← Texas

Tap water quality report

City of Bastrop

EPA monitoring tested this supplier for 109 contaminants and detected 30. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

109
contaminants tested
30
detected
13,209
people served
113
health-based violations
Water source
Ground water under surface influence
Ownership
Local government
Counties served
Bastrop

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

113
health-based violations
139
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2025-01-01 → 2025-03-31
MCL Health-based Resolved 2025-01-01 → 2025-03-31
MCL Health-based Resolved 2025-01-01 → 2025-03-31
MCL Health-based Resolved 2025-01-01 → 2025-03-31
MCL Health-based Resolved 2025-01-01 → 2025-03-31
MCL Health-based Resolved 2024-07-01 → 2024-09-30
MCL Health-based Resolved 2024-07-01 → 2024-09-30
MCL Health-based Resolved 2024-07-01 → 2024-09-30
MCL Health-based Resolved 2024-07-01 → 2024-09-30
MCL Health-based Resolved 2024-04-01 → 2024-06-30

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
1700 µg/L 131%
of the EPA limit, at the 95th percentile of samples — 1300 µg/L
worst single sample: 3400 µg/L
431/441 SYR4 2012–2019
Bromodichloromethane
21.13 µg/L
No EPA limit set
worst single sample: 37.4 µg/L
115/115 SYR4 2012–2019
Bromoform
27.43 µg/L
No EPA limit set
worst single sample: 37.2 µg/L
115/115 SYR4 2012–2019
Dibromochloromethane
47.01 µg/L
No EPA limit set
worst single sample: 58.5 µg/L
115/115 SYR4 2012–2019
Lead
7.7 µg/L 51%
of the EPA limit 15 µg/L
worst single sample: 25.9 µg/L
101/441 SYR4 2012–2019
TTHM
108.7 µg/L 136%
of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 136 µg/L
94/96 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
21.61 µg/L 36%
of the EPA limit 60 µg/L
worst single sample: 35.4 µg/L
94/94 SYR4 2012–2019
Dibromoacetic Acid
15.28 µg/L
No EPA limit set
worst single sample: 20.4 µg/L
93/94 SYR4 2012–2019
Chloroform
8.18 µg/L
No EPA limit set
worst single sample: 14 µg/L
69/115 SYR4 2012–2019
Dichloroacetic Acid
6.43 µg/L
No EPA limit set
worst single sample: 8.7 µg/L
55/94 SYR4 2012–2019
Nitrate
4460 µg/L 45%
of the EPA limit 10000 µg/L
worst single sample: 4990 µg/L
52/52 SYR4 2012–2019
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
27/27 LCR 2025
Trichloroacetic Acid
2.455 µg/L
No EPA limit set
worst single sample: 4.1 µg/L
24/94 SYR4 2012–2019
Fluoride
926 µg/L 23%
of the EPA limit 4000 µg/L
worst single sample: 1040 µg/L
22/22 SYR4 2012–2019
Barium
393 µg/L 20%
of the EPA limit 2000 µg/L
worst single sample: 395 µg/L
21/21 SYR4 2013–2019
Selenium
14.82 µg/L 30%
of the EPA limit 50 µg/L
worst single sample: 16.9 µg/L
17/21 SYR4 2013–2019
Arsenic
4.705 µg/L 47%
of the EPA limit 10 µg/L
worst single sample: 4.9 µg/L
14/21 SYR4 2013–2019
Monobromoacetic Acid
2.745 µg/L
No EPA limit set
worst single sample: 2.8 µg/L
12/94 SYR4 2012–2019
Combined Uranium
1.98 µg/L 6.6%
of the EPA limit 30 µg/L
worst single sample: 2 µg/L
5/5 SYR4 2013–2019
Gross Beta Particle Activity
6.555 pCi/L
No EPA limit set
worst single sample: 6.6 pCi/L
4/5 SYR4 2013–2019
Nitrate-Nitrite
4876 µg/L 49%
of the EPA limit 10000 µg/L
worst single sample: 4990 µg/L
4/4 SYR4 2012–2013
Atrazine
0.1490 µg/L 5%
of the EPA limit 3 µg/L
worst single sample: 0.1500 µg/L
3/26 SYR4 2012–2019
Combined Radium (-226 And -228)
2.04 pCi/L 41%
of the EPA limit 5 pCi/L
worst single sample: 2.1 pCi/L
3/3 SYR4 2016
Gross Alpha, Excl. Radon And U
2 pCi/L 13%
of the EPA limit 15 pCi/L
2/5 SYR4 2013–2019
Monochloroacetic Acid
3.05 µg/L
No EPA limit set
worst single sample: 3.1 µg/L
2/94 SYR4 2012–2019
Asbestos
0.3766 MFL 5.4%
of the EPA limit 7 MFL
1/1 SYR4 2012
Cyanide
20 µg/L 10%
of the EPA limit 200 µg/L
1/18 SYR4 2014–2019
Chromium
0.5140 µg/L 0.5%
of the EPA limit 100 µg/L
1/21 SYR4 2013–2019
Di(2-ethylhexyl) Phthalate
2.4 µg/L 40%
of the EPA limit 6 µg/L
1/26 SYR4 2012–2019
Lithium
26 µg/L
No EPA limit set
1/1 UCMR-5 2025
79 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCadmiumCarbofuranCarbon TetrachlorideChlordaneDichloromethaneDalaponDi(2-ethylhexyl) AdipateDinosebEthylene DibromideEndrinEthylbenzeneHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorNetfosaaNfdhaNmefosaaNitriteOxamylPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneThallium, TotalTolueneToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
HARRIS, ISHMAEL
Phone
512-332-8800
Email
[email protected]

Frequently asked questions about City of Bastrop

Is City of Bastrop tap water safe to drink?

EPA monitoring detected 30 contaminants in City of Bastrop's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in City of Bastrop's water?

EPA monitoring detected Copper, Bromodichloromethane, Bromoform, Dibromochloromethane, Lead, and others. The full list with the level and data source for each is above.

How many people does City of Bastrop serve?

City of Bastrop reports serving 13,209 people in Texas, per its EPA record.

Has City of Bastrop had any water quality violations?

The EPA has 139 violations on file for City of Bastrop, of which 113 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.