Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| Other | Monitoring | Resolved | 2025-07-01 |
| Other | Monitoring | Resolved | 2025-07-01 |
| Other | Monitoring | Resolved | 2016-07-01 |
| Other | Monitoring | Resolved | 2016-07-01 |
| MR | Monitoring | Resolved | 2013-12-30 |
| MR | Monitoring | Resolved | 2013-01-01 → 2013-03-31 |
| MR | Monitoring | Resolved | 2013-01-01 → 2013-03-31 |
| MR | Monitoring | Resolved | 2013-01-01 → 2013-03-31 |
| MR | Monitoring | Resolved | 2013-01-01 → 2013-03-31 |
| MR | Monitoring | Resolved | 2012-11-01 → 2012-11-30 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 221.2 µg/L 17% of the EPA limit 1300 µg/L
worst single sample: 296 µg/L | 65/66 | SYR4 | 2013–2019 |
| Nitrate | 320 µg/L 3.2% of the EPA limit 10000 µg/L
worst single sample: 330 µg/L | 48/48 | SYR4 | 2012–2019 |
| Selenium | 49.905 µg/L 100% of the EPA limit 50 µg/L
worst single sample: 53.7 µg/L | 28/28 | SYR4 | 2014–2019 |
| Lead | 4.15 µg/L 28% of the EPA limit 15 µg/L
worst single sample: 5 µg/L | 18/66 | SYR4 | 2013–2019 |
| Lead | 0.00090 mg/L 6% of the EPA limit 0.0150 mg/L | 13/13 | LCR | 2025 |
| Nitrate-Nitrite | 320 µg/L 3.2% of the EPA limit 10000 µg/L | 9/9 | SYR4 | 2012–2015 |
| Arsenic | 6.7 µg/L 67% of the EPA limit 10 µg/L | 6/6 | SYR4 | 2014–2017 |
| Barium | 232 µg/L 12% of the EPA limit 2000 µg/L | 6/6 | SYR4 | 2014–2017 |
| Combined Radium (-226 And -228) | 2.2775 pCi/L 46% of the EPA limit 5 pCi/L
worst single sample: 2.3 pCi/L | 6/6 | SYR4 | 2013–2019 |
| Fluoride | 250 µg/L 6.3% of the EPA limit 4000 µg/L
worst single sample: 260 µg/L | 6/6 | SYR4 | 2014–2017 |
| Gross Beta Particle Activity | 7.75 pCi/L No EPA limit set
worst single sample: 8.4 pCi/L | 6/6 | SYR4 | 2013–2019 |
| Lithium | 19.1 µg/L No EPA limit set | 6/6 | UCMR-5 | 2024 |
| Combined Uranium | 13.4 µg/L 45% of the EPA limit 30 µg/L
worst single sample: 14.6 µg/L | 5/5 | SYR4 | 2014–2019 |
| Dibromochloromethane | 14.22 µg/L No EPA limit set
worst single sample: 17 µg/L | 5/26 | SYR4 | 2013–2019 |
| Gross Alpha, Excl. Radon And U | 6.6 pCi/L 44% of the EPA limit 15 pCi/L
worst single sample: 7 pCi/L | 5/5 | SYR4 | 2014–2019 |
| Bromoform | 63.395 µg/L No EPA limit set
worst single sample: 74 µg/L | 4/26 | SYR4 | 2013–2019 |
| Bromodichloromethane | 4.815 µg/L No EPA limit set
worst single sample: 5 µg/L | 2/26 | SYR4 | 2013–2019 |
| Chloroform | 5.2 µg/L No EPA limit set | 1/26 | SYR4 | 2013–2019 |
| Dibromoacetic Acid | 1 µg/L No EPA limit set | 1/9 | SYR4 | 2013–2019 |
| Total Haloacetic Acids (HAA5) | 1 µg/L 1.7% of the EPA limit 60 µg/L | 1/9 | SYR4 | 2013–2019 |
| Xylenes, Total | 1.3 µg/L 0% of the EPA limit 10000 µg/L | 1/17 | SYR4 | 2015–2019 |
88 contaminants tested, none detected
Utility contact
Frequently asked questions about City of Meadows Place
Is City of Meadows Place tap water safe to drink?
EPA monitoring detected 21 contaminants in City of Meadows Place's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in City of Meadows Place's water?
EPA monitoring detected Copper, Nitrate, Selenium, Lead, Lead, and others. The full list with the level and data source for each is above.
How many people does City of Meadows Place serve?
City of Meadows Place reports serving 5,000 people in Texas, per its EPA record.
Has City of Meadows Place had any water quality violations?
The EPA has 27 violations on file for City of Meadows Place, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.