← Texas

Tap water quality report

Fort Bend County Mud 119

EPA monitoring tested this supplier for 109 contaminants and detected 25. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

109
contaminants tested
25
detected
5,088
people served
0
health-based violations
Water source
SWP
Ownership
Local government
Counties served
Fort Bend

Compliance record

No violations on file. The EPA has no formal drinking-water violations recorded for this supplier.

PFAS detected

PFAS are industrial “forever chemicals”. These are the EPA's latest nationwide test results (2023–2025).
ContaminantMaxDetection ratePeriod
Pfpea 0.0030 µg/L 1/4 2025

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Bromodichloromethane
13.14 µg/L
No EPA limit set
worst single sample: 17.6 µg/L
65/67 SYR4 2012–2019
Chloroform
30.08 µg/L
No EPA limit set
worst single sample: 32.1 µg/L
65/67 SYR4 2012–2019
Dichloroacetic Acid
29.505 µg/L
No EPA limit set
worst single sample: 32 µg/L
60/62 SYR4 2012–2019
TTHM
44.805 µg/L 56%
of the EPA limit 80 µg/L
worst single sample: 49 µg/L
60/62 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
45.22 µg/L 75%
of the EPA limit 60 µg/L
worst single sample: 49.4 µg/L
60/62 SYR4 2012–2019
Dibromochloromethane
7.175 µg/L
No EPA limit set
worst single sample: 11.1 µg/L
58/67 SYR4 2012–2019
Trichloroacetic Acid
10.33 µg/L
No EPA limit set
worst single sample: 11.3 µg/L
58/62 SYR4 2012–2019
Copper
747 µg/L 57%
of the EPA limit 1300 µg/L
worst single sample: 1104.5 µg/L
47/61 SYR4 2013–2019
Dibromoacetic Acid
5.225 µg/L
No EPA limit set
worst single sample: 8.7 µg/L
46/62 SYR4 2012–2019
Lead
3.78 µg/L 25%
of the EPA limit 15 µg/L
worst single sample: 25 µg/L
23/61 SYR4 2013–2019
Nitrate
660 µg/L 6.6%
of the EPA limit 10000 µg/L
16/16 SYR4 2012–2019
Bromoform
6.8 µg/L
No EPA limit set
worst single sample: 8.3 µg/L
13/67 SYR4 2012–2019
Lead
0.00058 mg/L 3.8%
of the EPA limit 0.0150 mg/L
8/8 LCR 2025
Simazine
0.2110 µg/L 5.3%
of the EPA limit 4 µg/L
worst single sample: 0.2200 µg/L
7/8 SYR4 2015–2019
Atrazine
0.4580 µg/L 15%
of the EPA limit 3 µg/L
worst single sample: 0.5100 µg/L
5/8 SYR4 2015–2019
Monochloroacetic Acid
7.98 µg/L
No EPA limit set
worst single sample: 8.5 µg/L
5/62 SYR4 2012–2019
Nitrate-Nitrite
546 µg/L 5.5%
of the EPA limit 10000 µg/L
worst single sample: 570 µg/L
3/3 SYR4 2012–2015
Barium
70.445 µg/L 3.5%
of the EPA limit 2000 µg/L
worst single sample: 71.4 µg/L
2/2 SYR4 2016–2019
Cyanide
128 µg/L 64%
of the EPA limit 200 µg/L
worst single sample: 130 µg/L
2/2 SYR4 2014–2017
Fluoride
347 µg/L 8.7%
of the EPA limit 4000 µg/L
worst single sample: 350 µg/L
2/2 SYR4 2014–2017
Monobromoacetic Acid
1.295 µg/L
No EPA limit set
worst single sample: 1.3 µg/L
2/62 SYR4 2012–2019
Lithium
17.8 µg/L
No EPA limit set
2/4 UCMR-5 2025
Combined Radium (-226 And -228)
1.5 pCi/L 30%
of the EPA limit 5 pCi/L
1/1 SYR4 2015
Gross Beta Particle Activity
5 pCi/L
No EPA limit set
1/1 SYR4 2015
84 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalArsenicAsbestosBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumCombined UraniumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebEthylene DibromideEndrinEthylbenzeneGross Alpha, Excl. Radon And UHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorNetfosaaNfdhaNmefosaaNitriteOxamylPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpesPftaPftrdaPfunaPentachlorophenolPicloramSeleniumStyreneTetrachloroethyleneThallium, TotalTolueneToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
SHELBY, ALAN
Phone
281-578-4200

Frequently asked questions about Fort Bend County Mud 119

Is Fort Bend County Mud 119 tap water safe to drink?

EPA monitoring detected 25 contaminants in Fort Bend County Mud 119's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Fort Bend County Mud 119's water?

EPA monitoring detected Bromodichloromethane, Chloroform, Dichloroacetic Acid, TTHM, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.

How many people does Fort Bend County Mud 119 serve?

Fort Bend County Mud 119 reports serving 5,088 people in Texas, per its EPA record.

Has Fort Bend County Mud 119 had any water quality violations?

The EPA has no formal drinking-water violations on file for Fort Bend County Mud 119.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.