Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2024-01-01 → 2024-03-31 |
| MCL | Health-based | Resolved | 2024-01-01 → 2024-03-31 |
| MCL | Health-based | Resolved | 2024-01-01 → 2024-03-31 |
| MCL | Health-based | Resolved | 2024-01-01 → 2024-03-31 |
| MCL | Health-based | Resolved | 2023-10-01 → 2023-12-31 |
| MCL | Health-based | Resolved | 2023-10-01 → 2023-12-31 |
| MCL | Health-based | Resolved | 2023-10-01 → 2023-12-31 |
| MCL | Health-based | Resolved | 2023-10-01 → 2023-12-31 |
| MCL | Health-based | Resolved | 2023-07-01 → 2023-09-30 |
| MCL | Health-based | Resolved | 2023-07-01 → 2023-09-30 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Bromodichloromethane | 132.525 µg/L No EPA limit set
worst single sample: 163 µg/L | 36/37 | SYR4 | 2012–2019 |
| Bromoform | 66.95 µg/L No EPA limit set
worst single sample: 72.3 µg/L | 36/37 | SYR4 | 2012–2019 |
| Chloroform | 90.25 µg/L No EPA limit set
worst single sample: 107 µg/L | 36/37 | SYR4 | 2012–2019 |
| Dibromochloromethane | 159.25 µg/L No EPA limit set
worst single sample: 181 µg/L | 36/37 | SYR4 | 2012–2019 |
| Copper | 520 µg/L 40% of the EPA limit 1300 µg/L
worst single sample: 1190 µg/L | 33/37 | SYR4 | 2014–2018 |
| TTHM | 438 µg/L 548% of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 494 µg/L | 31/32 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 32.2 µg/L No EPA limit set
worst single sample: 33.4 µg/L | 30/32 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 90.605 µg/L 151% of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 110 µg/L | 30/32 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 29.06 µg/L No EPA limit set
worst single sample: 46.8 µg/L | 30/32 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 30.96 µg/L No EPA limit set
worst single sample: 39.5 µg/L | 29/32 | SYR4 | 2012–2019 |
| Lead | 6.4845 µg/L 43% of the EPA limit 15 µg/L
worst single sample: 7.09 µg/L | 24/37 | SYR4 | 2014–2018 |
| Monobromoacetic Acid | 10.52 µg/L No EPA limit set
worst single sample: 40 µg/L | 22/32 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 5.975 µg/L No EPA limit set
worst single sample: 6.3 µg/L | 14/32 | SYR4 | 2012–2019 |
| Nitrate | 122 µg/L 1.2% of the EPA limit 10000 µg/L | 12/16 | SYR4 | 2012–2019 |
| Fluoride | 985.2 µg/L 25% of the EPA limit 4000 µg/L
worst single sample: 998 µg/L | 3/3 | SYR4 | 2013–2019 |
| Barium | 60.565 µg/L 3% of the EPA limit 2000 µg/L
worst single sample: 60.7 µg/L | 2/2 | SYR4 | 2014–2017 |
| Cyanide | 47.4 µg/L 24% of the EPA limit 200 µg/L | 1/2 | SYR4 | 2014–2017 |
| Gross Beta Particle Activity | 8.8 pCi/L No EPA limit set | 1/1 | SYR4 | 2017 |
| Lead | 0.0088 mg/L 59% of the EPA limit 0.0150 mg/L | 1/1 | LCR | 2024 |
| Nitrate-Nitrite | 62.5 µg/L 0.6% of the EPA limit 10000 µg/L | 1/3 | SYR4 | 2012–2015 |
58 contaminants tested, none detected
Utility contact
Frequently asked questions about Walnut Ridge Estates Water
Is Walnut Ridge Estates Water tap water safe to drink?
EPA monitoring detected 20 contaminants in Walnut Ridge Estates Water's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Walnut Ridge Estates Water's water?
EPA monitoring detected Bromodichloromethane, Bromoform, Chloroform, Dibromochloromethane, Copper, and others. The full list with the level and data source for each is above.
How many people does Walnut Ridge Estates Water serve?
Walnut Ridge Estates Water reports serving 84 people in Texas, per its EPA record.
Has Walnut Ridge Estates Water had any water quality violations?
The EPA has 615 violations on file for Walnut Ridge Estates Water, of which 365 are health-based (a contaminant limit or required treatment was breached) and 1 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.