Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Resolved | 2018-01-01 → 2018-01-31 |
| TT | Health-based | Resolved | 2018-01-01 → 2018-01-31 |
| TT | Health-based | Resolved | 2018-01-01 → 2018-01-31 |
| MON | Monitoring | Resolved | 2020-01-01 → 2020-01-31 |
| MON | Monitoring | Resolved | 2020-01-01 → 2020-01-31 |
| MON | Monitoring | Resolved | 2020-01-01 → 2020-01-31 |
| RPT | Monitoring | Resolved | 2019-12-29 |
| RPT | Monitoring | Resolved | 2019-12-29 |
| RPT | Monitoring | Resolved | 2019-12-29 |
| Other | Monitoring | Resolved | 2019-07-01 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 326.55 µg/L 25% of the EPA limit 1300 µg/L
worst single sample: 415 µg/L | 64/64 | SYR4 | 2012–2018 |
| Lead | 3.76 µg/L 25% of the EPA limit 15 µg/L
worst single sample: 12.2 µg/L | 52/64 | SYR4 | 2012–2018 |
| Lead | 0.0071 mg/L 47% of the EPA limit 0.0150 mg/L | 22/22 | LCR | 2024 |
| TTHM | 43.3 µg/L 54% of the EPA limit 80 µg/L
worst single sample: 51 µg/L | 21/21 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 38.64 µg/L 64% of the EPA limit 60 µg/L
worst single sample: 39 µg/L | 19/21 | SYR4 | 2012–2019 |
| Nitrate | 300 µg/L 3% of the EPA limit 10000 µg/L | 16/16 | SYR4 | 2012–2019 |
| Bromodichloromethane | 4.38 µg/L No EPA limit set
worst single sample: 4.9 µg/L | 14/16 | SYR4 | 2012–2019 |
| Chloroform | 42.22 µg/L No EPA limit set
worst single sample: 46.9 µg/L | 14/16 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 14.935 µg/L No EPA limit set
worst single sample: 15 µg/L | 14/14 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 23.805 µg/L No EPA limit set
worst single sample: 24 µg/L | 14/14 | SYR4 | 2012–2019 |
| Dibromochloromethane | 1.325 µg/L No EPA limit set
worst single sample: 1.4 µg/L | 4/16 | SYR4 | 2012–2019 |
| Arsenic | 0.7950 µg/L 8% of the EPA limit 10 µg/L
worst single sample: 0.8000 µg/L | 2/2 | SYR4 | 2016–2019 |
| Barium | 86.51 µg/L 4.3% of the EPA limit 2000 µg/L
worst single sample: 87 µg/L | 2/2 | SYR4 | 2016–2019 |
| Cyanide | 2 µg/L 1% of the EPA limit 200 µg/L | 1/2 | SYR4 | 2016–2019 |
| Gross Alpha, Excl. Radon And U | 0.7500 pCi/L 5% of the EPA limit 15 pCi/L | 1/2 | SYR4 | 2017–2019 |
| Gross Beta Particle Activity | 2.1 pCi/L No EPA limit set | 1/2 | SYR4 | 2012–2017 |
| Nitrate-Nitrite | 200 µg/L 2% of the EPA limit 10000 µg/L | 1/1 | SYR4 | 2013 |
63 contaminants tested, none detected
Utility contact
Frequently asked questions about Ashley Valley Water and Sewer Id
Is Ashley Valley Water and Sewer Id tap water safe to drink?
EPA monitoring detected 17 contaminants in Ashley Valley Water and Sewer Id's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Ashley Valley Water and Sewer Id's water?
EPA monitoring detected Copper, Lead, Lead, TTHM, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.
How many people does Ashley Valley Water and Sewer Id serve?
Ashley Valley Water and Sewer Id reports serving 13,835 people in Utah, per its EPA record.
Has Ashley Valley Water and Sewer Id had any water quality violations?
The EPA has 105 violations on file for Ashley Valley Water and Sewer Id, of which 3 are health-based (a contaminant limit or required treatment was breached) and 1 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.