Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2000-08-01 → 2000-08-31 |
| MCL | Health-based | Resolved | 2000-08-01 → 2000-08-31 |
| MCL | Health-based | Resolved | 1995-05-01 → 1995-05-31 |
| MCL | Health-based | Resolved | 1995-05-01 → 1995-05-31 |
| MCL | Health-based | Resolved | 1995-05-01 → 1995-05-31 |
| MCL | Health-based | Resolved | 1995-05-01 → 1995-05-31 |
| MR | Monitoring | Resolved | 2014-01-01 → 2014-12-31 |
| MR | Monitoring | Resolved | 2014-01-01 → 2014-12-31 |
| MR | Monitoring | Resolved | 2014-01-01 → 2014-12-31 |
| MR | Monitoring | Resolved | 2014-01-01 → 2014-12-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Fluoride | 1250 µg/L 31% of the EPA limit 4000 µg/L
worst single sample: 1310 µg/L | 98/194 | SYR4 | 2012–2019 |
| Copper | 184.95 µg/L 14% of the EPA limit 1300 µg/L
worst single sample: 205 µg/L | 40/40 | SYR4 | 2014–2017 |
| Combined Radium (-226 And -228) | 6.08 pCi/L 122% of the EPA limit, at the 95th percentile of samples — 5 pCi/L
worst single sample: 6.8 pCi/L | 19/19 | SYR4 | 2012–2019 |
| Gross Alpha, Excl. Radon And U | 10.33 pCi/L 69% of the EPA limit 15 pCi/L
worst single sample: 12.2 pCi/L | 18/18 | SYR4 | 2013–2019 |
| Lead | 0.0012 mg/L 8% of the EPA limit 0.0150 mg/L | 15/15 | LCR | 2023 |
| Chloroform | 3.92 µg/L No EPA limit set
worst single sample: 4.1 µg/L | 13/17 | SYR4 | 2013–2019 |
| Bromodichloromethane | 2 µg/L No EPA limit set | 10/17 | SYR4 | 2013–2019 |
| Lead | 9.18 µg/L 61% of the EPA limit 15 µg/L
worst single sample: 12.6 µg/L | 10/40 | SYR4 | 2014–2017 |
| TTHM | 7.042 µg/L 8.8% of the EPA limit 80 µg/L
worst single sample: 7.24 µg/L | 10/10 | SYR4 | 2015–2019 |
| Total Haloacetic Acids (HAA5) | 1.607 µg/L 2.7% of the EPA limit 60 µg/L
worst single sample: 1.67 µg/L | 10/10 | SYR4 | 2015–2019 |
| Dichloroacetic Acid | 0.8500 µg/L No EPA limit set
worst single sample: 0.8600 µg/L | 6/10 | SYR4 | 2015–2019 |
| Trichloroacetic Acid | 0.6720 µg/L No EPA limit set
worst single sample: 0.6900 µg/L | 4/10 | SYR4 | 2015–2019 |
| Barium | 81.125 µg/L 4.1% of the EPA limit 2000 µg/L
worst single sample: 81.2 µg/L | 2/2 | SYR4 | 2014–2017 |
| Dibromoacetic Acid | 0.1690 µg/L No EPA limit set
worst single sample: 0.1700 µg/L | 2/10 | SYR4 | 2015–2019 |
| Nitrate | 190 µg/L 1.9% of the EPA limit 10000 µg/L | 2/16 | SYR4 | 2012–2019 |
| Tetrachloroethylene | 1.395 µg/L 28% of the EPA limit 5 µg/L
worst single sample: 1.4 µg/L | 2/10 | SYR4 | 2012–2019 |
| Dibromochloromethane | 1.4 µg/L No EPA limit set | 1/17 | SYR4 | 2013–2019 |
| Gross Beta Particle Activity | 2.7 pCi/L No EPA limit set | 1/1 | SYR4 | 2014 |
87 contaminants tested, none detected
Utility contact
Frequently asked questions about Waupun Utilities
Is Waupun Utilities tap water safe to drink?
EPA monitoring detected 18 contaminants in Waupun Utilities's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Waupun Utilities's water?
EPA monitoring detected Fluoride, Copper, Combined Radium (-226 And -228), Gross Alpha, Excl. Radon And U, Lead, and others. The full list with the level and data source for each is above.
How many people does Waupun Utilities serve?
Waupun Utilities reports serving 8,056 people in Wisconsin, per its EPA record.
Has Waupun Utilities had any water quality violations?
The EPA has 18 violations on file for Waupun Utilities, of which 6 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.