Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2015-10-01 → 2015-12-31 |
| MCL | Health-based | Resolved | 2015-10-01 → 2015-12-31 |
| MCL | Health-based | Resolved | 2015-10-01 → 2015-12-31 |
| MCL | Health-based | Resolved | 2015-10-01 → 2015-12-31 |
| MCL | Health-based | Resolved | 2005-01-01 → 2005-03-31 |
| MCL | Health-based | Resolved | 2005-01-01 → 2005-03-31 |
| MCL | Health-based | Resolved | 2005-01-01 → 2005-03-31 |
| MCL | Health-based | Resolved | 2005-01-01 → 2005-03-31 |
| MCL | Health-based | Resolved | 2004-03-01 → 2004-06-30 |
| MCL | Health-based | Resolved | 2004-03-01 → 2004-06-30 |
PFAS detected
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 175.795 µg/L 14% of the EPA limit 1300 µg/L
worst single sample: 273 µg/L | 108/109 | SYR4 | 2012–2017 |
| Lead | 16.85 µg/L 112% of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 103 µg/L | 102/109 | SYR4 | 2012–2017 |
| Nitrate | 546.5 µg/L 5.5% of the EPA limit 10000 µg/L
worst single sample: 550 µg/L | 28/32 | SYR4 | 2012–2019 |
| Gross Alpha, Excl. Radon And U | 10.965 pCi/L 73% of the EPA limit 15 pCi/L
worst single sample: 14 pCi/L | 22/26 | SYR4 | 2012–2019 |
| Gross Beta Particle Activity | 15.9 pCi/L No EPA limit set
worst single sample: 16.7 pCi/L | 21/27 | SYR4 | 2012–2019 |
| Combined Radium (-226 And -228) | 3.075 pCi/L 62% of the EPA limit 5 pCi/L
worst single sample: 4.5 pCi/L | 20/23 | SYR4 | 2012–2019 |
| Combined Uranium | 34.665 µg/L 116% of the EPA limit, at the 95th percentile of samples — 30 µg/L
worst single sample: 35.9 µg/L | 20/26 | SYR4 | 2012–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 18/18 | LCR | 2024 |
| Dibromochloromethane | 4 µg/L No EPA limit set
worst single sample: 4.4 µg/L | 9/17 | SYR4 | 2013–2019 |
| Bromodichloromethane | 7.26 µg/L No EPA limit set
worst single sample: 7.4 µg/L | 8/17 | SYR4 | 2013–2019 |
| Bromoform | 2.55 µg/L No EPA limit set
worst single sample: 2.6 µg/L | 6/17 | SYR4 | 2013–2019 |
| Chloroform | 13.725 µg/L No EPA limit set
worst single sample: 14 µg/L | 6/17 | SYR4 | 2013–2019 |
| Nitrate-Nitrite | 445 µg/L 4.5% of the EPA limit 10000 µg/L
worst single sample: 560 µg/L | 6/6 | SYR4 | 2012–2015 |
| Barium | 244.6 µg/L 12% of the EPA limit 2000 µg/L
worst single sample: 245 µg/L | 5/5 | SYR4 | 2013–2019 |
| Fluoride | 527 µg/L 13% of the EPA limit 4000 µg/L
worst single sample: 560 µg/L | 4/4 | SYR4 | 2014–2017 |
| Arsenic | 8.85 µg/L 89% of the EPA limit 10 µg/L
worst single sample: 9.3 µg/L | 3/5 | SYR4 | 2013–2019 |
| Atrazine | 0.1280 µg/L 4.3% of the EPA limit 3 µg/L
worst single sample: 0.1300 µg/L | 3/10 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 1.96 µg/L No EPA limit set
worst single sample: 2 µg/L | 3/7 | SYR4 | 2013–2019 |
| TTHM | 17.46 µg/L 22% of the EPA limit 80 µg/L
worst single sample: 18.7 µg/L | 3/7 | SYR4 | 2013–2019 |
| Total Haloacetic Acids (HAA5) | 22.84 µg/L 38% of the EPA limit 60 µg/L
worst single sample: 25.2 µg/L | 3/7 | SYR4 | 2013–2019 |
| Lithium | 37.9 µg/L No EPA limit set | 3/4 | UCMR-5 | 2025 |
| Cyanide | 70 µg/L 35% of the EPA limit 200 µg/L | 1/4 | SYR4 | 2014–2017 |
| Dichloroacetic Acid | 17.2 µg/L No EPA limit set | 1/7 | SYR4 | 2013–2019 |
| Nitrite | 10 µg/L 1% of the EPA limit 1000 µg/L | 1/6 | SYR4 | 2012–2015 |
| Selenium | 10.1 µg/L 20% of the EPA limit 50 µg/L | 1/5 | SYR4 | 2013–2019 |
| Simazine | 0.1000 µg/L 2.5% of the EPA limit 4 µg/L | 1/10 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 6 µg/L No EPA limit set | 1/7 | SYR4 | 2013–2019 |
79 contaminants tested, none detected
Utility contact
Frequently asked questions about Windfern Forest Utility District
Is Windfern Forest Utility District tap water safe to drink?
EPA monitoring detected 30 contaminants in Windfern Forest Utility District's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Windfern Forest Utility District's water?
EPA monitoring detected Copper, Lead, Nitrate, Gross Alpha, Excl. Radon And U, Gross Beta Particle Activity, and others. The full list with the level and data source for each is above.
How many people does Windfern Forest Utility District serve?
Windfern Forest Utility District reports serving 7,170 people in Texas, per its EPA record.
Has Windfern Forest Utility District had any water quality violations?
The EPA has 35 violations on file for Windfern Forest Utility District, of which 26 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.