Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MR | Monitoring | Resolved | 2022-01-01 → 2022-12-31 |
| MR | Monitoring | Resolved | 2022-01-01 → 2022-12-31 |
| MR | Monitoring | Resolved | 2022-01-01 → 2022-12-31 |
| MR | Monitoring | Resolved | 2020-01-01 → 2022-12-31 |
| MR | Monitoring | Resolved | 2020-01-01 → 2022-12-31 |
| MR | Monitoring | Resolved | 2020-01-01 → 2022-12-31 |
| MR | Monitoring | Resolved | 2020-01-01 → 2022-12-31 |
| MR | Monitoring | Resolved | 2020-01-01 → 2022-12-31 |
| MR | Monitoring | Resolved | 2020-01-01 → 2022-12-31 |
| MR | Monitoring | Resolved | 2020-01-01 → 2022-12-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 188 µg/L 14% of the EPA limit 1300 µg/L
worst single sample: 274 µg/L | 151/153 | SYR4 | 2013–2019 |
| TTHM | 20.61 µg/L 26% of the EPA limit 80 µg/L
worst single sample: 30.1 µg/L | 130/140 | SYR4 | 2012–2019 |
| Lead | 9.1 µg/L 61% of the EPA limit 15 µg/L
worst single sample: 23.2 µg/L | 121/153 | SYR4 | 2013–2019 |
| Bromodichloromethane | 4.8 µg/L No EPA limit set
worst single sample: 7.4 µg/L | 112/126 | SYR4 | 2012–2019 |
| Dibromochloromethane | 2.7 µg/L No EPA limit set
worst single sample: 4.8 µg/L | 112/125 | SYR4 | 2012–2019 |
| Chloroform | 8.91 µg/L No EPA limit set
worst single sample: 15.4 µg/L | 107/128 | SYR4 | 2012–2019 |
| Nitrate | 1335.51 µg/L 13% of the EPA limit 10000 µg/L
worst single sample: 1710.9 µg/L | 74/80 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 13.675 µg/L 23% of the EPA limit 60 µg/L
worst single sample: 17.7 µg/L | 46/140 | SYR4 | 2012–2019 |
| Bromoform | 1.4 µg/L No EPA limit set
worst single sample: 1.7 µg/L | 43/127 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 3.36 µg/L No EPA limit set
worst single sample: 6.6 µg/L | 40/124 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 6.045 µg/L No EPA limit set
worst single sample: 6.5 µg/L | 38/124 | SYR4 | 2012–2019 |
| Lead | 0.0043 mg/L 29% of the EPA limit 0.0150 mg/L | 23/23 | LCR | 2025 |
| Barium | 90.85 µg/L 4.5% of the EPA limit 2000 µg/L
worst single sample: 101 µg/L | 8/8 | SYR4 | 2015–2019 |
| Selenium | 3.065 µg/L 6.1% of the EPA limit 50 µg/L
worst single sample: 3.8 µg/L | 8/8 | SYR4 | 2015–2019 |
| Fluoride | 300 µg/L 7.5% of the EPA limit 4000 µg/L | 6/8 | SYR4 | 2015–2019 |
| Arsenic | 1.08 µg/L 11% of the EPA limit 10 µg/L
worst single sample: 1.1 µg/L | 5/8 | SYR4 | 2015–2019 |
| Gross Beta Particle Activity | 3.68 pCi/L No EPA limit set
worst single sample: 3.8 pCi/L | 4/7 | SYR4 | 2015–2019 |
| Lithium | 27 µg/L No EPA limit set | 4/8 | UCMR-5 | 2023 |
| Cyanide | 7.7 µg/L 3.9% of the EPA limit 200 µg/L
worst single sample: 8 µg/L | 3/8 | SYR4 | 2015–2019 |
| Gross Alpha, Excl. Radon And U | 2.41 pCi/L 16% of the EPA limit 15 pCi/L
worst single sample: 2.5 pCi/L | 3/6 | SYR4 | 2015–2019 |
| Dibromoacetic Acid | 1.2 µg/L No EPA limit set | 2/124 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 300 µg/L 3% of the EPA limit 10000 µg/L | 1/2 | SYR4 | 2016 |
83 contaminants tested, none detected
Utility contact
Frequently asked questions about Provo City
Is Provo City tap water safe to drink?
EPA monitoring detected 22 contaminants in Provo City's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Provo City's water?
EPA monitoring detected Copper, TTHM, Lead, Bromodichloromethane, Dibromochloromethane, and others. The full list with the level and data source for each is above.
How many people does Provo City serve?
Provo City reports serving 116,288 people in Utah, per its EPA record.
Has Provo City had any water quality violations?
The EPA has 129 violations on file for Provo City, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.