Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MR | Monitoring | Resolved | 2002-10-01 |
| MR | Monitoring | Resolved | 2002-10-01 |
| MR | Monitoring | Resolved | 2002-10-01 |
| MR | Monitoring | Resolved | 2001-01-01 → 2001-12-31 |
| MR | Monitoring | Resolved | 2001-01-01 → 2001-12-31 |
| MR | Monitoring | Resolved | 2001-01-01 → 2001-12-31 |
| MR | Monitoring | Resolved | 2001-01-01 → 2001-12-31 |
| MR | Monitoring | Resolved | 2001-01-01 → 2001-12-31 |
| MR | Monitoring | Resolved | 2001-01-01 → 2001-12-31 |
| MR | Monitoring | Resolved | 2001-01-01 → 2001-12-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 1780 µg/L 137% of the EPA limit, at the 95th percentile of samples — 1300 µg/L
worst single sample: 2340 µg/L | 59/60 | SYR4 | 2012–2019 |
| Lead | 11.15 µg/L 74% of the EPA limit 15 µg/L
worst single sample: 14 µg/L | 38/60 | SYR4 | 2012–2019 |
| Nitrate | 2245 µg/L 22% of the EPA limit 10000 µg/L
worst single sample: 2300 µg/L | 32/32 | SYR4 | 2012–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 22/22 | LCR | 2025 |
| Chloroform | 11.13 µg/L No EPA limit set
worst single sample: 11.4 µg/L | 3/8 | SYR4 | 2012–2019 |
| Combined Radium (-226 And -228) | 1.307 pCi/L 26% of the EPA limit 5 pCi/L
worst single sample: 1.31 pCi/L | 3/4 | SYR4 | 2013–2019 |
| TTHM | 15.23 µg/L 19% of the EPA limit 80 µg/L
worst single sample: 15.8 µg/L | 3/8 | SYR4 | 2012–2019 |
| Bromodichloromethane | 2.825 µg/L No EPA limit set
worst single sample: 2.9 µg/L | 2/8 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 1.89 µg/L No EPA limit set
worst single sample: 1.9 µg/L | 2/8 | SYR4 | 2012–2019 |
| Gross Alpha, Excl. Radon And U | 12.8485 pCi/L 86% of the EPA limit 15 pCi/L
worst single sample: 13.4 pCi/L | 2/2 | SYR4 | 2013 |
| Gross Beta Particle Activity | 5.1625 pCi/L No EPA limit set
worst single sample: 5.24 pCi/L | 2/2 | SYR4 | 2019 |
| Nitrate-Nitrite | 2065 µg/L 21% of the EPA limit 10000 µg/L
worst single sample: 2100 µg/L | 2/2 | SYR4 | 2014 |
| Total Haloacetic Acids (HAA5) | 3.19 µg/L 5.3% of the EPA limit 60 µg/L
worst single sample: 3.2 µg/L | 2/8 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 1.3 µg/L No EPA limit set | 2/8 | SYR4 | 2012–2019 |
| Dibromochloromethane | 1.5 µg/L No EPA limit set | 1/8 | SYR4 | 2012–2019 |
| Fluoride | 110 µg/L 2.8% of the EPA limit 4000 µg/L | 1/4 | SYR4 | 2014–2017 |
63 contaminants tested, none detected
Utility contact
Frequently asked questions about Bgwc Carowood (sc4650035)
Is Bgwc Carowood (sc4650035) tap water safe to drink?
EPA monitoring detected 16 contaminants in Bgwc Carowood (sc4650035)'s water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Bgwc Carowood (sc4650035)'s water?
EPA monitoring detected Copper, Lead, Nitrate, Lead, Chloroform, and others. The full list with the level and data source for each is above.
How many people does Bgwc Carowood (sc4650035) serve?
Bgwc Carowood (sc4650035) reports serving 212 people in South Carolina, per its EPA record.
Has Bgwc Carowood (sc4650035) had any water quality violations?
The EPA has 180 violations on file for Bgwc Carowood (sc4650035), of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.