Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Resolved | 2024-10-17 |
| TT | Health-based | Resolved | 2024-10-17 |
| TT | Health-based | Resolved | 1994-01-01 |
| Other | Monitoring | Resolved | 2024-10-17 |
| Other | Monitoring | Resolved | 2011-10-01 |
| Other | Monitoring | Resolved | 2011-10-01 |
| Other | Monitoring | Resolved | 2011-07-01 |
| Other | Monitoring | Resolved | 2011-07-01 |
| Other | Monitoring | Resolved | 2010-07-01 |
| Other | Monitoring | Resolved | 2010-07-01 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Fluoride | 860 µg/L 22% of the EPA limit 4000 µg/L
worst single sample: 900 µg/L | 98/193 | SYR4 | 2012–2019 |
| Nitrate | 6750 µg/L 68% of the EPA limit 10000 µg/L
worst single sample: 7000 µg/L | 66/66 | SYR4 | 2012–2019 |
| Copper | 1100 µg/L 85% of the EPA limit 1300 µg/L
worst single sample: 1300 µg/L | 41/41 | SYR4 | 2014–2017 |
| Lead | 8.77 µg/L 58% of the EPA limit 15 µg/L
worst single sample: 13 µg/L | 40/41 | SYR4 | 2014–2017 |
| Lead | 0.0130 mg/L 87% of the EPA limit 0.0150 mg/L | 17/17 | LCR | 2023 |
| Bromodichloromethane | 6.08 µg/L No EPA limit set
worst single sample: 6.2 µg/L | 13/13 | SYR4 | 2012–2019 |
| Dibromochloromethane | 4.6 µg/L No EPA limit set | 13/13 | SYR4 | 2012–2019 |
| Chloroform | 6.705 µg/L No EPA limit set
worst single sample: 7.2 µg/L | 12/13 | SYR4 | 2012–2019 |
| TTHM | 18.6 µg/L 23% of the EPA limit 80 µg/L
worst single sample: 18.9 µg/L | 7/7 | SYR4 | 2013–2019 |
| Total Haloacetic Acids (HAA5) | 2.776 µg/L 4.6% of the EPA limit 60 µg/L
worst single sample: 2.8 µg/L | 7/7 | SYR4 | 2013–2019 |
| Bromoform | 1.175 µg/L No EPA limit set
worst single sample: 1.2 µg/L | 6/12 | SYR4 | 2013–2019 |
| Dibromoacetic Acid | 0.8600 µg/L No EPA limit set
worst single sample: 0.8700 µg/L | 6/7 | SYR4 | 2013–2019 |
| Trichloroacetic Acid | 0.9850 µg/L No EPA limit set
worst single sample: 1 µg/L | 6/7 | SYR4 | 2013–2019 |
| Dichloroacetic Acid | 1.0835 µg/L No EPA limit set
worst single sample: 1.1 µg/L | 4/7 | SYR4 | 2013–2019 |
| Barium | 74.3 µg/L 3.7% of the EPA limit 2000 µg/L
worst single sample: 81 µg/L | 3/3 | SYR4 | 2014–2017 |
| Combined Uranium | 0.8830 µg/L 2.9% of the EPA limit 30 µg/L
worst single sample: 0.8900 µg/L | 3/3 | SYR4 | 2013–2014 |
| Nitrate-Nitrite | 6100 µg/L 61% of the EPA limit 10000 µg/L | 3/3 | SYR4 | 2014–2017 |
| Combined Radium (-226 And -228) | 1.0685 pCi/L 21% of the EPA limit 5 pCi/L
worst single sample: 1.1 pCi/L | 2/2 | SYR4 | 2013–2014 |
| Gross Alpha, Excl. Radon And U | 1.74333 pCi/L 12% of the EPA limit 15 pCi/L
worst single sample: 1.78 pCi/L | 2/2 | SYR4 | 2013–2014 |
| Arsenic | 1.9 µg/L 19% of the EPA limit 10 µg/L | 1/3 | SYR4 | 2014–2017 |
| Cyanide | 19 µg/L 9.5% of the EPA limit 200 µg/L | 1/1 | SYR4 | 2014 |
| Gross Beta Particle Activity | 2.16 pCi/L No EPA limit set | 1/1 | SYR4 | 2013 |
| Monobromoacetic Acid | 0.2200 µg/L No EPA limit set | 1/7 | SYR4 | 2013–2019 |
| Nitrite | 39 µg/L 3.9% of the EPA limit 1000 µg/L | 1/3 | SYR4 | 2014–2017 |
| Thallium, Total | 0.2200 µg/L 11% of the EPA limit 2 µg/L | 1/3 | SYR4 | 2014–2017 |
52 contaminants tested, none detected
Utility contact
Frequently asked questions about Chilton Waterworks
Is Chilton Waterworks tap water safe to drink?
EPA monitoring detected 25 contaminants in Chilton Waterworks's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Chilton Waterworks's water?
EPA monitoring detected Fluoride, Nitrate, Copper, Lead, Lead, and others. The full list with the level and data source for each is above.
How many people does Chilton Waterworks serve?
Chilton Waterworks reports serving 4,191 people in Wisconsin, per its EPA record.
Has Chilton Waterworks had any water quality violations?
The EPA has 10 violations on file for Chilton Waterworks, of which 3 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.