← Texas

Tap water quality report

City of Strawn

EPA monitoring tested this supplier for 78 contaminants and detected 22. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

78
contaminants tested
22
detected
916
people served
274
health-based violations
Water source
Surface water
Ownership
Local government
Counties served
Palo Pinto

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

274
health-based violations
540
violations on file
11
still open
ViolationTypeStatusPeriod
TT Health-based Resolved 2024-08-01 → 2024-08-31
TT Health-based Resolved 2024-08-01 → 2024-08-31
TT Health-based Resolved 2024-08-01 → 2024-08-31
TT Health-based Resolved 2024-08-01 → 2024-08-31
TT Health-based Resolved 2024-08-01 → 2024-08-31
TT Health-based Resolved 2024-08-01 → 2024-08-31
TT Health-based Resolved 2024-08-01 → 2024-08-31
TT Health-based Resolved 2024-08-01 → 2024-08-31
TT Health-based Resolved 2023-11-01 → 2023-11-30
TT Health-based Resolved 2023-11-01 → 2023-11-30

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Bromodichloromethane
64.395 µg/L
No EPA limit set
worst single sample: 68.5 µg/L
40/40 SYR4 2012–2019
Chloroform
237.95 µg/L
No EPA limit set
worst single sample: 330 µg/L
40/40 SYR4 2012–2019
Dibromochloromethane
20.3 µg/L
No EPA limit set
worst single sample: 23.8 µg/L
36/40 SYR4 2012–2019
Copper
216.25 µg/L 17%
of the EPA limit 1300 µg/L
worst single sample: 419 µg/L
34/34 SYR4 2013–2018
TTHM
307.7 µg/L 385%
of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 367 µg/L
30/30 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
292 µg/L 487%
of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 408 µg/L
29/30 SYR4 2012–2019
Dichloroacetic Acid
114.705 µg/L
No EPA limit set
worst single sample: 169 µg/L
28/30 SYR4 2012–2019
Trichloroacetic Acid
176.4 µg/L
No EPA limit set
worst single sample: 228 µg/L
28/30 SYR4 2012–2019
Dibromoacetic Acid
5.38 µg/L
No EPA limit set
worst single sample: 11.5 µg/L
19/30 SYR4 2012–2019
Lead
3.322 µg/L 22%
of the EPA limit 15 µg/L
worst single sample: 5.6 µg/L
18/34 SYR4 2013–2018
Nitrate
1450 µg/L 14%
of the EPA limit 10000 µg/L
18/18 SYR4 2012–2019
Monochloroacetic Acid
9.21 µg/L
No EPA limit set
worst single sample: 10.4 µg/L
15/30 SYR4 2012–2019
Bromoform
4.74 µg/L
No EPA limit set
worst single sample: 5.1 µg/L
10/40 SYR4 2012–2019
Monobromoacetic Acid
3.1 µg/L
No EPA limit set
10/30 SYR4 2012–2019
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
8/8 LCR 2023
Barium
107 µg/L 5.4%
of the EPA limit 2000 µg/L
worst single sample: 110 µg/L
7/7 SYR4 2013–2019
Fluoride
180.8 µg/L 4.5%
of the EPA limit 4000 µg/L
worst single sample: 194 µg/L
7/8 SYR4 2012–2019
Cyanide
117.4 µg/L 59%
of the EPA limit 200 µg/L
worst single sample: 118 µg/L
5/6 SYR4 2014–2019
Arsenic
0.7818 µg/L 7.8%
of the EPA limit 10 µg/L
worst single sample: 0.7840 µg/L
2/7 SYR4 2013–2019
Antimony, Total
0.3400 µg/L 5.7%
of the EPA limit 6 µg/L
1/7 SYR4 2013–2019
Combined Radium (-226 And -228)
1 pCi/L 20%
of the EPA limit 5 pCi/L
1/1 SYR4 2012
Gross Beta Particle Activity
4.3 pCi/L
No EPA limit set
1/2 SYR4 2012–2018
56 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAsbestosAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumCombined UraniumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebEthylene DibromideEndrinEthylbenzeneGross Alpha, Excl. Radon And UHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorNitriteOxamylPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
MALLORY, OMER
Phone
254-672-5311
Email
[email protected]

Frequently asked questions about City of Strawn

Is City of Strawn tap water safe to drink?

EPA monitoring detected 22 contaminants in City of Strawn's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in City of Strawn's water?

EPA monitoring detected Bromodichloromethane, Chloroform, Dibromochloromethane, Copper, TTHM, and others. The full list with the level and data source for each is above.

How many people does City of Strawn serve?

City of Strawn reports serving 916 people in Texas, per its EPA record.

Has City of Strawn had any water quality violations?

The EPA has 540 violations on file for City of Strawn, of which 274 are health-based (a contaminant limit or required treatment was breached) and 11 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.