Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MR | Monitoring | Resolved | 2013-12-30 |
| MR | Monitoring | Resolved | 2011-10-01 |
PFAS detected
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Bromodichloromethane | 15.9 µg/L No EPA limit set
worst single sample: 32 µg/L | 51/51 | SYR4 | 2014–2019 |
| Chloroform | 36.35 µg/L No EPA limit set
worst single sample: 52.7 µg/L | 51/51 | SYR4 | 2014–2019 |
| Dibromochloromethane | 10.62 µg/L No EPA limit set
worst single sample: 17.5 µg/L | 47/51 | SYR4 | 2014–2019 |
| Copper | 57.825 µg/L 4.4% of the EPA limit 1300 µg/L
worst single sample: 78 µg/L | 46/62 | SYR4 | 2013–2019 |
| Dichloroacetic Acid | 33.1 µg/L No EPA limit set
worst single sample: 40.4 µg/L | 45/45 | SYR4 | 2014–2019 |
| TTHM | 53.72 µg/L 67% of the EPA limit 80 µg/L
worst single sample: 106 µg/L | 45/45 | SYR4 | 2014–2019 |
| Total Haloacetic Acids (HAA5) | 45.1 µg/L 75% of the EPA limit 60 µg/L
worst single sample: 65.7 µg/L | 45/45 | SYR4 | 2014–2019 |
| Trichloroacetic Acid | 13.46 µg/L No EPA limit set
worst single sample: 19.2 µg/L | 45/45 | SYR4 | 2014–2019 |
| Dibromoacetic Acid | 4.775 µg/L No EPA limit set
worst single sample: 6.1 µg/L | 36/45 | SYR4 | 2014–2019 |
| Nitrate | 580 µg/L 5.8% of the EPA limit 10000 µg/L | 16/16 | SYR4 | 2012–2019 |
| Bromoform | 9.8 µg/L No EPA limit set
worst single sample: 12 µg/L | 12/51 | SYR4 | 2014–2019 |
| Atrazine | 0.2655 µg/L 8.9% of the EPA limit 3 µg/L
worst single sample: 0.2700 µg/L | 10/11 | SYR4 | 2015–2019 |
| Lead | 3.064 µg/L 20% of the EPA limit 15 µg/L
worst single sample: 3.19 µg/L | 10/62 | SYR4 | 2013–2019 |
| Simazine | 0.2785 µg/L 7% of the EPA limit 4 µg/L
worst single sample: 0.3100 µg/L | 8/11 | SYR4 | 2015–2019 |
| Lead | 0.0025 mg/L 17% of the EPA limit 0.0150 mg/L | 6/6 | LCR | 2025 |
| Monochloroacetic Acid | 5.3 µg/L No EPA limit set
worst single sample: 5.5 µg/L | 6/45 | SYR4 | 2014–2019 |
| Nitrate-Nitrite | 505 µg/L 5.1% of the EPA limit 10000 µg/L
worst single sample: 520 µg/L | 3/3 | SYR4 | 2012–2015 |
| Lithium | 12.2 µg/L No EPA limit set | 3/4 | UCMR-5 | 2023 |
| Barium | 83.82 µg/L 4.2% of the EPA limit 2000 µg/L
worst single sample: 84.8 µg/L | 2/2 | SYR4 | 2014–2017 |
| Cyanide | 163 µg/L 82% of the EPA limit 200 µg/L
worst single sample: 170 µg/L | 2/2 | SYR4 | 2014–2017 |
| Fluoride | 357 µg/L 8.9% of the EPA limit 4000 µg/L
worst single sample: 360 µg/L | 2/2 | SYR4 | 2014–2017 |
| Combined Radium (-226 And -228) | 2 pCi/L 40% of the EPA limit 5 pCi/L | 1/1 | SYR4 | 2014 |
| Combined Uranium | 1.1 µg/L 3.7% of the EPA limit 30 µg/L | 1/1 | SYR4 | 2014 |
| Di(2-ethylhexyl) Phthalate | 1.7 µg/L 28% of the EPA limit 6 µg/L | 1/11 | SYR4 | 2015–2019 |
| Gross Alpha, Excl. Radon And U | 1 pCi/L 6.7% of the EPA limit 15 pCi/L | 1/1 | SYR4 | 2014 |
| Gross Beta Particle Activity | 4.8 pCi/L No EPA limit set | 1/1 | SYR4 | 2014 |
76 contaminants tested, none detected
Utility contact
Frequently asked questions about Fort Bend County Mud 142
Is Fort Bend County Mud 142 tap water safe to drink?
EPA monitoring detected 33 contaminants in Fort Bend County Mud 142's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Fort Bend County Mud 142's water?
EPA monitoring detected Bromodichloromethane, Chloroform, Dibromochloromethane, Copper, Dichloroacetic Acid, and others. The full list with the level and data source for each is above.
How many people does Fort Bend County Mud 142 serve?
Fort Bend County Mud 142 reports serving 11,595 people in Texas, per its EPA record.
Has Fort Bend County Mud 142 had any water quality violations?
The EPA has 2 violations on file for Fort Bend County Mud 142, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.