← Texas

Tap water quality report

Kings Manor Mud

EPA monitoring tested this supplier for 109 contaminants and detected 17. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

109
contaminants tested
17
detected
4,377
people served
0
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Harris

Compliance record

No violations on file. The EPA has no formal drinking-water violations recorded for this supplier.

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
270 µg/L 21%
of the EPA limit 1300 µg/L
worst single sample: 286 µg/L
54/62 SYR4 2012–2018
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
9/9 LCR 2024
Barium
249.75 µg/L 12%
of the EPA limit 2000 µg/L
worst single sample: 250 µg/L
2/2 SYR4 2014–2017
Combined Radium (-226 And -228)
1.144 pCi/L 23%
of the EPA limit 5 pCi/L
worst single sample: 1.15 pCi/L
2/2 SYR4 2014–2017
Fluoride
129.5 µg/L 3.2%
of the EPA limit 4000 µg/L
worst single sample: 130 µg/L
2/2 SYR4 2014–2017
Gross Alpha, Excl. Radon And U
5.595 pCi/L 37%
of the EPA limit 15 pCi/L
worst single sample: 5.6 pCi/L
2/2 SYR4 2014–2017
Gross Beta Particle Activity
5.07 pCi/L
No EPA limit set
worst single sample: 5.1 pCi/L
2/2 SYR4 2014–2017
Selenium
4.05 µg/L 8.1%
of the EPA limit 50 µg/L
worst single sample: 4.1 µg/L
2/2 SYR4 2014–2017
Lithium
11 µg/L
No EPA limit set
2/2 UCMR-5 2025
Arsenic
2.2 µg/L 22%
of the EPA limit 10 µg/L
1/2 SYR4 2014–2017
Bromodichloromethane
6.6 µg/L
No EPA limit set
1/12 SYR4 2013–2019
Bromoform
2.5 µg/L
No EPA limit set
1/12 SYR4 2013–2019
Chloroform
2.5 µg/L
No EPA limit set
1/12 SYR4 2013–2019
Dibromochloromethane
5.6 µg/L
No EPA limit set
1/12 SYR4 2013–2019
Ethylbenzene
0.8000 µg/L 0.1%
of the EPA limit 700 µg/L
1/5 SYR4 2015–2019
Lead
0.6000 µg/L 4%
of the EPA limit 15 µg/L
1/62 SYR4 2012–2018
Xylenes, Total
4.4 µg/L 0%
of the EPA limit 10000 µg/L
1/5 SYR4 2015–2019
92 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalAsbestosAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumCombined UraniumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDibromoacetic AcidDichloroacetic AcidDinosebEthylene DibromideEndrinHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidMonochloroacetic AcidNetfosaaNfdhaNmefosaaNitrateNitrate-NitriteNitriteOxamylPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSimazineStyreneTTHMTetrachloroethyleneThallium, TotalTolueneTotal Haloacetic Acids (HAA5)ToxapheneTrichloroacetic AcidTrichloroethyleneVinyl Chloridecis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
SMITH, BOB
Phone
281-290-3102

Frequently asked questions about Kings Manor Mud

Is Kings Manor Mud tap water safe to drink?

EPA monitoring detected 17 contaminants in Kings Manor Mud's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Kings Manor Mud's water?

EPA monitoring detected Copper, Lead, Barium, Combined Radium (-226 And -228), Fluoride, and others. The full list with the level and data source for each is above.

How many people does Kings Manor Mud serve?

Kings Manor Mud reports serving 4,377 people in Texas, per its EPA record.

Has Kings Manor Mud had any water quality violations?

The EPA has no formal drinking-water violations on file for Kings Manor Mud.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.