Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Archived | 2025-01-01 → 2025-03-31 |
| MCL | Health-based | Archived | 2025-01-01 → 2025-03-31 |
| MCL | Health-based | Archived | 2025-01-01 → 2025-03-31 |
| MCL | Health-based | Archived | 2025-01-01 → 2025-03-31 |
| TT | Health-based | Addressed | 2024-10-17 |
| TT | Health-based | Addressed | 2024-10-17 |
| MCL | Health-based | Archived | 2024-10-01 → 2024-12-31 |
| MCL | Health-based | Archived | 2024-10-01 → 2024-12-31 |
| MCL | Health-based | Archived | 2024-10-01 → 2024-12-31 |
| MCL | Health-based | Archived | 2024-10-01 → 2024-12-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Combined Uranium | 49.24 µg/L 164% of the EPA limit, at the 95th percentile of samples — 30 µg/L
worst single sample: 51.8 µg/L | 49/49 | SYR4 | 2012–2018 |
| Gross Beta Particle Activity | 17.425 pCi/L No EPA limit set
worst single sample: 20.21 pCi/L | 46/49 | SYR4 | 2012–2018 |
| Gross Alpha, Excl. Radon And U | 15.82 pCi/L 105% of the EPA limit, at the 95th percentile of samples — 15 pCi/L
worst single sample: 34.07 pCi/L | 41/49 | SYR4 | 2012–2018 |
| Nitrate-Nitrite | 782.5 µg/L 7.8% of the EPA limit 10000 µg/L
worst single sample: 790 µg/L | 36/42 | SYR4 | 2012–2018 |
| Combined Radium (-226 And -228) | 4.57 pCi/L 91% of the EPA limit 5 pCi/L
worst single sample: 7.82 pCi/L | 27/49 | SYR4 | 2012–2018 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 9/9 | LCR | 2014 |
| Copper | 33.365 µg/L 2.6% of the EPA limit 1300 µg/L
worst single sample: 37.6 µg/L | 8/10 | SYR4 | 2014–2017 |
| Chloroform | 3.28 µg/L No EPA limit set
worst single sample: 3.3 µg/L | 5/7 | SYR4 | 2012–2017 |
| Bromodichloromethane | 4.7 µg/L No EPA limit set | 4/7 | SYR4 | 2012–2017 |
| Barium | 113.9 µg/L 5.7% of the EPA limit 2000 µg/L
worst single sample: 114 µg/L | 3/3 | SYR4 | 2017 |
| Bromoform | 1.79 µg/L No EPA limit set
worst single sample: 1.8 µg/L | 3/7 | SYR4 | 2012–2017 |
| Dibromochloromethane | 5.8 µg/L No EPA limit set | 3/7 | SYR4 | 2012–2017 |
| Dichloroacetic Acid | 16.68 µg/L No EPA limit set
worst single sample: 17.9 µg/L | 3/4 | SYR4 | 2012–2017 |
| Trichloroacetic Acid | 8.15 µg/L No EPA limit set
worst single sample: 8.3 µg/L | 3/4 | SYR4 | 2012–2017 |
| Arsenic | 4.4 µg/L 44% of the EPA limit 10 µg/L
worst single sample: 4.5 µg/L | 2/3 | SYR4 | 2013 |
| Monochloroacetic Acid | 9.555 µg/L No EPA limit set
worst single sample: 9.7 µg/L | 2/4 | SYR4 | 2012–2017 |
| Total Haloacetic Acids (HAA5) | 34.08 µg/L 57% of the EPA limit 60 µg/L
worst single sample: 34.4 µg/L | 2/4 | SYR4 | 2012–2017 |
| Dibromoacetic Acid | 7.2 µg/L No EPA limit set | 1/4 | SYR4 | 2012–2017 |
34 contaminants tested, none detected
Utility contact
Frequently asked questions about Brooksville
Is Brooksville tap water safe to drink?
EPA monitoring detected 18 contaminants in Brooksville's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Brooksville's water?
EPA monitoring detected Combined Uranium, Gross Beta Particle Activity, Gross Alpha, Excl. Radon And U, Nitrate-Nitrite, Combined Radium (-226 And -228), and others. The full list with the level and data source for each is above.
How many people does Brooksville serve?
Brooksville reports serving 90 people in Oklahoma, per its EPA record.
Has Brooksville had any water quality violations?
The EPA has 3041 violations on file for Brooksville, of which 256 are health-based (a contaminant limit or required treatment was breached) and 20 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.