Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2017-07-01 → 2017-09-30 |
| MCL | Health-based | Resolved | 2017-07-01 → 2017-09-30 |
| MCL | Health-based | Resolved | 2017-07-01 → 2017-09-30 |
| MCL | Health-based | Resolved | 2017-07-01 → 2017-09-30 |
| MCL | Health-based | Resolved | 2017-04-01 → 2017-06-30 |
| MCL | Health-based | Resolved | 2017-04-01 → 2017-06-30 |
| MCL | Health-based | Resolved | 2017-04-01 → 2017-06-30 |
| MCL | Health-based | Resolved | 2017-04-01 → 2017-06-30 |
| MCL | Health-based | Resolved | 2016-01-01 → 2016-03-31 |
| MCL | Health-based | Resolved | 2016-01-01 → 2016-03-31 |
PFAS detected
| Contaminant | Max | Detection rate | Period |
|---|---|---|---|
| Pfpea | 0.0332 µg/L | 1/6 | 2023 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Dibromochloromethane | 39.255 µg/L No EPA limit set
worst single sample: 51.8 µg/L | 70/70 | SYR4 | 2012–2019 |
| Bromodichloromethane | 13.795 µg/L No EPA limit set
worst single sample: 16.5 µg/L | 68/70 | SYR4 | 2012–2019 |
| Copper | 478 µg/L 37% of the EPA limit 1300 µg/L
worst single sample: 940 µg/L | 63/67 | SYR4 | 2014–2019 |
| Chloroform | 18.275 µg/L No EPA limit set
worst single sample: 23.3 µg/L | 62/70 | SYR4 | 2012–2019 |
| Bromoform | 64.77 µg/L No EPA limit set
worst single sample: 71.6 µg/L | 54/70 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 11.99 µg/L No EPA limit set
worst single sample: 15.6 µg/L | 52/52 | SYR4 | 2012–2019 |
| TTHM | 114 µg/L 143% of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 145 µg/L | 52/52 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 15.3 µg/L 26% of the EPA limit 60 µg/L
worst single sample: 21.8 µg/L | 52/52 | SYR4 | 2012–2019 |
| Nitrate | 190 µg/L 1.9% of the EPA limit 10000 µg/L
worst single sample: 210 µg/L | 46/48 | SYR4 | 2012–2019 |
| Lead | 9.575 µg/L 64% of the EPA limit 15 µg/L
worst single sample: 17 µg/L | 36/67 | SYR4 | 2014–2019 |
| Dichloroacetic Acid | 6.4 µg/L No EPA limit set
worst single sample: 6.7 µg/L | 33/52 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 5.7 µg/L No EPA limit set
worst single sample: 6 µg/L | 21/52 | SYR4 | 2012–2019 |
| Lead | 0.0014 mg/L 9.4% of the EPA limit 0.0150 mg/L | 13/13 | LCR | 2025 |
| Nitrate-Nitrite | 200 µg/L 2% of the EPA limit 10000 µg/L
worst single sample: 210 µg/L | 11/12 | SYR4 | 2012–2019 |
| Barium | 83.63 µg/L 4.2% of the EPA limit 2000 µg/L
worst single sample: 87.9 µg/L | 8/8 | SYR4 | 2016–2019 |
| Fluoride | 2050 µg/L 51% of the EPA limit 4000 µg/L
worst single sample: 2060 µg/L | 6/6 | SYR4 | 2014–2017 |
| Lithium | 81.9 µg/L No EPA limit set | 6/6 | UCMR-5 | 2023 |
| Monobromoacetic Acid | 1.34 µg/L No EPA limit set
worst single sample: 1.4 µg/L | 5/52 | SYR4 | 2012–2019 |
| Combined Radium (-226 And -228) | 1.5 pCi/L 30% of the EPA limit 5 pCi/L | 3/3 | SYR4 | 2015 |
| Di(2-ethylhexyl) Phthalate | 1.557 µg/L 26% of the EPA limit 6 µg/L
worst single sample: 1.6 µg/L | 2/11 | SYR4 | 2015–2019 |
| Gross Beta Particle Activity | 6 pCi/L No EPA limit set | 1/3 | SYR4 | 2015 |
| Monochloroacetic Acid | 5.3 µg/L No EPA limit set | 1/52 | SYR4 | 2012–2019 |
86 contaminants tested, none detected
Utility contact
Frequently asked questions about Bastrop County Wcid 2
Is Bastrop County Wcid 2 tap water safe to drink?
EPA monitoring detected 23 contaminants in Bastrop County Wcid 2's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Bastrop County Wcid 2's water?
EPA monitoring detected Dibromochloromethane, Bromodichloromethane, Copper, Chloroform, Bromoform, and others. The full list with the level and data source for each is above.
How many people does Bastrop County Wcid 2 serve?
Bastrop County Wcid 2 reports serving 7,269 people in Texas, per its EPA record.
Has Bastrop County Wcid 2 had any water quality violations?
The EPA has 67 violations on file for Bastrop County Wcid 2, of which 43 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.