← Texas

Tap water quality report

City of Odessa

EPA monitoring tested this supplier for 107 contaminants and detected 31. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

107
contaminants tested
31
detected
123,334
people served
12
health-based violations
Water source
Surface water
Ownership
Local government
Counties served
Ector

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

12
health-based violations
48
violations on file
1
still open
ViolationTypeStatusPeriod
TT Health-based Resolved 2021-02-01 → 2021-02-28
TT Health-based Resolved 2021-02-01 → 2021-02-28
TT Health-based Resolved 2021-02-01 → 2021-02-28
TT Health-based Resolved 2021-02-01 → 2021-02-28
TT Health-based Resolved 2019-10-01 → 2019-10-31
TT Health-based Resolved 2019-10-01 → 2019-10-31
TT Health-based Resolved 2019-10-01 → 2019-10-31
TT Health-based Resolved 2019-10-01 → 2019-10-31
MCL Health-based Archived 1983-08-09 → 1983-11-08
MCL Health-based Archived 1983-06-01 → 1983-08-31

PFAS detected

PFAS are industrial “forever chemicals”. These are the EPA's latest nationwide test results (2023–2025).
ContaminantMaxDetection ratePeriod
PFBS 0.0045 µg/L 4/4 2025
PFHXS 0.0049 µg/L 4/4 2025
Pfba 0.0054 µg/L 1/4 2025

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Bromodichloromethane
11.725 µg/L
No EPA limit set
worst single sample: 39.5 µg/L
256/257 SYR4 2012–2019
Dibromochloromethane
18.73 µg/L
No EPA limit set
worst single sample: 25.3 µg/L
255/257 SYR4 2012–2019
Bromoform
42.1 µg/L
No EPA limit set
worst single sample: 64.2 µg/L
251/257 SYR4 2012–2019
TTHM
68.03 µg/L 85%
of the EPA limit 80 µg/L
worst single sample: 93.4 µg/L
248/250 SYR4 2012–2019
Chloroform
4.71 µg/L
No EPA limit set
worst single sample: 22.6 µg/L
241/257 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
25.95 µg/L 43%
of the EPA limit 60 µg/L
worst single sample: 35.9 µg/L
235/249 SYR4 2012–2019
Dichloroacetic Acid
7.64 µg/L
No EPA limit set
worst single sample: 15.3 µg/L
217/249 SYR4 2012–2019
Dibromoacetic Acid
18.675 µg/L
No EPA limit set
worst single sample: 25.5 µg/L
214/249 SYR4 2012–2019
Monobromoacetic Acid
4.5 µg/L
No EPA limit set
worst single sample: 7 µg/L
181/249 SYR4 2012–2019
Copper
250.8 µg/L 19%
of the EPA limit 1300 µg/L
worst single sample: 410 µg/L
125/125 SYR4 2012–2017
Monochloroacetic Acid
12.31 µg/L
No EPA limit set
worst single sample: 26.6 µg/L
110/249 SYR4 2012–2019
Trichloroacetic Acid
2.4 µg/L
No EPA limit set
worst single sample: 3.4 µg/L
110/249 SYR4 2012–2019
Lead
7.86 µg/L 52%
of the EPA limit 15 µg/L
worst single sample: 21.8 µg/L
82/125 SYR4 2012–2017
Nitrate
813.8 µg/L 8.1%
of the EPA limit 10000 µg/L
worst single sample: 853 µg/L
28/28 SYR4 2012–2019
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
19/19 LCR 2024
Fluoride
880.5 µg/L 22%
of the EPA limit 4000 µg/L
worst single sample: 1150 µg/L
8/8 SYR4 2012–2019
Arsenic
2.631 µg/L 26%
of the EPA limit 10 µg/L
worst single sample: 2.73 µg/L
7/7 SYR4 2013–2019
Barium
196.1 µg/L 9.8%
of the EPA limit 2000 µg/L
worst single sample: 203 µg/L
7/7 SYR4 2013–2019
Selenium
7.126 µg/L 14%
of the EPA limit 50 µg/L
worst single sample: 7.6 µg/L
5/7 SYR4 2013–2019
Antimony, Total
0.6285 µg/L 10%
of the EPA limit 6 µg/L
worst single sample: 0.6300 µg/L
4/7 SYR4 2013–2019
Chromium
2.15985 µg/L 2.2%
of the EPA limit 100 µg/L
worst single sample: 2.4 µg/L
4/7 SYR4 2013–2019
Lithium
48 µg/L
No EPA limit set
4/4 UCMR-5 2025
Cyanide
225.3 µg/L 113%
of the EPA limit, at the 95th percentile of samples — 200 µg/L
worst single sample: 232 µg/L
3/3 SYR4 2015–2019
Atrazine
0.1000 µg/L 3.3%
of the EPA limit 3 µg/L
1/11 SYR4 2012–2019
Carbon Tetrachloride
1.44 µg/L 29%
of the EPA limit 5 µg/L
1/8 SYR4 2012–2019
Combined Uranium
1.5 µg/L 5%
of the EPA limit 30 µg/L
1/1 SYR4 2017
Gross Beta Particle Activity
6.1 pCi/L
No EPA limit set
1/1 SYR4 2017
Thallium, Total
0.4550 µg/L 23%
of the EPA limit 2 µg/L
1/7 SYR4 2013–2019
76 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAsbestosBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCadmiumCarbofuranChlordaneDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebEthylene DibromideEndrinEthylbenzeneGross Alpha, Excl. Radon And UHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorNetfosaaNfdhaNmefosaaNitriteOxamylPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneTolueneToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
HENDRICK, CAL
Phone
432-335-4104
Email
[email protected]

Frequently asked questions about City of Odessa

Is City of Odessa tap water safe to drink?

EPA monitoring detected 31 contaminants in City of Odessa's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in City of Odessa's water?

EPA monitoring detected Bromodichloromethane, Dibromochloromethane, Bromoform, TTHM, Chloroform, and others. The full list with the level and data source for each is above.

How many people does City of Odessa serve?

City of Odessa reports serving 123,334 people in Texas, per its EPA record.

Has City of Odessa had any water quality violations?

The EPA has 48 violations on file for City of Odessa, of which 12 are health-based (a contaminant limit or required treatment was breached) and 1 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.