← Texas

Tap water quality report

Trail of the Lakes Mud

EPA monitoring tested this supplier for 109 contaminants and detected 23. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

109
contaminants tested
23
detected
9,480
people served
55
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Harris

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

55
health-based violations
78
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Archived 2024-04-01 → 2024-06-30
MCL Health-based Archived 2024-04-01 → 2024-06-30
MCL Health-based Archived 2024-04-01 → 2024-06-30
MCL Health-based Archived 2024-04-01 → 2024-06-30
MCL Health-based Archived 2024-04-01 → 2024-06-30
MCL Health-based Archived 2024-04-01 → 2024-06-30
MCL Health-based Archived 2024-04-01 → 2024-06-30
MCL Health-based Archived 2024-04-01 → 2024-06-30
MCL Health-based Archived 2024-04-01 → 2024-06-30
MCL Health-based Archived 2024-04-01 → 2024-06-30

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
132.5 µg/L 10%
of the EPA limit 1300 µg/L
worst single sample: 190 µg/L
56/64 SYR4 2012–2018
Lead
14.8 µg/L 99%
of the EPA limit 15 µg/L
worst single sample: 22 µg/L
19/64 SYR4 2012–2018
Bromoform
19.25 µg/L
No EPA limit set
worst single sample: 22 µg/L
12/17 SYR4 2012–2019
Dibromochloromethane
9.065 µg/L
No EPA limit set
worst single sample: 10 µg/L
12/17 SYR4 2012–2019
Lead
0.0010 mg/L 6.7%
of the EPA limit 0.0150 mg/L
12/12 LCR 2024
Nitrate
40 µg/L 0.4%
of the EPA limit 10000 µg/L
12/32 SYR4 2012–2019
Bromodichloromethane
2.34 µg/L
No EPA limit set
worst single sample: 2.4 µg/L
7/17 SYR4 2012–2019
TTHM
6.34 µg/L 7.9%
of the EPA limit 80 µg/L
worst single sample: 6.8 µg/L
5/7 SYR4 2013–2019
Arsenic
4.25 µg/L 43%
of the EPA limit 10 µg/L
worst single sample: 4.4 µg/L
4/4 SYR4 2014–2017
Barium
307.35 µg/L 15%
of the EPA limit 2000 µg/L
worst single sample: 324 µg/L
4/4 SYR4 2014–2017
Fluoride
1485.5 µg/L 37%
of the EPA limit 4000 µg/L
worst single sample: 1580 µg/L
4/4 SYR4 2014–2017
Lithium
25.1 µg/L
No EPA limit set
4/4 UCMR-5 2023
Nitrate-Nitrite
39 µg/L 0.4%
of the EPA limit 10000 µg/L
worst single sample: 40 µg/L
3/6 SYR4 2012–2015
Chloroform
1.085 µg/L
No EPA limit set
worst single sample: 1.1 µg/L
2/17 SYR4 2012–2019
Xylenes, Total
2.97 µg/L 0%
of the EPA limit 10000 µg/L
worst single sample: 3.1 µg/L
2/10 SYR4 2012–2019
Combined Radium (-226 And -228)
3.28 pCi/L 66%
of the EPA limit 5 pCi/L
1/1 SYR4 2017
Di(2-ethylhexyl) Phthalate
0.7400 µg/L 12%
of the EPA limit 6 µg/L
1/5 SYR4 2012–2018
Dibromoacetic Acid
2.4 µg/L
No EPA limit set
1/7 SYR4 2013–2019
Ethylbenzene
0.5000 µg/L 0.1%
of the EPA limit 700 µg/L
1/10 SYR4 2012–2019
Gross Alpha, Excl. Radon And U
11.7 pCi/L 78%
of the EPA limit 15 pCi/L
1/2 SYR4 2015–2017
Gross Beta Particle Activity
6.3 pCi/L
No EPA limit set
1/2 SYR4 2015–2017
Selenium
3.2 µg/L 6.4%
of the EPA limit 50 µg/L
1/4 SYR4 2014–2017
Total Haloacetic Acids (HAA5)
2.4 µg/L 4%
of the EPA limit 60 µg/L
1/7 SYR4 2013–2019
86 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalAsbestosAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumCombined UraniumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDichloroacetic AcidDinosebEthylene DibromideEndrinHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidMonochloroacetic AcidNetfosaaNfdhaNmefosaaNitriteOxamylPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneThallium, TotalTolueneToxapheneTrichloroacetic AcidTrichloroethyleneVinyl Chloridecis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
PENDLETON, KIM
Phone
713-651-0111

Frequently asked questions about Trail of the Lakes Mud

Is Trail of the Lakes Mud tap water safe to drink?

EPA monitoring detected 23 contaminants in Trail of the Lakes Mud's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Trail of the Lakes Mud's water?

EPA monitoring detected Copper, Lead, Bromoform, Dibromochloromethane, Lead, and others. The full list with the level and data source for each is above.

How many people does Trail of the Lakes Mud serve?

Trail of the Lakes Mud reports serving 9,480 people in Texas, per its EPA record.

Has Trail of the Lakes Mud had any water quality violations?

The EPA has 78 violations on file for Trail of the Lakes Mud, of which 55 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.