Compliance record
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 177.12 µg/L 14% of the EPA limit 1300 µg/L
worst single sample: 660 µg/L | 67/112 | SYR4 | 2015–2019 |
| Nitrate | 50 µg/L 0.5% of the EPA limit 10000 µg/L | 28/32 | SYR4 | 2012–2019 |
| Lead | 8.015 µg/L 53% of the EPA limit 15 µg/L
worst single sample: 9.8 µg/L | 18/112 | SYR4 | 2015–2019 |
| Lead | 0.00051 mg/L 3.4% of the EPA limit 0.0150 mg/L | 10/10 | LCR | 2025 |
| Combined Radium (-226 And -228) | 3.418 pCi/L 68% of the EPA limit 5 pCi/L
worst single sample: 3.7 pCi/L | 7/9 | SYR4 | 2012–2019 |
| Combined Uranium | 8.28 µg/L 28% of the EPA limit 30 µg/L
worst single sample: 8.4 µg/L | 7/9 | SYR4 | 2015–2019 |
| Gross Alpha, Excl. Radon And U | 12.8 pCi/L 85% of the EPA limit 15 pCi/L
worst single sample: 14 pCi/L | 7/9 | SYR4 | 2015–2019 |
| Fluoride | 1257.5 µg/L 31% of the EPA limit 4000 µg/L
worst single sample: 1390 µg/L | 6/6 | SYR4 | 2013–2019 |
| Nitrate-Nitrite | 50 µg/L 0.5% of the EPA limit 10000 µg/L | 6/6 | SYR4 | 2012–2015 |
| Bromoform | 2.48 µg/L No EPA limit set
worst single sample: 2.5 µg/L | 5/51 | SYR4 | 2013–2019 |
| TTHM | 3.82 µg/L 4.8% of the EPA limit 80 µg/L
worst single sample: 4 µg/L | 5/40 | SYR4 | 2013–2019 |
| Barium | 182.7 µg/L 9.1% of the EPA limit 2000 µg/L
worst single sample: 183 µg/L | 4/4 | SYR4 | 2015–2018 |
| Dibromoacetic Acid | 1.34 µg/L No EPA limit set
worst single sample: 1.4 µg/L | 4/40 | SYR4 | 2013–2019 |
| Dibromochloromethane | 2.18 µg/L No EPA limit set
worst single sample: 2.3 µg/L | 4/51 | SYR4 | 2013–2019 |
| Gross Beta Particle Activity | 6.095 pCi/L No EPA limit set
worst single sample: 6.2 pCi/L | 4/11 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 1.34 µg/L 2.2% of the EPA limit 60 µg/L
worst single sample: 1.4 µg/L | 4/40 | SYR4 | 2013–2019 |
| Lithium | 29.4 µg/L No EPA limit set | 4/4 | UCMR-5 | 2023 |
| Arsenic | 4.44 µg/L 44% of the EPA limit 10 µg/L
worst single sample: 4.6 µg/L | 3/4 | SYR4 | 2015–2018 |
| Xylenes, Total | 1.9 µg/L 0% of the EPA limit 10000 µg/L | 2/11 | SYR4 | 2014–2019 |
| Bromodichloromethane | 1.2 µg/L No EPA limit set | 1/51 | SYR4 | 2013–2019 |
| Selenium | 4.1 µg/L 8.2% of the EPA limit 50 µg/L | 1/4 | SYR4 | 2015–2018 |
88 contaminants tested, none detected
Utility contact
Frequently asked questions about City of Sugar Land - Greatwood
Is City of Sugar Land - Greatwood tap water safe to drink?
EPA monitoring detected 21 contaminants in City of Sugar Land - Greatwood's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in City of Sugar Land - Greatwood's water?
EPA monitoring detected Copper, Nitrate, Lead, Lead, Combined Radium (-226 And -228), and others. The full list with the level and data source for each is above.
How many people does City of Sugar Land - Greatwood serve?
City of Sugar Land - Greatwood reports serving 12,368 people in Texas, per its EPA record.
Has City of Sugar Land - Greatwood had any water quality violations?
The EPA has no formal drinking-water violations on file for City of Sugar Land - Greatwood.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.