Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Resolved | 2022-02-01 → 2022-02-28 |
| TT | Health-based | Resolved | 2022-02-01 → 2022-02-28 |
| TT | Health-based | Resolved | 2022-02-01 → 2022-02-28 |
| TT | Health-based | Resolved | 2022-02-01 → 2022-02-28 |
| TT | Health-based | Resolved | 2022-02-01 → 2022-02-28 |
| TT | Health-based | Resolved | 2018-10-01 → 2018-10-31 |
| TT | Health-based | Resolved | 2018-10-01 → 2018-10-31 |
| TT | Health-based | Resolved | 2018-10-01 → 2018-10-31 |
| TT | Health-based | Resolved | 2018-10-01 → 2018-10-31 |
| TT | Health-based | Resolved | 2018-10-01 → 2018-10-31 |
PFAS detected
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Bromodichloromethane | 18.885 µg/L No EPA limit set
worst single sample: 23.2 µg/L | 244/244 | SYR4 | 2012–2019 |
| Chloroform | 30.285 µg/L No EPA limit set
worst single sample: 78.1 µg/L | 244/244 | SYR4 | 2012–2019 |
| Dibromochloromethane | 12.985 µg/L No EPA limit set
worst single sample: 21.4 µg/L | 244/244 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 15.41 µg/L No EPA limit set
worst single sample: 27.8 µg/L | 220/220 | SYR4 | 2012–2019 |
| TTHM | 59.045 µg/L 74% of the EPA limit 80 µg/L
worst single sample: 101 µg/L | 220/222 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 23.91 µg/L 40% of the EPA limit 60 µg/L
worst single sample: 44.7 µg/L | 220/220 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 7.07 µg/L No EPA limit set
worst single sample: 18.7 µg/L | 219/220 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 4.1 µg/L No EPA limit set
worst single sample: 7.7 µg/L | 193/220 | SYR4 | 2012–2019 |
| Bromoform | 3.355 µg/L No EPA limit set
worst single sample: 5.7 µg/L | 130/244 | SYR4 | 2012–2019 |
| Copper | 9.6 µg/L 0.7% of the EPA limit 1300 µg/L
worst single sample: 15.7 µg/L | 95/163 | SYR4 | 2012–2018 |
| Nitrate | 560 µg/L 5.6% of the EPA limit 10000 µg/L
worst single sample: 570 µg/L | 46/46 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 3.525 µg/L No EPA limit set
worst single sample: 4.2 µg/L | 36/220 | SYR4 | 2012–2019 |
| Fluoride | 820 µg/L 21% of the EPA limit 4000 µg/L
worst single sample: 840 µg/L | 21/21 | SYR4 | 2012–2019 |
| Barium | 11.91 µg/L 0.6% of the EPA limit 2000 µg/L
worst single sample: 12 µg/L | 19/19 | SYR4 | 2013–2019 |
| Cyanide | 132.5 µg/L 66% of the EPA limit 200 µg/L
worst single sample: 140 µg/L | 16/17 | SYR4 | 2014–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 16/16 | LCR | 2024 |
| Lead | 3.923 µg/L 26% of the EPA limit 15 µg/L
worst single sample: 3.93 µg/L | 8/163 | SYR4 | 2012–2018 |
| Monobromoacetic Acid | 1.43 µg/L No EPA limit set
worst single sample: 1.5 µg/L | 8/220 | SYR4 | 2012–2019 |
| Chromium | 0.4283 µg/L 0.4% of the EPA limit 100 µg/L
worst single sample: 0.4290 µg/L | 2/19 | SYR4 | 2013–2019 |
| Diquat | 4.03 µg/L 20% of the EPA limit 20 µg/L
worst single sample: 4.2 µg/L | 2/7 | SYR4 | 2015–2019 |
| Simazine | 0.0800 µg/L 2% of the EPA limit 4 µg/L | 2/24 | SYR4 | 2012–2019 |
| Arsenic | 0.9340 µg/L 9.3% of the EPA limit 10 µg/L | 1/19 | SYR4 | 2013–2019 |
| Gross Beta Particle Activity | 4.8 pCi/L No EPA limit set | 1/4 | SYR4 | 2015–2018 |
81 contaminants tested, none detected
Utility contact
Frequently asked questions about City of Austin Water & Wastewater
Is City of Austin Water & Wastewater tap water safe to drink?
EPA monitoring detected 29 contaminants in City of Austin Water & Wastewater's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in City of Austin Water & Wastewater's water?
EPA monitoring detected Bromodichloromethane, Chloroform, Dibromochloromethane, Dichloroacetic Acid, TTHM, and others. The full list with the level and data source for each is above.
How many people does City of Austin Water & Wastewater serve?
City of Austin Water & Wastewater reports serving 1,115,323 people in Texas, per its EPA record.
Has City of Austin Water & Wastewater had any water quality violations?
The EPA has 26 violations on file for City of Austin Water & Wastewater, of which 22 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.