Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MR | Monitoring | Resolved | 2014-12-30 |
| MR | Monitoring | Resolved | 2014-12-30 |
| MR | Monitoring | Resolved | 2014-10-01 |
| MR | Monitoring | Resolved | 2014-10-01 |
| MR | Monitoring | Resolved | 2014-10-01 |
| MR | Monitoring | Resolved | 2014-10-01 |
| MR | Monitoring | Resolved | 2013-01-01 → 2013-12-31 |
| MR | Monitoring | Resolved | 2013-01-01 → 2013-12-31 |
| MR | Monitoring | Resolved | 2013-01-01 → 2013-12-31 |
| MR | Monitoring | Resolved | 2013-01-01 → 2013-12-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 144 µg/L 11% of the EPA limit 1300 µg/L
worst single sample: 155 µg/L | 62/80 | SYR4 | 2013–2018 |
| Nitrate | 150 µg/L 1.5% of the EPA limit 10000 µg/L | 58/58 | SYR4 | 2012–2019 |
| Lead | 12.53 µg/L 84% of the EPA limit 15 µg/L
worst single sample: 20.2 µg/L | 27/80 | SYR4 | 2013–2018 |
| Lead | 0.0010 mg/L 6.7% of the EPA limit 0.0150 mg/L | 14/14 | LCR | 2024 |
| Nitrate-Nitrite | 150 µg/L 1.5% of the EPA limit 10000 µg/L | 13/13 | SYR4 | 2012–2015 |
| Lithium | 22.8 µg/L No EPA limit set | 8/8 | UCMR-5 | 2023 |
| Combined Radium (-226 And -228) | 1.453 pCi/L 29% of the EPA limit 5 pCi/L
worst single sample: 1.48 pCi/L | 4/4 | SYR4 | 2012–2017 |
| Arsenic | 2.88 µg/L 29% of the EPA limit 10 µg/L
worst single sample: 2.9 µg/L | 2/2 | SYR4 | 2014–2017 |
| Barium | 195.6 µg/L 9.8% of the EPA limit 2000 µg/L
worst single sample: 197 µg/L | 2/2 | SYR4 | 2014–2017 |
| Fluoride | 259 µg/L 6.5% of the EPA limit 4000 µg/L
worst single sample: 260 µg/L | 2/2 | SYR4 | 2014–2017 |
| Gross Beta Particle Activity | 5.065 pCi/L No EPA limit set
worst single sample: 5.1 pCi/L | 2/4 | SYR4 | 2012–2017 |
| Chloroform | 1.5 µg/L No EPA limit set | 1/11 | SYR4 | 2013–2019 |
| Combined Uranium | 2.8 µg/L 9.3% of the EPA limit 30 µg/L | 1/1 | SYR4 | 2017 |
| Dibromoacetic Acid | 2.6 µg/L No EPA limit set | 1/7 | SYR4 | 2013–2019 |
| Dibromochloromethane | 1 µg/L No EPA limit set | 1/11 | SYR4 | 2013–2019 |
| Dichloroacetic Acid | 3 µg/L No EPA limit set | 1/7 | SYR4 | 2013–2019 |
| Gross Alpha, Excl. Radon And U | 9 pCi/L 60% of the EPA limit 15 pCi/L | 1/1 | SYR4 | 2017 |
| TTHM | 1 µg/L 1.3% of the EPA limit 80 µg/L | 1/7 | SYR4 | 2013–2019 |
| Total Haloacetic Acids (HAA5) | 5.6 µg/L 9.3% of the EPA limit 60 µg/L | 1/7 | SYR4 | 2013–2019 |
90 contaminants tested, none detected
Utility contact
Frequently asked questions about Chelford City Mud
Is Chelford City Mud tap water safe to drink?
EPA monitoring detected 19 contaminants in Chelford City Mud's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Chelford City Mud's water?
EPA monitoring detected Copper, Nitrate, Lead, Lead, Nitrate-Nitrite, and others. The full list with the level and data source for each is above.
How many people does Chelford City Mud serve?
Chelford City Mud reports serving 8,917 people in Texas, per its EPA record.
Has Chelford City Mud had any water quality violations?
The EPA has 17 violations on file for Chelford City Mud, of which 0 are health-based (a contaminant limit or required treatment was breached) and 1 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.