Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2007-04-01 → 2007-06-30 |
| MCL | Health-based | Resolved | 2007-04-01 → 2007-06-30 |
| MCL | Health-based | Resolved | 2007-04-01 → 2007-06-30 |
| MR | Monitoring | Resolved | 2019-04-01 |
| MR | Monitoring | Resolved | 2019-04-01 |
| MR | Monitoring | Resolved | 2013-10-01 |
| MR | Monitoring | Resolved | 2013-10-01 |
| MR | Monitoring | Resolved | 2012-10-01 |
| MR | Monitoring | Resolved | 2012-10-01 |
| MR | Monitoring | Resolved | 2010-11-01 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 299 µg/L 23% of the EPA limit 1300 µg/L
worst single sample: 545 µg/L | 161/210 | SYR4 | 2012–2019 |
| Chloroform | 4.78 µg/L No EPA limit set
worst single sample: 7.2 µg/L | 32/150 | SYR4 | 2012–2019 |
| Bromodichloromethane | 4.4 µg/L No EPA limit set
worst single sample: 13 µg/L | 31/150 | SYR4 | 2012–2019 |
| Dibromochloromethane | 4.65 µg/L No EPA limit set
worst single sample: 14 µg/L | 31/150 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 6 µg/L 10% of the EPA limit 60 µg/L
worst single sample: 7.2 µg/L | 31/117 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 3.82 µg/L No EPA limit set
worst single sample: 4.4 µg/L | 29/117 | SYR4 | 2012–2019 |
| TTHM | 14.175 µg/L 18% of the EPA limit 80 µg/L
worst single sample: 15.2 µg/L | 26/117 | SYR4 | 2012–2019 |
| Lead | 54.36 µg/L 362% of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 98.5 µg/L | 25/210 | SYR4 | 2012–2019 |
| Nitrate | 69 µg/L 0.7% of the EPA limit 10000 µg/L
worst single sample: 70 µg/L | 22/80 | SYR4 | 2012–2019 |
| Lead | 0.0019 mg/L 13% of the EPA limit 0.0150 mg/L | 13/13 | LCR | 2023 |
| Barium | 285 µg/L 14% of the EPA limit 2000 µg/L | 11/11 | SYR4 | 2014–2019 |
| Fluoride | 520 µg/L 13% of the EPA limit 4000 µg/L
worst single sample: 530 µg/L | 11/11 | SYR4 | 2014–2019 |
| Bromoform | 4.44 µg/L No EPA limit set
worst single sample: 6 µg/L | 9/150 | SYR4 | 2012–2019 |
| Lithium | 17.5 µg/L No EPA limit set | 8/12 | UCMR-5 | 2024 |
| Gross Alpha, Excl. Radon And U | 5.35 pCi/L 36% of the EPA limit 15 pCi/L
worst single sample: 5.6 pCi/L | 6/8 | SYR4 | 2014–2019 |
| Xylenes, Total | 4.9 µg/L 0% of the EPA limit 10000 µg/L
worst single sample: 6.1 µg/L | 6/33 | SYR4 | 2014–2019 |
| Arsenic | 2.76 µg/L 28% of the EPA limit 10 µg/L
worst single sample: 2.8 µg/L | 5/11 | SYR4 | 2014–2019 |
| Di(2-ethylhexyl) Phthalate | 2.59 µg/L 43% of the EPA limit 6 µg/L
worst single sample: 2.7 µg/L | 3/23 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 2.18 µg/L No EPA limit set
worst single sample: 2.3 µg/L | 3/117 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 50 µg/L 0.5% of the EPA limit 10000 µg/L | 3/13 | SYR4 | 2012–2015 |
| Combined Uranium | 2.07 µg/L 6.9% of the EPA limit 30 µg/L
worst single sample: 2.1 µg/L | 2/8 | SYR4 | 2014–2019 |
| Monochloroacetic Acid | 4.795 µg/L No EPA limit set
worst single sample: 4.8 µg/L | 2/117 | SYR4 | 2012–2019 |
| Combined Radium (-226 And -228) | 1.01 pCi/L 20% of the EPA limit 5 pCi/L | 1/3 | SYR4 | 2017 |
| Ethylbenzene | 1.2 µg/L 0.2% of the EPA limit 700 µg/L | 1/33 | SYR4 | 2014–2019 |
| Gross Beta Particle Activity | 4.4 pCi/L No EPA limit set | 1/8 | SYR4 | 2014–2019 |
| Toluene | 0.7000 µg/L 0.1% of the EPA limit 1000 µg/L | 1/33 | SYR4 | 2014–2019 |
| Trichloroacetic Acid | 2.3 µg/L No EPA limit set | 1/117 | SYR4 | 2012–2019 |
82 contaminants tested, none detected
Utility contact
Frequently asked questions about City of Houston Ud 5 - Kingwood
Is City of Houston Ud 5 - Kingwood tap water safe to drink?
EPA monitoring detected 27 contaminants in City of Houston Ud 5 - Kingwood's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in City of Houston Ud 5 - Kingwood's water?
EPA monitoring detected Copper, Chloroform, Bromodichloromethane, Dibromochloromethane, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.
How many people does City of Houston Ud 5 - Kingwood serve?
City of Houston Ud 5 - Kingwood reports serving 80,073 people in Texas, per its EPA record.
Has City of Houston Ud 5 - Kingwood had any water quality violations?
The EPA has 19 violations on file for City of Houston Ud 5 - Kingwood, of which 3 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.