← Texas

Tap water quality report

Agua Sud

EPA monitoring tested this supplier for 109 contaminants and detected 31. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

109
contaminants tested
31
detected
53,796
people served
28
health-based violations
Water source
Surface water
Ownership
Local government
Counties served
Hidalgo

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

28
health-based violations
39
violations on file
2
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2023-03-01 → 2023-03-31
MCL Health-based Resolved 2023-03-01 → 2023-03-31
MCL Health-based Resolved 2023-03-01 → 2023-03-31
MCL Health-based Resolved 2023-03-01 → 2023-03-31
MCL Health-based Resolved 2015-10-01 → 2015-12-31
MCL Health-based Resolved 2015-10-01 → 2015-12-31
MCL Health-based Resolved 2015-10-01 → 2015-12-31
MCL Health-based Resolved 2015-10-01 → 2015-12-31
MCL Health-based Resolved 2015-07-01 → 2015-09-30
MCL Health-based Resolved 2015-07-01 → 2015-09-30

PFAS detected

PFAS are industrial “forever chemicals”. These are the EPA's latest nationwide test results (2023–2025).
ContaminantMaxDetection ratePeriod
Pfba 0.0119 µg/L 5/8 2025
Pfhxa 0.0046 µg/L 2/8 2025
Pfpea 0.0048 µg/L 2/8 2025

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Chlorite
710 µg/L 71%
of the EPA limit 1000 µg/L
worst single sample: 960 µg/L
668/680 SYR4 2013–2019
Dibromochloromethane
34.256 µg/L
No EPA limit set
worst single sample: 51.5 µg/L
138/138 SYR4 2012–2019
Bromodichloromethane
17.22 µg/L
No EPA limit set
worst single sample: 23.5 µg/L
137/138 SYR4 2012–2019
Bromoform
31.72 µg/L
No EPA limit set
worst single sample: 51.8 µg/L
137/138 SYR4 2012–2019
Chloroform
6.84 µg/L
No EPA limit set
worst single sample: 10.1 µg/L
127/138 SYR4 2012–2019
Dibromoacetic Acid
19.64 µg/L
No EPA limit set
worst single sample: 31.9 µg/L
114/114 SYR4 2012–2019
Dichloroacetic Acid
10.34 µg/L
No EPA limit set
worst single sample: 14.4 µg/L
114/114 SYR4 2012–2019
TTHM
82.065 µg/L 103%
of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 131 µg/L
114/114 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
32.575 µg/L 54%
of the EPA limit 60 µg/L
worst single sample: 45.6 µg/L
114/114 SYR4 2012–2019
Copper
104.775 µg/L 8.1%
of the EPA limit 1300 µg/L
worst single sample: 1250 µg/L
106/106 SYR4 2012–2019
Trichloroacetic Acid
4.7 µg/L
No EPA limit set
worst single sample: 6.4 µg/L
72/114 SYR4 2012–2019
Monobromoacetic Acid
6.95 µg/L
No EPA limit set
worst single sample: 11.7 µg/L
48/114 SYR4 2012–2019
Nitrate
180 µg/L 1.8%
of the EPA limit 10000 µg/L
worst single sample: 330 µg/L
48/54 SYR4 2012–2019
Fluoride
658.5 µg/L 16%
of the EPA limit 4000 µg/L
worst single sample: 660 µg/L
24/24 SYR4 2012–2019
Barium
133.95 µg/L 6.7%
of the EPA limit 2000 µg/L
worst single sample: 135 µg/L
22/22 SYR4 2012–2019
Lead
5.147 µg/L 34%
of the EPA limit 15 µg/L
worst single sample: 8.8 µg/L
22/106 SYR4 2012–2019
Selenium
5.38 µg/L 11%
of the EPA limit 50 µg/L
worst single sample: 5.9 µg/L
14/22 SYR4 2012–2019
Lead
0.00080 mg/L 5.3%
of the EPA limit 0.0150 mg/L
13/13 LCR 2025
Lithium
64.4 µg/L
No EPA limit set
8/8 UCMR-5 2024
Arsenic
2.9 µg/L 29%
of the EPA limit 10 µg/L
worst single sample: 3 µg/L
5/22 SYR4 2012–2019
Gross Beta Particle Activity
7.2 pCi/L
No EPA limit set
worst single sample: 7.3 pCi/L
3/3 SYR4 2016–2017
Monochloroacetic Acid
3.38 µg/L
No EPA limit set
worst single sample: 3.4 µg/L
3/114 SYR4 2012–2019
Antimony, Total
0.6430 µg/L 11%
of the EPA limit 6 µg/L
1/22 SYR4 2012–2019
Atrazine
0.1000 µg/L 3.3%
of the EPA limit 3 µg/L
1/29 SYR4 2012–2019
Cyanide
50 µg/L 25%
of the EPA limit 200 µg/L
1/18 SYR4 2014–2019
Combined Radium (-226 And -228)
1.5 pCi/L 30%
of the EPA limit 5 pCi/L
1/1 SYR4 2016
Combined Uranium
1.6 µg/L 5.3%
of the EPA limit 30 µg/L
1/3 SYR4 2016–2017
Gross Alpha, Excl. Radon And U
2 pCi/L 13%
of the EPA limit 15 pCi/L
1/3 SYR4 2016–2017
78 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAsbestosBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebEthylene DibromideEndrinEthylbenzeneHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorNetfosaaNfdhaNmefosaaNitriteOxamylPFBSPfdaPfdoaPfeesaPfhpaPfhpsPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpesPftaPftrdaPfunaPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneThallium, TotalTolueneToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
OCHOA, JOSE LUIS
Phone
956-585-2459
Email
[email protected]

Frequently asked questions about Agua Sud

Is Agua Sud tap water safe to drink?

EPA monitoring detected 31 contaminants in Agua Sud's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Agua Sud's water?

EPA monitoring detected Chlorite, Dibromochloromethane, Bromodichloromethane, Bromoform, Chloroform, and others. The full list with the level and data source for each is above.

How many people does Agua Sud serve?

Agua Sud reports serving 53,796 people in Texas, per its EPA record.

Has Agua Sud had any water quality violations?

The EPA has 39 violations on file for Agua Sud, of which 28 are health-based (a contaminant limit or required treatment was breached) and 2 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.