Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2025-01-01 → 2025-12-31 |
| MCL | Health-based | Resolved | 2025-01-01 → 2025-12-31 |
| MCL | Health-based | Resolved | 2025-01-01 → 2025-12-31 |
| MCL | Health-based | Resolved | 2025-01-01 → 2025-12-31 |
| MCL | Health-based | Resolved | 2005-09-01 → 2005-09-30 |
| MCL | Health-based | Resolved | 2005-09-01 → 2005-09-30 |
| MCL | Health-based | Resolved | 2005-09-01 → 2005-09-30 |
| MCL | Health-based | Resolved | 2005-09-01 → 2005-09-30 |
| MCL | Health-based | Resolved | 2005-06-01 → 2005-06-30 |
| MCL | Health-based | Resolved | 2005-06-01 → 2005-06-30 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 164.1 µg/L 13% of the EPA limit 1300 µg/L
worst single sample: 311 µg/L | 179/180 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 6744 µg/L 67% of the EPA limit 10000 µg/L
worst single sample: 8650 µg/L | 47/47 | SYR4 | 2012–2019 |
| Nitrate | 5440 µg/L 54% of the EPA limit 10000 µg/L
worst single sample: 6360 µg/L | 44/44 | SYR4 | 2012–2017 |
| Bromoform | 2.8 µg/L No EPA limit set
worst single sample: 2.9 µg/L | 30/34 | SYR4 | 2012–2019 |
| Dibromochloromethane | 2.4775 µg/L No EPA limit set
worst single sample: 2.5 µg/L | 30/34 | SYR4 | 2012–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 18/18 | LCR | 2025 |
| TTHM | 6.636 µg/L 8.3% of the EPA limit 80 µg/L
worst single sample: 8.3 µg/L | 17/39 | SYR4 | 2012–2019 |
| Arsenic | 5.5675 µg/L 56% of the EPA limit 10 µg/L
worst single sample: 5.6 µg/L | 14/19 | SYR4 | 2012–2019 |
| Combined Uranium | 15.275 µg/L 51% of the EPA limit 30 µg/L
worst single sample: 16.9 µg/L | 14/14 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 1.8095 µg/L No EPA limit set
worst single sample: 1.92 µg/L | 14/27 | SYR4 | 2012–2019 |
| Gross Beta Particle Activity | 12.115 pCi/L No EPA limit set
worst single sample: 14 pCi/L | 14/14 | SYR4 | 2012–2019 |
| Gross Alpha, Excl. Radon And U | 11 pCi/L 73% of the EPA limit 15 pCi/L
worst single sample: 11.3 pCi/L | 13/14 | SYR4 | 2012–2019 |
| Lithium | 154 µg/L No EPA limit set | 12/12 | UCMR-5 | 2023 |
| Barium | 52.6 µg/L 2.6% of the EPA limit 2000 µg/L
worst single sample: 53 µg/L | 9/9 | SYR4 | 2012–2019 |
| Fluoride | 1910 µg/L 48% of the EPA limit 4000 µg/L
worst single sample: 1930 µg/L | 9/9 | SYR4 | 2012–2019 |
| Lead | 4.9 µg/L 33% of the EPA limit 15 µg/L
worst single sample: 6.52 µg/L | 9/180 | SYR4 | 2012–2019 |
| Combined Radium (-226 And -228) | 2.15925 pCi/L 43% of the EPA limit 5 pCi/L
worst single sample: 2.34 pCi/L | 6/14 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 1.8775 µg/L 3.1% of the EPA limit 60 µg/L
worst single sample: 1.92 µg/L | 6/39 | SYR4 | 2012–2019 |
| Bromodichloromethane | 1.1 µg/L No EPA limit set | 4/34 | SYR4 | 2012–2019 |
| Xylenes, Total | 2.01 µg/L 0% of the EPA limit 10000 µg/L
worst single sample: 2.1 µg/L | 4/25 | SYR4 | 2012–2019 |
| Benzene | 0.8500 µg/L 17% of the EPA limit 5 µg/L | 1/25 | SYR4 | 2012–2019 |
| Selenium | 5 µg/L 10% of the EPA limit 50 µg/L | 1/9 | SYR4 | 2012–2019 |
82 contaminants tested, none detected
Utility contact
Frequently asked questions about Guymon
Is Guymon tap water safe to drink?
EPA monitoring detected 22 contaminants in Guymon's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Guymon's water?
EPA monitoring detected Copper, Nitrate-Nitrite, Nitrate, Bromoform, Dibromochloromethane, and others. The full list with the level and data source for each is above.
How many people does Guymon serve?
Guymon reports serving 11,442 people in Oklahoma, per its EPA record.
Has Guymon had any water quality violations?
The EPA has 70 violations on file for Guymon, of which 34 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.