Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2023-07-01 → 2023-09-30 |
| MCL | Health-based | Resolved | 2023-07-01 → 2023-09-30 |
| MCL | Health-based | Resolved | 2023-07-01 → 2023-09-30 |
| MCL | Health-based | Resolved | 2023-04-01 → 2023-06-30 |
| MCL | Health-based | Resolved | 2023-04-01 → 2023-06-30 |
| MCL | Health-based | Resolved | 2023-04-01 → 2023-06-30 |
| MCL | Health-based | Resolved | 2023-04-01 → 2023-06-30 |
| MCL | Health-based | Resolved | 2023-04-01 → 2023-06-30 |
| MCL | Health-based | Resolved | 2023-04-01 → 2023-06-30 |
| MCL | Health-based | Resolved | 2023-04-01 → 2023-06-30 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Bromodichloromethane | 13 µg/L No EPA limit set
worst single sample: 16 µg/L | 86/86 | SYR4 | 2012–2019 |
| Chloroform | 87.25 µg/L No EPA limit set
worst single sample: 160 µg/L | 86/86 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 32.15 µg/L No EPA limit set
worst single sample: 45 µg/L | 78/78 | SYR4 | 2012–2019 |
| TTHM | 102.6 µg/L 128% of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 174 µg/L | 78/78 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 61 µg/L 102% of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 90 µg/L | 78/78 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 32.2 µg/L No EPA limit set
worst single sample: 41 µg/L | 77/78 | SYR4 | 2012–2019 |
| Copper | 138.75 µg/L 11% of the EPA limit 1300 µg/L
worst single sample: 696 µg/L | 66/108 | SYR4 | 2012–2019 |
| Dibromochloromethane | 2.185 µg/L No EPA limit set
worst single sample: 2.8 µg/L | 64/86 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 4.005 µg/L No EPA limit set
worst single sample: 5.9 µg/L | 40/78 | SYR4 | 2012–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 16/16 | LCR | 2025 |
| Nitrate-Nitrite | 210 µg/L 2.1% of the EPA limit 10000 µg/L | 14/16 | SYR4 | 2012–2019 |
| Lead | 74.24 µg/L 495% of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 116 µg/L | 10/108 | SYR4 | 2012–2019 |
| Barium | 25.65 µg/L 1.3% of the EPA limit 2000 µg/L
worst single sample: 26 µg/L | 8/8 | SYR4 | 2012–2019 |
| Fluoride | 1209 µg/L 30% of the EPA limit 4000 µg/L
worst single sample: 1230 µg/L | 8/8 | SYR4 | 2012–2019 |
| Combined Radium (-226 And -228) | 0.4000 pCi/L 8% of the EPA limit 5 pCi/L | 1/1 | SYR4 | 2015 |
| Gross Beta Particle Activity | 1.9 pCi/L No EPA limit set | 1/1 | SYR4 | 2015 |
89 contaminants tested, none detected
Utility contact
Frequently asked questions about Emporia, City of
Is Emporia, City of tap water safe to drink?
EPA monitoring detected 16 contaminants in Emporia, City of's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Emporia, City of's water?
EPA monitoring detected Bromodichloromethane, Chloroform, Dichloroacetic Acid, TTHM, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.
How many people does Emporia, City of serve?
Emporia, City of reports serving 7,594 people in Virginia, per its EPA record.
Has Emporia, City of had any water quality violations?
The EPA has 181 violations on file for Emporia, City of, of which 166 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.