← Texas

Tap water quality report

Benbrook Water Authority

EPA monitoring tested this supplier for 110 contaminants and detected 35. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

110
contaminants tested
35
detected
25,616
people served
0
health-based violations
Water source
Surface water
Ownership
Local government
Counties served
Tarrant

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

0
health-based violations
39
violations on file
0
still open
ViolationTypeStatusPeriod
MR Monitoring Archived 2022-01-01 → 2024-12-31
MR Monitoring Archived 2022-01-01 → 2024-12-31
MR Monitoring Archived 2022-01-01 → 2024-12-31
MR Monitoring Archived 2022-01-01 → 2024-12-31
MR Monitoring Archived 2022-01-01 → 2024-12-31
MR Monitoring Archived 2022-01-01 → 2024-12-31
MR Monitoring Archived 2022-01-01 → 2024-12-31
MR Monitoring Archived 2022-01-01 → 2024-12-31
MR Monitoring Archived 2022-01-01 → 2024-12-31
MR Monitoring Archived 2022-01-01 → 2024-12-31

PFAS detected

PFAS are industrial “forever chemicals”. These are the EPA's latest nationwide test results (2023–2025).
ContaminantMaxDetection ratePeriod
Pfba 0.0051 µg/L 1/20 2025
PFBS 0.0031 µg/L 1/20 2025
Pfhpa 0.0064 µg/L 1/20 2025

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Chlorite
341.15 µg/L 34%
of the EPA limit 1000 µg/L
worst single sample: 469 µg/L
210/234 SYR4 2013–2019
Chloroform
23.525 µg/L
No EPA limit set
worst single sample: 33 µg/L
166/213 SYR4 2012–2019
Dibromochloromethane
23.28 µg/L
No EPA limit set
worst single sample: 30.2 µg/L
165/213 SYR4 2012–2019
Bromodichloromethane
27.175 µg/L
No EPA limit set
worst single sample: 35.4 µg/L
162/213 SYR4 2012–2019
Nitrate
318 µg/L 3.2%
of the EPA limit 10000 µg/L
worst single sample: 474 µg/L
162/176 SYR4 2012–2019
Bromoform
8.4445 µg/L
No EPA limit set
worst single sample: 9.5 µg/L
148/213 SYR4 2012–2019
TTHM
79.6 µg/L 99%
of the EPA limit 80 µg/L
worst single sample: 85 µg/L
141/158 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
29.2 µg/L 49%
of the EPA limit 60 µg/L
worst single sample: 35.8 µg/L
141/156 SYR4 2012–2019
Dichloroacetic Acid
14.02 µg/L
No EPA limit set
worst single sample: 17.7 µg/L
129/156 SYR4 2012–2019
Monobromoacetic Acid
3.3 µg/L
No EPA limit set
worst single sample: 5.9 µg/L
117/156 SYR4 2012–2019
Trichloroacetic Acid
5.7 µg/L
No EPA limit set
worst single sample: 7.8 µg/L
114/156 SYR4 2012–2019
Copper
140.36 µg/L 11%
of the EPA limit 1300 µg/L
worst single sample: 160.4 µg/L
109/110 SYR4 2013–2019
Dibromoacetic Acid
9.76 µg/L
No EPA limit set
worst single sample: 12.7 µg/L
108/156 SYR4 2012–2019
Monochloroacetic Acid
6.225 µg/L
No EPA limit set
worst single sample: 8.5 µg/L
36/156 SYR4 2012–2019
Lead
3.58 µg/L 24%
of the EPA limit 15 µg/L
worst single sample: 10.2 µg/L
35/110 SYR4 2013–2019
Fluoride
656.4 µg/L 16%
of the EPA limit 4000 µg/L
worst single sample: 1180 µg/L
29/29 SYR4 2012–2019
Barium
74 µg/L 3.7%
of the EPA limit 2000 µg/L
worst single sample: 81 µg/L
26/26 SYR4 2013–2019
Nitrate-Nitrite
400.7 µg/L 4%
of the EPA limit 10000 µg/L
worst single sample: 407 µg/L
19/26 SYR4 2012–2015
Lithium
55.4 µg/L
No EPA limit set
19/20 UCMR-5 2025
Gross Beta Particle Activity
7.33 pCi/L
No EPA limit set
worst single sample: 7.5 pCi/L
18/20 SYR4 2012–2019
Lead
0.0017 mg/L 11%
of the EPA limit 0.0150 mg/L
17/17 LCR 2025
Chromium
10.075 µg/L 10%
of the EPA limit 100 µg/L
worst single sample: 13 µg/L
16/26 SYR4 2013–2019
Cyanide
171.75 µg/L 86%
of the EPA limit 200 µg/L
worst single sample: 180 µg/L
12/27 SYR4 2013–2019
Combined Radium (-226 And -228)
2.7 pCi/L 54%
of the EPA limit 5 pCi/L
worst single sample: 2.73 pCi/L
7/8 SYR4 2012–2019
Gross Alpha, Excl. Radon And U
10.08 pCi/L 67%
of the EPA limit 15 pCi/L
worst single sample: 10.8 pCi/L
7/12 SYR4 2013–2019
Selenium
1.757 µg/L 3.5%
of the EPA limit 50 µg/L
worst single sample: 1.76 µg/L
4/26 SYR4 2013–2019
Antimony, Total
0.2000 µg/L 3.3%
of the EPA limit 6 µg/L
2/26 SYR4 2013–2019
Arsenic
1.0081 µg/L 10%
of the EPA limit 10 µg/L
worst single sample: 1.01 µg/L
2/26 SYR4 2013–2019
Di(2-ethylhexyl) Phthalate
0.9750 µg/L 16%
of the EPA limit 6 µg/L
worst single sample: 1 µg/L
2/42 SYR4 2012–2019
Thallium, Total
0.2509 µg/L 13%
of the EPA limit 2 µg/L
worst single sample: 0.2530 µg/L
2/26 SYR4 2013–2019
Xylenes, Total
1.529 µg/L 0%
of the EPA limit 10000 µg/L
worst single sample: 1.58 µg/L
2/57 SYR4 2012–2019
Carbon Tetrachloride
0.7800 µg/L 16%
of the EPA limit 5 µg/L
1/57 SYR4 2012–2019
75 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAsbestosAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCadmiumCarbofuranChlordaneCombined UraniumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDinosebEthylene DibromideEndrinEthylbenzeneHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorNetfosaaNfdhaNmefosaaNitriteOxamylPfdaPfdoaPfeesaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneTolueneToxapheneTrichloroethyleneVinyl Chloridecis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
SMITH, DAVID, M
Phone
817-249-1250
Email
[email protected]

Frequently asked questions about Benbrook Water Authority

Is Benbrook Water Authority tap water safe to drink?

EPA monitoring detected 35 contaminants in Benbrook Water Authority's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Benbrook Water Authority's water?

EPA monitoring detected Chlorite, Chloroform, Dibromochloromethane, Bromodichloromethane, Nitrate, and others. The full list with the level and data source for each is above.

How many people does Benbrook Water Authority serve?

Benbrook Water Authority reports serving 25,616 people in Texas, per its EPA record.

Has Benbrook Water Authority had any water quality violations?

The EPA has 39 violations on file for Benbrook Water Authority, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.