Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MR | Monitoring | Resolved | 2024-01-01 → 2024-06-30 |
| MR | Monitoring | Resolved | 2024-01-01 → 2024-06-30 |
| MR | Monitoring | Resolved | 2024-01-01 → 2024-06-30 |
| MR | Monitoring | Resolved | 2024-01-01 → 2024-06-30 |
| MR | Monitoring | Resolved | 2024-01-01 → 2024-06-30 |
| MR | Monitoring | Resolved | 2024-01-01 → 2024-06-30 |
| Other | Monitoring | Resolved | 2006-04-01 |
| MR | Monitoring | Resolved | 2005-12-01 → 2005-12-31 |
| MR | Monitoring | Resolved | 2005-12-01 → 2005-12-31 |
| MR | Monitoring | Resolved | 2005-12-01 → 2005-12-31 |
PFAS detected
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Nitrate | 880 µg/L 8.8% of the EPA limit 10000 µg/L
worst single sample: 1000 µg/L | 52/52 | SYR4 | 2012–2019 |
| Bromodichloromethane | 9.86 µg/L No EPA limit set
worst single sample: 12.4 µg/L | 45/50 | SYR4 | 2012–2019 |
| Chloroform | 21.54 µg/L No EPA limit set
worst single sample: 28.6 µg/L | 45/50 | SYR4 | 2012–2019 |
| Dibromochloromethane | 3.19 µg/L No EPA limit set
worst single sample: 4.5 µg/L | 38/50 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 32 µg/L No EPA limit set
worst single sample: 35.1 µg/L | 37/40 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 43.68 µg/L 73% of the EPA limit 60 µg/L
worst single sample: 45.3 µg/L | 37/40 | SYR4 | 2012–2019 |
| TTHM | 34.55 µg/L 43% of the EPA limit 80 µg/L
worst single sample: 35 µg/L | 36/40 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 9.825 µg/L No EPA limit set
worst single sample: 11.7 µg/L | 36/40 | SYR4 | 2012–2019 |
| Copper | 100.9 µg/L 7.8% of the EPA limit 1300 µg/L
worst single sample: 133 µg/L | 28/43 | SYR4 | 2012–2017 |
| Dibromoacetic Acid | 2.2 µg/L No EPA limit set
worst single sample: 2.4 µg/L | 27/40 | SYR4 | 2012–2019 |
| Lead | 0.00050 mg/L 3.3% of the EPA limit 0.0150 mg/L | 12/12 | LCR | 2024 |
| Atrazine | 0.2365 µg/L 7.9% of the EPA limit 3 µg/L
worst single sample: 0.2400 µg/L | 8/9 | SYR4 | 2012–2018 |
| Nitrate-Nitrite | 768 µg/L 7.7% of the EPA limit 10000 µg/L
worst single sample: 780 µg/L | 7/7 | SYR4 | 2012–2014 |
| Simazine | 0.1375 µg/L 3.4% of the EPA limit 4 µg/L
worst single sample: 0.1400 µg/L | 6/9 | SYR4 | 2012–2018 |
| Barium | 128.2 µg/L 6.4% of the EPA limit 2000 µg/L
worst single sample: 132 µg/L | 5/5 | SYR4 | 2012–2019 |
| Cyanide | 166 µg/L 83% of the EPA limit 200 µg/L
worst single sample: 170 µg/L | 5/5 | SYR4 | 2014–2019 |
| Fluoride | 482 µg/L 12% of the EPA limit 4000 µg/L
worst single sample: 500 µg/L | 5/5 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 8.67 µg/L No EPA limit set
worst single sample: 9 µg/L | 4/40 | SYR4 | 2012–2019 |
| Lithium | 15.2 µg/L No EPA limit set | 3/5 | UCMR-5 | 2025 |
| Gross Beta Particle Activity | 4.57 pCi/L No EPA limit set
worst single sample: 4.6 pCi/L | 2/2 | SYR4 | 2015–2017 |
| Lead | 1.96 µg/L 13% of the EPA limit 15 µg/L
worst single sample: 2 µg/L | 2/43 | SYR4 | 2012–2017 |
| Arsenic | 2.7 µg/L 27% of the EPA limit 10 µg/L | 1/5 | SYR4 | 2012–2019 |
| Bromoform | 0.6000 µg/L No EPA limit set | 1/50 | SYR4 | 2012–2019 |
| Combined Radium (-226 And -228) | 1.5 pCi/L 30% of the EPA limit 5 pCi/L | 1/1 | SYR4 | 2015 |
| Combined Uranium | 1.1 µg/L 3.7% of the EPA limit 30 µg/L | 1/2 | SYR4 | 2015–2017 |
| Di(2-ethylhexyl) Phthalate | 0.9900 µg/L 17% of the EPA limit 6 µg/L | 1/9 | SYR4 | 2012–2018 |
81 contaminants tested, none detected
Utility contact
Frequently asked questions about Harris County Mud 172
Is Harris County Mud 172 tap water safe to drink?
EPA monitoring detected 28 contaminants in Harris County Mud 172's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Harris County Mud 172's water?
EPA monitoring detected Nitrate, Bromodichloromethane, Chloroform, Dibromochloromethane, Dichloroacetic Acid, and others. The full list with the level and data source for each is above.
How many people does Harris County Mud 172 serve?
Harris County Mud 172 reports serving 4,404 people in Texas, per its EPA record.
Has Harris County Mud 172 had any water quality violations?
The EPA has 11 violations on file for Harris County Mud 172, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.