Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Unaddressed | 2026-05-23 |
| TT | Health-based | Unaddressed | 2026-05-23 |
| TT | Health-based | Unaddressed | 2026-04-24 |
| TT | Health-based | Unaddressed | 2026-04-24 |
| TT | Health-based | Unaddressed | 2026-01-10 |
| TT | Health-based | Unaddressed | 2026-01-10 |
| TT | Health-based | Unaddressed | 2026-01-10 |
| TT | Health-based | Unaddressed | 2025-10-01 |
| TT | Health-based | Unaddressed | 2025-10-01 |
| TT | Health-based | Unaddressed | 2025-10-01 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Dibromochloromethane | 88.025 µg/L No EPA limit set
worst single sample: 175.5 µg/L | 96/119 | SYR4 | 2012–2019 |
| Bromodichloromethane | 140.51 µg/L No EPA limit set
worst single sample: 228.8 µg/L | 95/119 | SYR4 | 2012–2019 |
| Chloroform | 137.4 µg/L No EPA limit set
worst single sample: 211.8 µg/L | 95/119 | SYR4 | 2012–2019 |
| Bromoform | 14.325 µg/L No EPA limit set
worst single sample: 17.4 µg/L | 76/119 | SYR4 | 2012–2019 |
| TTHM | 246.16 µg/L 308% of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 307 µg/L | 53/61 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 70.59 µg/L 118% of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 102.6 µg/L | 48/55 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 26.72 µg/L No EPA limit set
worst single sample: 38 µg/L | 45/55 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 35.535 µg/L No EPA limit set
worst single sample: 48 µg/L | 42/55 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 14.36 µg/L No EPA limit set
worst single sample: 16 µg/L | 37/55 | SYR4 | 2012–2019 |
| Nitrate | 1412.5 µg/L 14% of the EPA limit 10000 µg/L
worst single sample: 1510 µg/L | 34/34 | SYR4 | 2012–2019 |
| Copper | 317.25 µg/L 24% of the EPA limit 1300 µg/L
worst single sample: 920 µg/L | 26/27 | SYR4 | 2012–2017 |
| Monochloroacetic Acid | 6.31 µg/L No EPA limit set
worst single sample: 6.4 µg/L | 19/55 | SYR4 | 2012–2019 |
| Lead | 5.136 µg/L 34% of the EPA limit 15 µg/L
worst single sample: 7.68 µg/L | 17/27 | SYR4 | 2012–2017 |
| Lead | 0.0027 mg/L 18% of the EPA limit 0.0150 mg/L | 13/13 | LCR | 2025 |
| Barium | 79.1 µg/L 4% of the EPA limit 2000 µg/L
worst single sample: 80 µg/L | 10/10 | SYR4 | 2012–2019 |
| Monobromoacetic Acid | 2.655 µg/L No EPA limit set
worst single sample: 2.7 µg/L | 10/55 | SYR4 | 2012–2019 |
| Fluoride | 1167 µg/L 29% of the EPA limit 4000 µg/L
worst single sample: 1230 µg/L | 7/11 | SYR4 | 2012–2019 |
| Chromium | 3.3475 µg/L 3.3% of the EPA limit 100 µg/L
worst single sample: 3.8 µg/L | 6/10 | SYR4 | 2012–2019 |
| Xylenes, Total | 1.928 µg/L 0% of the EPA limit 10000 µg/L
worst single sample: 2.23 µg/L | 5/64 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 940.475 µg/L 9.4% of the EPA limit 10000 µg/L
worst single sample: 1100 µg/L | 4/4 | SYR4 | 2013–2019 |
| Combined Radium (-226 And -228) | 1.475 pCi/L 30% of the EPA limit 5 pCi/L
worst single sample: 1.5 pCi/L | 2/2 | SYR4 | 2012–2018 |
| Beryllium, Total | 0.1200 µg/L 3% of the EPA limit 4 µg/L | 1/10 | SYR4 | 2012–2019 |
| Dalapon | 3.94 µg/L 2% of the EPA limit 200 µg/L | 1/12 | SYR4 | 2012–2019 |
| Ethylbenzene | 1.1 µg/L 0.2% of the EPA limit 700 µg/L | 1/64 | SYR4 | 2012–2019 |
| Gross Beta Particle Activity | 5 pCi/L No EPA limit set | 1/3 | SYR4 | 2012–2018 |
| Selenium | 1.18 µg/L 2.4% of the EPA limit 50 µg/L | 1/10 | SYR4 | 2012–2019 |
| Thallium, Total | 0.3240 µg/L 16% of the EPA limit 2 µg/L | 1/10 | SYR4 | 2012–2019 |
| Toluene | 0.5500 µg/L 0.1% of the EPA limit 1000 µg/L | 1/64 | SYR4 | 2012–2019 |
51 contaminants tested, none detected
Utility contact
Frequently asked questions about City of Zavalla
Is City of Zavalla tap water safe to drink?
EPA monitoring detected 28 contaminants in City of Zavalla's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in City of Zavalla's water?
EPA monitoring detected Dibromochloromethane, Bromodichloromethane, Chloroform, Bromoform, TTHM, and others. The full list with the level and data source for each is above.
How many people does City of Zavalla serve?
City of Zavalla reports serving 880 people in Texas, per its EPA record.
Has City of Zavalla had any water quality violations?
The EPA has 489 violations on file for City of Zavalla, of which 272 are health-based (a contaminant limit or required treatment was breached) and 28 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.