Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Archived | 2025-11-01 → 2025-11-30 |
| MCL | Health-based | Archived | 2025-11-01 → 2025-11-30 |
| MCL | Health-based | Archived | 2025-11-01 → 2025-11-30 |
| MCL | Health-based | Archived | 2025-11-01 → 2025-11-30 |
| TT | Health-based | Resolved | 2016-05-06 |
| TT | Health-based | Resolved | 2016-05-06 |
| TT | Health-based | Resolved | 2016-05-06 |
| MCL | Health-based | Resolved | 2015-10-01 → 2015-10-31 |
| MCL | Health-based | Resolved | 2015-10-01 → 2015-10-31 |
| MCL | Health-based | Resolved | 2015-10-01 → 2015-10-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Lead | 0.0062 mg/L 41% of the EPA limit 0.0150 mg/L | 16/16 | LCR | 2025 |
| Copper | 66.53 µg/L 5.1% of the EPA limit 1300 µg/L
worst single sample: 110 µg/L | 15/15 | SYR4 | 2012–2019 |
| Lead | 1.575 µg/L 11% of the EPA limit 15 µg/L
worst single sample: 1.6 µg/L | 6/15 | SYR4 | 2012–2019 |
| Arsenic | 1.36 µg/L 14% of the EPA limit 10 µg/L
worst single sample: 1.4 µg/L | 2/2 | SYR4 | 2016–2019 |
| Barium | 209.415 µg/L 10% of the EPA limit 2000 µg/L
worst single sample: 210 µg/L | 2/2 | SYR4 | 2016–2019 |
| Fluoride | 689.13 µg/L 17% of the EPA limit 4000 µg/L
worst single sample: 700 µg/L | 2/2 | SYR4 | 2016–2019 |
| Gross Beta Particle Activity | 6.015 pCi/L No EPA limit set
worst single sample: 6.2 pCi/L | 2/3 | SYR4 | 2013–2019 |
| Nitrate | 500 µg/L 5% of the EPA limit 10000 µg/L | 2/8 | SYR4 | 2013–2019 |
| Gross Alpha, Excl. Radon And U | 1.6 pCi/L 11% of the EPA limit 15 pCi/L | 1/3 | SYR4 | 2013–2019 |
| Nitrate-Nitrite | 160 µg/L 1.6% of the EPA limit 10000 µg/L | 1/4 | SYR4 | 2012–2018 |
57 contaminants tested, none detected
Utility contact
Frequently asked questions about Glendale Town Water
Is Glendale Town Water tap water safe to drink?
EPA monitoring detected 10 contaminants in Glendale Town Water's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Glendale Town Water's water?
EPA monitoring detected Lead, Copper, Lead, Arsenic, Barium, and others. The full list with the level and data source for each is above.
How many people does Glendale Town Water serve?
Glendale Town Water reports serving 411 people in Utah, per its EPA record.
Has Glendale Town Water had any water quality violations?
The EPA has 504 violations on file for Glendale Town Water, of which 35 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.