Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2000-09-01 → 2000-09-30 |
| MCL | Health-based | Resolved | 2000-09-01 → 2000-09-30 |
| MCL | Health-based | Resolved | 2000-09-01 → 2000-09-30 |
| MCL | Health-based | Resolved | 2000-09-01 → 2000-09-30 |
| MCL | Health-based | Archived | 1998-08-01 → 1998-08-31 |
| Other | Monitoring | Resolved | 2025-07-01 |
| Other | Monitoring | Resolved | 2025-07-01 |
| MR | Monitoring | Archived | 2023-01-01 → 2025-12-31 |
| MR | Monitoring | Archived | 2023-01-01 → 2025-12-31 |
| MR | Monitoring | Archived | 2023-01-01 → 2025-12-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Antimony, Total | 5.82 µg/L 97% of the EPA limit 6 µg/L
worst single sample: 11.7 µg/L | 99/100 | SYR4 | 2012–2019 |
| Lead | 0.0075 mg/L 50% of the EPA limit 0.0150 mg/L | 22/22 | LCR | 2025 |
| Lead | 7.05 µg/L 47% of the EPA limit 15 µg/L
worst single sample: 7.8 µg/L | 16/17 | SYR4 | 2013–2019 |
| Nitrate | 200 µg/L 2% of the EPA limit 10000 µg/L | 16/18 | SYR4 | 2012–2019 |
| Copper | 76.31 µg/L 5.9% of the EPA limit 1300 µg/L
worst single sample: 109 µg/L | 15/17 | SYR4 | 2013–2019 |
| Cadmium | 1.5 µg/L 30% of the EPA limit 5 µg/L | 7/7 | SYR4 | 2012–2019 |
| Arsenic | 1.5 µg/L 15% of the EPA limit 10 µg/L | 4/5 | SYR4 | 2013–2019 |
| Barium | 48.5 µg/L 2.4% of the EPA limit 2000 µg/L
worst single sample: 50 µg/L | 3/3 | SYR4 | 2013–2019 |
| Bromodichloromethane | 0.8900 µg/L No EPA limit set
worst single sample: 0.9000 µg/L | 3/7 | SYR4 | 2012–2017 |
| Chloroform | 1.6 µg/L No EPA limit set | 3/7 | SYR4 | 2012–2017 |
| Selenium | 2.2 µg/L 4.4% of the EPA limit 50 µg/L
worst single sample: 2.3 µg/L | 3/3 | SYR4 | 2013–2019 |
| TTHM | 2.45 µg/L 3.1% of the EPA limit 80 µg/L
worst single sample: 2.5 µg/L | 2/2 | SYR4 | 2014–2017 |
| Dichloroacetic Acid | 1 µg/L No EPA limit set | 1/2 | SYR4 | 2014–2017 |
| Gross Alpha, Excl. Radon And U | 0.5000 pCi/L 3.3% of the EPA limit 15 pCi/L | 1/2 | SYR4 | 2012–2018 |
| Gross Beta Particle Activity | 1.6 pCi/L No EPA limit set | 1/2 | SYR4 | 2012–2018 |
| Mercury | 0.3000 µg/L 15% of the EPA limit 2 µg/L | 1/3 | SYR4 | 2013–2019 |
| Xylenes, Total | 1.6 µg/L 0% of the EPA limit 10000 µg/L | 1/5 | SYR4 | 2012–2016 |
87 contaminants tested, none detected
Utility contact
Frequently asked questions about Alta Town Water
Is Alta Town Water tap water safe to drink?
EPA monitoring detected 17 contaminants in Alta Town Water's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Alta Town Water's water?
EPA monitoring detected Antimony, Total, Lead, Lead, Nitrate, Copper, and others. The full list with the level and data source for each is above.
How many people does Alta Town Water serve?
Alta Town Water reports serving 5,228 people in Utah, per its EPA record.
Has Alta Town Water had any water quality violations?
The EPA has 145 violations on file for Alta Town Water, of which 5 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.