Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Resolved | 2021-11-01 |
| TT | Health-based | Resolved | 2021-11-01 |
| TT | Health-based | Resolved | 2021-11-01 |
| TT | Health-based | Resolved | 2021-11-01 |
| MCL | Health-based | Resolved | 1999-07-01 → 1999-07-31 |
| MCL | Health-based | Resolved | 1999-07-01 → 1999-07-31 |
| MCL | Health-based | Resolved | 1999-07-01 → 1999-07-31 |
| MR | Monitoring | Resolved | 2019-01-01 → 2019-12-31 |
| MR | Monitoring | Resolved | 2019-01-01 → 2019-12-31 |
| MR | Monitoring | Resolved | 2019-01-01 → 2019-12-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 326.6 µg/L 25% of the EPA limit 1300 µg/L
worst single sample: 470 µg/L | 22/23 | SYR4 | 2013–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 15/15 | LCR | 2023 |
| Lead | 24.51 µg/L 163% of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 31 µg/L | 12/22 | SYR4 | 2013–2019 |
| Chloroform | 56.895 µg/L No EPA limit set
worst single sample: 69.9 µg/L | 10/10 | SYR4 | 2013–2019 |
| Barium | 111.85 µg/L 5.6% of the EPA limit 2000 µg/L
worst single sample: 122 µg/L | 8/8 | SYR4 | 2013–2019 |
| Bromodichloromethane | 10.0985 µg/L No EPA limit set
worst single sample: 13 µg/L | 8/10 | SYR4 | 2013–2019 |
| TTHM | 70.53 µg/L 88% of the EPA limit 80 µg/L
worst single sample: 76.2 µg/L | 8/8 | SYR4 | 2013–2019 |
| Dibromochloromethane | 3.26 µg/L No EPA limit set
worst single sample: 3.8 µg/L | 7/10 | SYR4 | 2013–2019 |
| Nitrate-Nitrite | 3119 µg/L 31% of the EPA limit 10000 µg/L
worst single sample: 3170 µg/L | 7/7 | SYR4 | 2012–2018 |
| Total Haloacetic Acids (HAA5) | 13.3 µg/L 22% of the EPA limit 60 µg/L
worst single sample: 13.9 µg/L | 5/8 | SYR4 | 2013–2019 |
| Dichloroacetic Acid | 8.7975 µg/L No EPA limit set
worst single sample: 8.88 µg/L | 4/6 | SYR4 | 2013–2019 |
| Nitrate | 2700 µg/L 27% of the EPA limit 10000 µg/L | 4/4 | SYR4 | 2014–2015 |
| Fluoride | 191 µg/L 4.8% of the EPA limit 4000 µg/L
worst single sample: 200 µg/L | 3/10 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 4.791 µg/L No EPA limit set
worst single sample: 5.04 µg/L | 3/6 | SYR4 | 2013–2019 |
| Bromoform | 2.1 µg/L No EPA limit set | 1/10 | SYR4 | 2013–2019 |
| Combined Radium (-226 And -228) | 0.1000 pCi/L 2% of the EPA limit 5 pCi/L | 1/2 | SYR4 | 2012–2018 |
| Gross Beta Particle Activity | 3.7 pCi/L No EPA limit set | 1/2 | SYR4 | 2012–2018 |
63 contaminants tested, none detected
Utility contact
Frequently asked questions about North Spring Behavioral Healthcare
Is North Spring Behavioral Healthcare tap water safe to drink?
EPA monitoring detected 17 contaminants in North Spring Behavioral Healthcare's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in North Spring Behavioral Healthcare's water?
EPA monitoring detected Copper, Lead, Lead, Chloroform, Barium, and others. The full list with the level and data source for each is above.
How many people does North Spring Behavioral Healthcare serve?
North Spring Behavioral Healthcare reports serving 225 people in Virginia, per its EPA record.
Has North Spring Behavioral Healthcare had any water quality violations?
The EPA has 74 violations on file for North Spring Behavioral Healthcare, of which 7 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.