Compliance record
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Chloroform | 67.305 µg/L No EPA limit set
worst single sample: 85.4 µg/L | 234/234 | SYR4 | 2012–2019 |
| Bromodichloromethane | 20.925 µg/L No EPA limit set
worst single sample: 24.2 µg/L | 232/234 | SYR4 | 2012–2019 |
| Dibromochloromethane | 7.945 µg/L No EPA limit set
worst single sample: 16.9 µg/L | 231/234 | SYR4 | 2012–2019 |
| TTHM | 95.695 µg/L 120% of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 109 µg/L | 228/228 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 42.83 µg/L 71% of the EPA limit 60 µg/L
worst single sample: 54.1 µg/L | 228/228 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 24.625 µg/L No EPA limit set
worst single sample: 30.6 µg/L | 224/224 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 16.84 µg/L No EPA limit set
worst single sample: 21.4 µg/L | 224/224 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 2.94 µg/L No EPA limit set
worst single sample: 4.62 µg/L | 133/224 | SYR4 | 2012–2019 |
| Copper | 411.4 µg/L 32% of the EPA limit 1300 µg/L
worst single sample: 1340 µg/L | 103/113 | SYR4 | 2012–2019 |
| Bromoform | 1.582 µg/L No EPA limit set
worst single sample: 2.49 µg/L | 69/234 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 3.271 µg/L No EPA limit set
worst single sample: 3.38 µg/L | 52/224 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 4690 µg/L 47% of the EPA limit 10000 µg/L
worst single sample: 4800 µg/L | 32/32 | SYR4 | 2012–2019 |
| Lead | 4 µg/L 27% of the EPA limit 15 µg/L
worst single sample: 9 µg/L | 23/113 | SYR4 | 2012–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 13/13 | LCR | 2025 |
| Barium | 90.5 µg/L 4.5% of the EPA limit 2000 µg/L
worst single sample: 92 µg/L | 11/11 | SYR4 | 2012–2019 |
| Fluoride | 786.5 µg/L 20% of the EPA limit 4000 µg/L
worst single sample: 790 µg/L | 8/11 | SYR4 | 2012–2019 |
| Gross Beta Particle Activity | 4.935 pCi/L No EPA limit set
worst single sample: 5.48 pCi/L | 6/6 | SYR4 | 2013–2019 |
| Monobromoacetic Acid | 1.5885 µg/L No EPA limit set
worst single sample: 1.59 µg/L | 4/224 | SYR4 | 2012–2019 |
| Combined Radium (-226 And -228) | 0.4850 pCi/L 9.7% of the EPA limit 5 pCi/L
worst single sample: 0.5000 pCi/L | 2/2 | SYR4 | 2017–2019 |
87 contaminants tested, none detected
Utility contact
Frequently asked questions about Leesburg, Town of
Is Leesburg, Town of tap water safe to drink?
EPA monitoring detected 19 contaminants in Leesburg, Town of's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Leesburg, Town of's water?
EPA monitoring detected Chloroform, Bromodichloromethane, Dibromochloromethane, TTHM, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.
How many people does Leesburg, Town of serve?
Leesburg, Town of reports serving 65,028 people in Virginia, per its EPA record.
Has Leesburg, Town of had any water quality violations?
The EPA has no formal drinking-water violations on file for Leesburg, Town of.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.