← Texas

Tap water quality report

City of Temple

EPA monitoring tested this supplier for 108 contaminants and detected 31. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

108
contaminants tested
31
detected
94,935
people served
109
health-based violations
Water source
Surface water
Ownership
Local government
Counties served
Bell

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

109
health-based violations
138
violations on file
1
still open
ViolationTypeStatusPeriod
TT Health-based Resolved 2019-11-01 → 2019-11-30
TT Health-based Resolved 2019-11-01 → 2019-11-30
TT Health-based Resolved 2019-11-01 → 2019-11-30
TT Health-based Resolved 2019-11-01 → 2019-11-30
TT Health-based Resolved 2019-10-01 → 2019-10-31
TT Health-based Resolved 2019-10-01 → 2019-10-31
TT Health-based Resolved 2019-10-01 → 2019-10-31
TT Health-based Resolved 2019-10-01 → 2019-10-31
TT Health-based Resolved 2019-09-01 → 2019-09-30
TT Health-based Resolved 2019-09-01 → 2019-09-30

PFAS detected

PFAS are industrial “forever chemicals”. These are the EPA's latest nationwide test results (2023–2025).
ContaminantMaxDetection ratePeriod
PFHXS 0.0047 µg/L 4/4 2024
PFBS 0.0042 µg/L 3/4 2024
Pfba 0.0078 µg/L 2/4 2024
Pfhxa 0.0073 µg/L 2/4 2024
Pfpea 0.0065 µg/L 2/4 2024
PFOS 0.0049 µg/L 1/4 2024

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Bromodichloromethane
43.29 µg/L
No EPA limit set
worst single sample: 52 µg/L
242/242 SYR4 2012–2019
Chloroform
65.275 µg/L
No EPA limit set
worst single sample: 97.8 µg/L
242/242 SYR4 2012–2019
Dibromochloromethane
24.99 µg/L
No EPA limit set
worst single sample: 29.2 µg/L
242/242 SYR4 2012–2019
Dibromoacetic Acid
10.76 µg/L
No EPA limit set
worst single sample: 12.6 µg/L
235/235 SYR4 2012–2019
Dichloroacetic Acid
38.76 µg/L
No EPA limit set
worst single sample: 74.2 µg/L
235/235 SYR4 2012–2019
TTHM
134.3 µg/L 168%
of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 160 µg/L
235/236 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
70.38 µg/L 117%
of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 99.2 µg/L
235/235 SYR4 2012–2019
Trichloroacetic Acid
20.19 µg/L
No EPA limit set
worst single sample: 40.1 µg/L
232/235 SYR4 2012–2019
Bromoform
8.8 µg/L
No EPA limit set
worst single sample: 9.9 µg/L
227/242 SYR4 2012–2019
Chlorite
617.5 µg/L 62%
of the EPA limit 1000 µg/L
worst single sample: 840 µg/L
226/228 SYR4 2013–2019
Copper
348.5 µg/L 27%
of the EPA limit 1300 µg/L
worst single sample: 560 µg/L
124/125 SYR4 2012–2019
Lead
4.49 µg/L 30%
of the EPA limit 15 µg/L
worst single sample: 25 µg/L
78/125 SYR4 2012–2019
Monobromoacetic Acid
4 µg/L
No EPA limit set
worst single sample: 6 µg/L
56/235 SYR4 2012–2019
Monochloroacetic Acid
17.06 µg/L
No EPA limit set
worst single sample: 17.6 µg/L
53/235 SYR4 2012–2019
Nitrate
1150 µg/L 12%
of the EPA limit 10000 µg/L
20/20 SYR4 2012–2019
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
15/15 LCR 2025
Atrazine
0.3230 µg/L 11%
of the EPA limit 3 µg/L
worst single sample: 0.3300 µg/L
8/11 SYR4 2012–2019
Fluoride
226.5 µg/L 5.7%
of the EPA limit 4000 µg/L
worst single sample: 230 µg/L
8/8 SYR4 2012–2019
Barium
65.41 µg/L 3.3%
of the EPA limit 2000 µg/L
worst single sample: 65.5 µg/L
7/7 SYR4 2013–2019
Cyanide
110 µg/L 55%
of the EPA limit 200 µg/L
3/6 SYR4 2014–2019
Dalapon
1.29 µg/L 0.6%
of the EPA limit 200 µg/L
worst single sample: 1.3 µg/L
3/206 SYR4 2012–2019
Antimony, Total
0.4830 µg/L 8.1%
of the EPA limit 6 µg/L
1/7 SYR4 2013–2019
Arsenic
2.4 µg/L 24%
of the EPA limit 10 µg/L
1/7 SYR4 2013–2019
Di(2-ethylhexyl) Phthalate
7.7 µg/L 128%
of the EPA limit, at the 95th percentile of samples — 6 µg/L
1/11 SYR4 2012–2019
Gross Beta Particle Activity
4.5 pCi/L
No EPA limit set
1/1 SYR4 2017
77 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAsbestosBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumCombined UraniumDichloromethaneDi(2-ethylhexyl) AdipateDinosebEthylene DibromideEndrinEthylbenzeneGross Alpha, Excl. Radon And UHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorNetfosaaNfdhaNmefosaaNitriteOxamylPfdaPfdoaPfeesaPfhpaPfhpsPfmbaPfmpaPFNAPFOAPfpesPftaPftrdaPfunaPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneLithiumO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
DAVIS, TIM
Phone
254-298-5700
Email
[email protected]

Frequently asked questions about City of Temple

Is City of Temple tap water safe to drink?

EPA monitoring detected 31 contaminants in City of Temple's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in City of Temple's water?

EPA monitoring detected Bromodichloromethane, Chloroform, Dibromochloromethane, Dibromoacetic Acid, Dichloroacetic Acid, and others. The full list with the level and data source for each is above.

How many people does City of Temple serve?

City of Temple reports serving 94,935 people in Texas, per its EPA record.

Has City of Temple had any water quality violations?

The EPA has 138 violations on file for City of Temple, of which 109 are health-based (a contaminant limit or required treatment was breached) and 1 remain open. The rest are monitoring or reporting failures.

Where does this data come from?