Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MR | Monitoring | Resolved | 2012-01-01 |
| MR | Monitoring | Resolved | 2011-07-01 |
| MR | Monitoring | Resolved | 2011-01-01 |
| MR | Monitoring | Resolved | 2010-07-01 → 2010-09-30 |
| MR | Monitoring | Resolved | 2010-07-01 |
| MR | Monitoring | Resolved | 1992-07-01 → 1993-06-30 |
PFAS detected
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 132.8 µg/L 10% of the EPA limit 1300 µg/L
worst single sample: 215 µg/L | 98/104 | SYR4 | 2012–2019 |
| Lead | 16.22 µg/L 108% of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 27.6 µg/L | 73/104 | SYR4 | 2012–2019 |
| Bromodichloromethane | 10.07 µg/L No EPA limit set
worst single sample: 25 µg/L | 39/42 | SYR4 | 2012–2019 |
| Chloroform | 18.99 µg/L No EPA limit set
worst single sample: 27.6 µg/L | 39/42 | SYR4 | 2012–2019 |
| Dibromochloromethane | 6.05 µg/L No EPA limit set
worst single sample: 20 µg/L | 35/42 | SYR4 | 2012–2019 |
| Nitrate | 847.5 µg/L 8.5% of the EPA limit 10000 µg/L
worst single sample: 1010 µg/L | 34/34 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 23.49 µg/L No EPA limit set
worst single sample: 25 µg/L | 28/30 | SYR4 | 2012–2019 |
| TTHM | 36.935 µg/L 46% of the EPA limit 80 µg/L
worst single sample: 75.9 µg/L | 28/30 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 34.465 µg/L 57% of the EPA limit 60 µg/L
worst single sample: 43.4 µg/L | 28/30 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 7.955 µg/L No EPA limit set
worst single sample: 8.4 µg/L | 28/30 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 4.95 µg/L No EPA limit set
worst single sample: 6.8 µg/L | 26/30 | SYR4 | 2012–2019 |
| Lead | 0.0029 mg/L 19% of the EPA limit 0.0150 mg/L | 15/15 | LCR | 2023 |
| Cyanide | 190 µg/L 95% of the EPA limit 200 µg/L | 11/26 | SYR4 | 2014–2019 |
| Atrazine | 0.2910 µg/L 9.7% of the EPA limit 3 µg/L
worst single sample: 0.3000 µg/L | 10/16 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 773 µg/L 7.7% of the EPA limit 10000 µg/L
worst single sample: 800 µg/L | 7/7 | SYR4 | 2012–2015 |
| Simazine | 0.1370 µg/L 3.4% of the EPA limit 4 µg/L
worst single sample: 0.1400 µg/L | 7/16 | SYR4 | 2012–2019 |
| Barium | 67.01 µg/L 3.4% of the EPA limit 2000 µg/L
worst single sample: 69.8 µg/L | 4/4 | SYR4 | 2014–2017 |
| Fluoride | 380.5 µg/L 9.5% of the EPA limit 4000 µg/L
worst single sample: 400 µg/L | 4/4 | SYR4 | 2014–2017 |
| Bromoform | 3.22 µg/L No EPA limit set
worst single sample: 3.3 µg/L | 3/42 | SYR4 | 2012–2019 |
| Gross Beta Particle Activity | 13.52 pCi/L No EPA limit set
worst single sample: 13.6 pCi/L | 3/4 | SYR4 | 2012–2017 |
| Lithium | 20 µg/L No EPA limit set | 3/8 | UCMR-5 | 2023 |
| Combined Radium (-226 And -228) | 6.555 pCi/L 131% of the EPA limit, at the 95th percentile of samples — 5 pCi/L
worst single sample: 6.6 pCi/L | 2/2 | SYR4 | 2012 |
| Combined Uranium | 10.6 µg/L 35% of the EPA limit 30 µg/L
worst single sample: 10.7 µg/L | 2/4 | SYR4 | 2012–2017 |
| Gross Alpha, Excl. Radon And U | 26.395 pCi/L 176% of the EPA limit, at the 95th percentile of samples — 15 pCi/L
worst single sample: 26.7 pCi/L | 2/4 | SYR4 | 2012–2017 |
| Monochloroacetic Acid | 6.095 µg/L No EPA limit set
worst single sample: 6.3 µg/L | 2/30 | SYR4 | 2012–2019 |
| Nitrite | 67.5 µg/L 6.8% of the EPA limit 1000 µg/L
worst single sample: 70 µg/L | 2/7 | SYR4 | 2012–2015 |
| Xylenes, Total | 0.5950 µg/L 0% of the EPA limit 10000 µg/L
worst single sample: 0.6000 µg/L | 2/12 | SYR4 | 2012–2019 |
| Di(2-ethylhexyl) Phthalate | 0.6400 µg/L 11% of the EPA limit 6 µg/L | 1/16 | SYR4 | 2012–2019 |
76 contaminants tested, none detected
Utility contact
Frequently asked questions about Jackrabbit Road Pud
Is Jackrabbit Road Pud tap water safe to drink?
EPA monitoring detected 33 contaminants in Jackrabbit Road Pud's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Jackrabbit Road Pud's water?
EPA monitoring detected Copper, Lead, Bromodichloromethane, Chloroform, Dibromochloromethane, and others. The full list with the level and data source for each is above.
How many people does Jackrabbit Road Pud serve?
Jackrabbit Road Pud reports serving 8,346 people in Texas, per its EPA record.
Has Jackrabbit Road Pud had any water quality violations?
The EPA has 6 violations on file for Jackrabbit Road Pud, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.