Monitoring Resolved 2024-05-01 → 2024-05-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Fluoride
1102 µg/L 28%
of the EPA limit 4000 µg/L
worst single sample: 1190 µg/L
97/194 SYR4 2012–2019
Copper
69 µg/L 5.3%
of the EPA limit 1300 µg/L
worst single sample: 103 µg/L
18/20 SYR4 2014–2017
Nitrate
4500 µg/L 45%
of the EPA limit 10000 µg/L
16/16 SYR4 2012–2019
Lead
0.0120 mg/L 80%
of the EPA limit 0.0150 mg/L
14/14 LCR 2023
Lead
11 µg/L 73%
of the EPA limit 15 µg/L
9/20 SYR4 2014–2017
Chloroform
3.67 µg/L
No EPA limit set
worst single sample: 3.7 µg/L
7/7 SYR4 2014–2019
Dibromochloromethane
4.65 µg/L
No EPA limit set
worst single sample: 4.8 µg/L
7/7 SYR4 2014–2019
Bromodichloromethane
4.275 µg/L
No EPA limit set
worst single sample: 4.4 µg/L
6/7 SYR4 2014–2019
Bromoform
2.125 µg/L
No EPA limit set
worst single sample: 2.2 µg/L
6/7 SYR4 2014–2019
TTHM
14.6 µg/L 18%
of the EPA limit 80 µg/L
worst single sample: 14.8 µg/L
6/6 SYR4 2014–2019
Total Haloacetic Acids (HAA5)
27.1427 µg/L 45%
of the EPA limit 60 µg/L
worst single sample: 30.003 µg/L
3/6 SYR4 2014–2019
Barium
99.84 µg/L 5%
of the EPA limit 2000 µg/L
worst single sample: 100 µg/L
2/2 SYR4 2014–2017
Dibromoacetic Acid
1.385 µg/L
No EPA limit set
worst single sample: 1.4 µg/L
2/6 SYR4 2014–2019
Nitrate-Nitrite
4326 µg/L 43%
of the EPA limit 10000 µg/L
worst single sample: 4370 µg/L
2/2 SYR4 2014–2017
Combined Radium (-226 And -228)
0.2900 pCi/L 5.8%
of the EPA limit 5 pCi/L
1/1 SYR4 2014
Gross Alpha, Excl. Radon And U
1.27 pCi/L 8.5%
of the EPA limit 15 pCi/L
1/1 SYR4 2014
Gross Beta Particle Activity
0.8600 pCi/L
No EPA limit set
1/1 SYR4 2014
Monochloroacetic Acid
29.7 µg/L
No EPA limit set
1/6 SYR4 2014–2019
56 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalArsenicAtrazineBhc-GammaBenzeneBeryllium, TotalChlorobenzeneCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumDichloromethaneDalaponDichloroacetic AcidDinosebDiquatEndothallEndrinEthylbenzeneGlyphosateHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidNitriteOxamylPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneToxapheneTrichloroacetic AcidTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Frequently asked questions about Athens Waterworks

Is Athens Waterworks tap water safe to drink?

EPA monitoring detected 18 contaminants in Athens Waterworks's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Athens Waterworks's water?

EPA monitoring detected Fluoride, Copper, Nitrate, Lead, Lead, and others. The full list with the level and data source for each is above.

How many people does Athens Waterworks serve?

Athens Waterworks reports serving 1,025 people in Wisconsin, per its EPA record.

Has Athens Waterworks had any water quality violations?

The EPA has 166 violations on file for Athens Waterworks, of which 2 are health-based (a contaminant limit or required treatment was breached) and 3 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.