← Virginia

Tap water quality report

Rocky Mount, Town of

EPA monitoring tested this supplier for 107 contaminants and detected 21. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

107
contaminants tested
21
detected
6,000
people served
4
health-based violations
Water source
Surface water
Ownership
Local government
Counties served
Franklin

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

4
health-based violations
16
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2015-07-01 → 2015-09-30
MCL Health-based Resolved 2015-07-01 → 2015-09-30
MCL Health-based Resolved 2015-07-01 → 2015-09-30
MCL Health-based Resolved 2015-07-01 → 2015-09-30
Other Monitoring Resolved 2020-07-01
Other Monitoring Resolved 2020-07-01
MR Monitoring Resolved 2013-10-01 → 2013-12-31
MR Monitoring Resolved 2013-10-01 → 2013-12-31
MR Monitoring Resolved 2013-10-01 → 2013-12-31
MR Monitoring Resolved 2013-10-01 → 2013-12-31

PFAS detected

PFAS are industrial “forever chemicals”. These are the EPA's latest nationwide test results (2023–2025).
ContaminantMaxDetection ratePeriod
Pfba 0.0069 µg/L 1/8 2024

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Bromodichloromethane
10.01 µg/L
No EPA limit set
worst single sample: 11.7 µg/L
59/59 SYR4 2012–2019
Chloroform
98.84 µg/L
No EPA limit set
worst single sample: 149 µg/L
59/59 SYR4 2012–2019
TTHM
107.665 µg/L 135%
of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 159 µg/L
58/58 SYR4 2012–2019
Dichloroacetic Acid
30.58 µg/L
No EPA limit set
worst single sample: 51.6 µg/L
57/57 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
80 µg/L 133%
of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 114 µg/L
57/57 SYR4 2012–2019
Trichloroacetic Acid
48.76 µg/L
No EPA limit set
worst single sample: 62.7 µg/L
57/57 SYR4 2012–2019
Monochloroacetic Acid
4.175 µg/L
No EPA limit set
worst single sample: 5.52 µg/L
51/57 SYR4 2012–2019
Dibromochloromethane
1.268 µg/L
No EPA limit set
worst single sample: 1.38 µg/L
45/59 SYR4 2012–2019
Copper
76.68 µg/L 5.9%
of the EPA limit 1300 µg/L
worst single sample: 229 µg/L
43/49 SYR4 2012–2019
Lead
3.72 µg/L 25%
of the EPA limit 15 µg/L
worst single sample: 6.1 µg/L
27/49 SYR4 2012–2019
Lead
0.00037 mg/L 2.5%
of the EPA limit 0.0150 mg/L
15/15 LCR 2023
Fluoride
810 µg/L 20%
of the EPA limit 4000 µg/L
worst single sample: 830 µg/L
9/9 SYR4 2012–2019
Barium
21.985 µg/L 1.1%
of the EPA limit 2000 µg/L
worst single sample: 22.3 µg/L
8/8 SYR4 2012–2019
Nitrate-Nitrite
1002.5 µg/L 10%
of the EPA limit 10000 µg/L
worst single sample: 1020 µg/L
8/8 SYR4 2012–2019
Monobromoacetic Acid
2.522 µg/L
No EPA limit set
worst single sample: 2.6 µg/L
5/57 SYR4 2012–2019
Nitrate
820 µg/L 8.2%
of the EPA limit 10000 µg/L
2/2 SYR4 2018
Antimony, Total
0.8000 µg/L 13%
of the EPA limit 6 µg/L
1/8 SYR4 2012–2019
Combined Radium (-226 And -228)
1.43 pCi/L 29%
of the EPA limit 5 pCi/L
1/1 SYR4 2017
Gross Beta Particle Activity
0.6100 pCi/L
No EPA limit set
1/1 SYR4 2017
Xylenes, Total
0.4200 µg/L 0%
of the EPA limit 10000 µg/L
1/9 SYR4 2012–2019
86 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaArsenicAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalBromoformChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDibromoacetic AcidDinosebEthylene DibromideEndrinEthylbenzeneHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorNetfosaaNfdhaNmefosaaNitriteOxamylPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl Chloridecis-1,2-DichloroethyleneLithiumO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
WOOD, ROBERT J.
Phone
540-483-7660
Email
[email protected]

Frequently asked questions about Rocky Mount, Town of

Is Rocky Mount, Town of tap water safe to drink?

EPA monitoring detected 21 contaminants in Rocky Mount, Town of's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Rocky Mount, Town of's water?

EPA monitoring detected Bromodichloromethane, Chloroform, TTHM, Dichloroacetic Acid, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.

How many people does Rocky Mount, Town of serve?

Rocky Mount, Town of reports serving 6,000 people in Virginia, per its EPA record.

Has Rocky Mount, Town of had any water quality violations?

The EPA has 16 violations on file for Rocky Mount, Town of, of which 4 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.