← Texas

Tap water quality report

City of Pearland

EPA monitoring tested this supplier for 109 contaminants and detected 34. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

109
contaminants tested
34
detected
125,828
people served
13
health-based violations
Water source
Surface water
Ownership
Local government
Counties served
Brazoria

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

13
health-based violations
61
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2008-06-01 → 2008-06-30
MCL Health-based Resolved 2008-06-01 → 2008-06-30
MCL Health-based Resolved 2008-06-01 → 2008-06-30
MCL Health-based Resolved 2007-04-01 → 2007-04-30
MCL Health-based Resolved 2007-04-01 → 2007-04-30
MCL Health-based Resolved 2007-04-01 → 2007-04-30
MCL Health-based Resolved 2004-06-01 → 2004-06-30
MCL Health-based Resolved 2004-06-01 → 2004-06-30
MCL Health-based Resolved 2004-06-01 → 2004-06-30
MCL Health-based Resolved 2004-06-01 → 2004-06-30

PFAS detected

PFAS are industrial “forever chemicals”. These are the EPA's latest nationwide test results (2023–2025).
ContaminantMaxDetection ratePeriod
Pfpea 0.0667 µg/L 14/32 2025
Pfba 0.0202 µg/L 11/32 2025
Pfhxa 0.0063 µg/L 9/32 2025
PFBS 0.0037 µg/L 3/32 2025
PFOS 0.0044 µg/L 2/32 2025
PFHXS 0.0041 µg/L 1/32 2025

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
656.4 µg/L 50%
of the EPA limit 1300 µg/L
worst single sample: 2500 µg/L
205/221 SYR4 2012–2019
Chloroform
31.1 µg/L
No EPA limit set
worst single sample: 37.9 µg/L
138/305 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
49.05 µg/L 82%
of the EPA limit 60 µg/L
worst single sample: 57.3 µg/L
131/248 SYR4 2012–2019
Bromodichloromethane
12.8 µg/L
No EPA limit set
worst single sample: 21 µg/L
130/305 SYR4 2012–2019
TTHM
43.9 µg/L 55%
of the EPA limit 80 µg/L
worst single sample: 49.8 µg/L
129/248 SYR4 2012–2019
Dichloroacetic Acid
33 µg/L
No EPA limit set
worst single sample: 40.3 µg/L
126/248 SYR4 2012–2019
Nitrate
1020 µg/L 10%
of the EPA limit 10000 µg/L
worst single sample: 1240 µg/L
124/198 SYR4 2012–2019
Trichloroacetic Acid
10.915 µg/L
No EPA limit set
worst single sample: 12.7 µg/L
114/248 SYR4 2012–2019
Dibromochloromethane
6.415 µg/L
No EPA limit set
worst single sample: 20 µg/L
112/305 SYR4 2012–2019
Lead
8 µg/L 53%
of the EPA limit 15 µg/L
worst single sample: 84 µg/L
81/221 SYR4 2012–2019
Dibromoacetic Acid
2.6 µg/L
No EPA limit set
worst single sample: 3.2 µg/L
67/248 SYR4 2012–2019
Monochloroacetic Acid
31.42 µg/L
No EPA limit set
worst single sample: 40.3 µg/L
27/248 SYR4 2012–2019
Nitrate-Nitrite
957.5 µg/L 9.6%
of the EPA limit 10000 µg/L
worst single sample: 1120 µg/L
26/41 SYR4 2012–2019
Fluoride
1534 µg/L 38%
of the EPA limit 4000 µg/L
worst single sample: 2830 µg/L
25/25 SYR4 2012–2018
Lithium
19.7 µg/L
No EPA limit set
23/32 UCMR-5 2025
Barium
227.85 µg/L 11%
of the EPA limit 2000 µg/L
worst single sample: 237 µg/L
22/22 SYR4 2012–2018
Bromoform
7.995 µg/L
No EPA limit set
worst single sample: 9.1 µg/L
18/305 SYR4 2012–2019
Lead
0.0016 mg/L 11%
of the EPA limit 0.0150 mg/L
14/14 LCR 2025
Xylenes, Total
4.9 µg/L 0%
of the EPA limit 10000 µg/L
worst single sample: 7.3 µg/L
13/57 SYR4 2012–2019
Arsenic
4.3 µg/L 43%
of the EPA limit 10 µg/L
worst single sample: 4.8 µg/L
11/22 SYR4 2012–2018
Combined Radium (-226 And -228)
3.275 pCi/L 66%
of the EPA limit 5 pCi/L
worst single sample: 3.4 pCi/L
6/7 SYR4 2014–2017
Nitrite
67.5 µg/L 6.8%
of the EPA limit 1000 µg/L
worst single sample: 80 µg/L
6/44 SYR4 2012–2019
Cyanide
20 µg/L 10%
of the EPA limit 200 µg/L
4/21 SYR4 2014–2017
Gross Alpha, Excl. Radon And U
4.84 pCi/L 32%
of the EPA limit 15 pCi/L
worst single sample: 5 pCi/L
3/11 SYR4 2014–2018
Ethylbenzene
0.5000 µg/L 0.1%
of the EPA limit 700 µg/L
2/57 SYR4 2012–2019
Asbestos
0.1952 MFL 2.8%
of the EPA limit 7 MFL
1/1 SYR4 2012
Gross Beta Particle Activity
4.2 pCi/L
No EPA limit set
1/12 SYR4 2012–2018
Selenium
3.2 µg/L 6.4%
of the EPA limit 50 µg/L
1/22 SYR4 2012–2018
75 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumCombined UraniumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebEthylene DibromideEndrinHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidNetfosaaNfdhaNmefosaaOxamylPfdaPfdoaPfeesaPfhpaPfhpsPfmbaPfmpaPFNAPFOAPfpesPftaPftrdaPfunaPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneThallium, TotalTolueneToxapheneTrichloroethyleneVinyl Chloridecis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
WILTZ, QUENTIN
Phone
281-652-1600

Frequently asked questions about City of Pearland

Is City of Pearland tap water safe to drink?

EPA monitoring detected 34 contaminants in City of Pearland's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in City of Pearland's water?

EPA monitoring detected Copper, Chloroform, Total Haloacetic Acids (HAA5), Bromodichloromethane, TTHM, and others. The full list with the level and data source for each is above.

How many people does City of Pearland serve?

City of Pearland reports serving 125,828 people in Texas, per its EPA record.

Has City of Pearland had any water quality violations?

The EPA has 61 violations on file for City of Pearland, of which 13 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.