← Texas

Tap water quality report

Harris County Mud 82

EPA monitoring tested this supplier for 109 contaminants and detected 24. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

109
contaminants tested
24
detected
18,990
people served
0
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Harris

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

0
health-based violations
29
violations on file
0
still open
ViolationTypeStatusPeriod
Other Monitoring Resolved 2023-07-30
Other Monitoring Resolved 2023-07-30
MON Monitoring Resolved 2023-06-01 → 2023-06-30
MON Monitoring Resolved 2023-06-01 → 2023-06-30
MON Monitoring Resolved 2023-06-01 → 2023-06-30
MON Monitoring Resolved 2023-06-01 → 2023-06-30
MR Monitoring Resolved 2022-06-04
MR Monitoring Resolved 2022-06-04
MR Monitoring Resolved 2022-06-04
MR Monitoring Resolved 2022-06-04

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
137.6 µg/L 11%
of the EPA limit 1300 µg/L
worst single sample: 170 µg/L
48/62 SYR4 2013–2017
Nitrate
240 µg/L 2.4%
of the EPA limit 10000 µg/L
worst single sample: 250 µg/L
42/48 SYR4 2012–2019
Lead
17.58 µg/L 117%
of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 32 µg/L
31/62 SYR4 2013–2017
Dibromochloromethane
24.925 µg/L
No EPA limit set
worst single sample: 38.5 µg/L
16/26 SYR4 2012–2019
Bromoform
10.64 µg/L
No EPA limit set
worst single sample: 12.2 µg/L
14/26 SYR4 2012–2019
Lead
0.0032 mg/L 22%
of the EPA limit 0.0150 mg/L
14/14 LCR 2024
Bromodichloromethane
34.26 µg/L
No EPA limit set
worst single sample: 44.9 µg/L
8/26 SYR4 2012–2019
Nitrate-Nitrite
233 µg/L 2.3%
of the EPA limit 10000 µg/L
worst single sample: 240 µg/L
8/9 SYR4 2012–2015
Barium
277.1 µg/L 14%
of the EPA limit 2000 µg/L
worst single sample: 281 µg/L
7/7 SYR4 2013–2019
Arsenic
4.375 µg/L 44%
of the EPA limit 10 µg/L
worst single sample: 4.4 µg/L
6/7 SYR4 2013–2019
Fluoride
1007.5 µg/L 25%
of the EPA limit 4000 µg/L
worst single sample: 1010 µg/L
6/6 SYR4 2014–2017
TTHM
86.7 µg/L 108%
of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 100 µg/L
6/10 SYR4 2013–2019
Lithium
27.7 µg/L
No EPA limit set
6/6 UCMR-5 2023
Chloroform
4.395 µg/L
No EPA limit set
worst single sample: 4.8 µg/L
4/26 SYR4 2012–2019
Combined Radium (-226 And -228)
2.35 pCi/L 47%
of the EPA limit 5 pCi/L
worst single sample: 2.5 pCi/L
4/5 SYR4 2013–2019
Di(2-ethylhexyl) Phthalate
1.277 µg/L 21%
of the EPA limit 6 µg/L
worst single sample: 1.3 µg/L
2/12 SYR4 2012–2019
Dibromoacetic Acid
1.295 µg/L
No EPA limit set
worst single sample: 1.3 µg/L
2/10 SYR4 2013–2019
Total Haloacetic Acids (HAA5)
2.435 µg/L 4.1%
of the EPA limit 60 µg/L
worst single sample: 2.5 µg/L
2/10 SYR4 2013–2019
Xylenes, Total
3.825 µg/L 0%
of the EPA limit 10000 µg/L
worst single sample: 4 µg/L
2/16 SYR4 2012–2019
Dichloroacetic Acid
1.2 µg/L
No EPA limit set
1/10 SYR4 2013–2019
Ethylbenzene
0.7000 µg/L 0.1%
of the EPA limit 700 µg/L
1/16 SYR4 2012–2019
Gross Alpha, Excl. Radon And U
4.8 pCi/L 32%
of the EPA limit 15 pCi/L
1/4 SYR4 2016–2019
Gross Beta Particle Activity
4.5 pCi/L
No EPA limit set
1/6 SYR4 2013–2019
Selenium
5 µg/L 10%
of the EPA limit 50 µg/L
1/7 SYR4 2013–2019
85 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalAsbestosAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumCombined UraniumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDinosebEthylene DibromideEndrinHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidMonochloroacetic AcidNetfosaaNfdhaNmefosaaNitriteOxamylPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneThallium, TotalTolueneToxapheneTrichloroacetic AcidTrichloroethyleneVinyl Chloridecis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
CHESNUTT, JERRY
Phone
713-860-6400

Frequently asked questions about Harris County Mud 82

Is Harris County Mud 82 tap water safe to drink?

EPA monitoring detected 24 contaminants in Harris County Mud 82's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Harris County Mud 82's water?

EPA monitoring detected Copper, Nitrate, Lead, Dibromochloromethane, Bromoform, and others. The full list with the level and data source for each is above.

How many people does Harris County Mud 82 serve?

Harris County Mud 82 reports serving 18,990 people in Texas, per its EPA record.

Has Harris County Mud 82 had any water quality violations?

The EPA has 29 violations on file for Harris County Mud 82, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.