EPA monitoring tested this supplier for 79 contaminants and detected 29. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

79
contaminants tested
29
detected
1,458
people served
138
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Trinity

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

138
health-based violations
1,062
violations on file
43
still open
ViolationTypeStatusPeriod
TT Health-based Unaddressed 2024-10-17
TT Health-based Unaddressed 2024-10-17
MCL Health-based Resolved 2023-10-01 → 2023-12-31
MCL Health-based Resolved 2023-10-01 → 2023-12-31
MCL Health-based Resolved 2023-10-01 → 2023-12-31
MCL Health-based Resolved 2023-10-01 → 2023-12-31
MCL Health-based Resolved 2023-10-01 → 2023-12-31
TT Health-based Resolved 2021-11-18
TT Health-based Resolved 2021-11-18
TT Health-based Resolved 2021-11-18

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Bromodichloromethane
35.67 µg/L
No EPA limit set
worst single sample: 71.3 µg/L
87/88 SYR4 2012–2019
Dibromochloromethane
36.81 µg/L
No EPA limit set
worst single sample: 47.5 µg/L
87/88 SYR4 2012–2019
Bromoform
26.8 µg/L
No EPA limit set
worst single sample: 51.6 µg/L
85/88 SYR4 2012–2019
Chloroform
38.74 µg/L
No EPA limit set
worst single sample: 59.7 µg/L
84/88 SYR4 2012–2019
TTHM
103.05 µg/L 129%
of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 156.2 µg/L
71/71 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
50.5 µg/L 84%
of the EPA limit 60 µg/L
worst single sample: 90.8 µg/L
71/71 SYR4 2012–2019
Dichloroacetic Acid
23.92 µg/L
No EPA limit set
worst single sample: 38.9 µg/L
70/71 SYR4 2012–2019
Trichloroacetic Acid
19.12 µg/L
No EPA limit set
worst single sample: 42.3 µg/L
69/71 SYR4 2012–2019
Dibromoacetic Acid
11.025 µg/L
No EPA limit set
worst single sample: 12 µg/L
66/71 SYR4 2012–2019
Copper
1875 µg/L 144%
of the EPA limit, at the 95th percentile of samples — 1300 µg/L
worst single sample: 3130 µg/L
62/97 SYR4 2012–2019
Nitrate
741.85 µg/L 7.4%
of the EPA limit 10000 µg/L
worst single sample: 911 µg/L
38/48 SYR4 2012–2019
Lead
25.55 µg/L 170%
of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 31 µg/L
36/97 SYR4 2012–2019
Monochloroacetic Acid
6.62 µg/L
No EPA limit set
worst single sample: 8.6 µg/L
23/71 SYR4 2012–2019
Monobromoacetic Acid
2.7 µg/L
No EPA limit set
worst single sample: 4.5 µg/L
19/71 SYR4 2012–2019
Barium
71.48 µg/L 3.6%
of the EPA limit 2000 µg/L
worst single sample: 73.8 µg/L
9/9 SYR4 2012–2019
Fluoride
415.6 µg/L 10%
of the EPA limit 4000 µg/L
worst single sample: 450 µg/L
9/9 SYR4 2012–2019
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
9/9 LCR 2023
Chromium
2.296 µg/L 2.3%
of the EPA limit 100 µg/L
worst single sample: 2.38 µg/L
5/9 SYR4 2012–2019
Gross Beta Particle Activity
9.78 pCi/L
No EPA limit set
worst single sample: 9.8 pCi/L
5/5 SYR4 2012–2018
Nitrate-Nitrite
660.4 µg/L 6.6%
of the EPA limit 10000 µg/L
worst single sample: 681 µg/L
5/7 SYR4 2012–2019
Combined Radium (-226 And -228)
2.385 pCi/L 48%
of the EPA limit 5 pCi/L
worst single sample: 2.4 pCi/L
4/4 SYR4 2012–2018
Ethylbenzene
16.602 µg/L 2.4%
of the EPA limit 700 µg/L
worst single sample: 19.2 µg/L
4/17 SYR4 2014–2019
Xylenes, Total
79.3575 µg/L 0.8%
of the EPA limit 10000 µg/L
worst single sample: 91.8 µg/L
4/17 SYR4 2014–2019
Cyanide
35.965 µg/L 18%
of the EPA limit 200 µg/L
worst single sample: 36.9 µg/L
2/6 SYR4 2014–2017
Selenium
1.195 µg/L 2.4%
of the EPA limit 50 µg/L
worst single sample: 1.2 µg/L
2/9 SYR4 2012–2019
Thallium, Total
0.4021 µg/L 20%
of the EPA limit 2 µg/L
worst single sample: 0.4080 µg/L
2/9 SYR4 2012–2019
Antimony, Total
0.2330 µg/L 3.9%
of the EPA limit 6 µg/L
1/9 SYR4 2012–2019
Arsenic
0.3420 µg/L 3.4%
of the EPA limit 10 µg/L
1/9 SYR4 2012–2019
Toluene
0.8310 µg/L 0.1%
of the EPA limit 1000 µg/L
1/17 SYR4 2014–2019
50 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAsbestosAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCadmiumCarbofuranCarbon TetrachlorideChlordaneCombined UraniumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebEthylene DibromideEndrinGross Alpha, Excl. Radon And UHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorNitriteOxamylPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneToxapheneTrichloroethyleneVinyl Chloridecis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
CHAMBERLIN, JOHN
Phone
936-594-9417
Email
[email protected]

Frequently asked questions about Glendale Wsc

Is Glendale Wsc tap water safe to drink?

EPA monitoring detected 29 contaminants in Glendale Wsc's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Glendale Wsc's water?

EPA monitoring detected Bromodichloromethane, Dibromochloromethane, Bromoform, Chloroform, TTHM, and others. The full list with the level and data source for each is above.

How many people does Glendale Wsc serve?

Glendale Wsc reports serving 1,458 people in Texas, per its EPA record.

Has Glendale Wsc had any water quality violations?