Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Resolved | 2024-10-17 |
| TT | Health-based | Resolved | 2024-10-17 |
| MCL | Health-based | Resolved | 2011-04-01 → 2011-06-30 |
| MCL | Health-based | Resolved | 2011-04-01 → 2011-06-30 |
| MCL | Health-based | Resolved | 2011-04-01 → 2011-06-30 |
| MCL | Health-based | Resolved | 2011-04-01 → 2011-06-30 |
| MCL | Health-based | Resolved | 2009-10-01 → 2009-12-31 |
| MCL | Health-based | Resolved | 2009-10-01 → 2009-12-31 |
| MCL | Health-based | Resolved | 2009-10-01 → 2009-12-31 |
| MCL | Health-based | Resolved | 2009-10-01 → 2009-12-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 279 µg/L 21% of the EPA limit 1300 µg/L
worst single sample: 646 µg/L | 39/44 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 8018 µg/L 80% of the EPA limit 10000 µg/L
worst single sample: 8740 µg/L | 20/20 | SYR4 | 2012–2019 |
| Lead | 0.0194 mg/L 129% above the EPA limit of 0.0150 mg/L | 16/16 | LCR | 2025 |
| Dibromochloromethane | 3.816 µg/L No EPA limit set
worst single sample: 3.98 µg/L | 9/18 | SYR4 | 2013–2019 |
| Gross Beta Particle Activity | 3.588 pCi/L No EPA limit set
worst single sample: 3.68 pCi/L | 9/9 | SYR4 | 2016–2018 |
| Combined Radium (-226 And -228) | 0.8263 pCi/L 17% of the EPA limit 5 pCi/L
worst single sample: 0.8350 pCi/L | 8/8 | SYR4 | 2016–2018 |
| Combined Uranium | 1.762 µg/L 5.9% of the EPA limit 30 µg/L
worst single sample: 1.79 µg/L | 8/9 | SYR4 | 2016–2018 |
| Gross Alpha, Excl. Radon And U | 2.551 pCi/L 17% of the EPA limit 15 pCi/L
worst single sample: 2.74 pCi/L | 8/9 | SYR4 | 2016–2018 |
| Bromodichloromethane | 3.131 µg/L No EPA limit set
worst single sample: 3.26 µg/L | 7/18 | SYR4 | 2013–2019 |
| Bromoform | 5.454 µg/L No EPA limit set
worst single sample: 5.76 µg/L | 7/18 | SYR4 | 2013–2019 |
| Nitrate | 6060 µg/L 61% of the EPA limit 10000 µg/L | 6/6 | SYR4 | 2012–2013 |
| Lead | 18.36 µg/L 122% of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 20.7 µg/L | 5/44 | SYR4 | 2012–2019 |
| TTHM | 10.46 µg/L 13% of the EPA limit 80 µg/L
worst single sample: 10.5 µg/L | 5/8 | SYR4 | 2014–2019 |
| Dibromoacetic Acid | 1.9685 µg/L No EPA limit set
worst single sample: 2 µg/L | 4/8 | SYR4 | 2014–2019 |
| Total Haloacetic Acids (HAA5) | 2.765 µg/L 4.6% of the EPA limit 60 µg/L
worst single sample: 2.9 µg/L | 4/8 | SYR4 | 2014–2019 |
| Chloroform | 2.269 µg/L No EPA limit set
worst single sample: 2.3 µg/L | 3/18 | SYR4 | 2013–2019 |
| Barium | 256.95 µg/L 13% of the EPA limit 2000 µg/L
worst single sample: 261 µg/L | 2/2 | SYR4 | 2016–2017 |
| Fluoride | 297 µg/L 7.4% of the EPA limit 4000 µg/L
worst single sample: 300 µg/L | 2/2 | SYR4 | 2016–2017 |
| Dichloroacetic Acid | 1.66 µg/L No EPA limit set | 1/8 | SYR4 | 2014–2019 |
50 contaminants tested, none detected
Utility contact
Frequently asked questions about Mooreland
Is Mooreland tap water safe to drink?
EPA monitoring detected 19 contaminants in Mooreland's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Mooreland's water?
EPA monitoring detected Copper, Nitrate-Nitrite, Lead, Dibromochloromethane, Gross Beta Particle Activity, and others. The full list with the level and data source for each is above.
How many people does Mooreland serve?
Mooreland reports serving 1,226 people in Oklahoma, per its EPA record.
Has Mooreland had any water quality violations?
The EPA has 466 violations on file for Mooreland, of which 308 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.