← Oklahoma

Tap water quality report

Moore Public Works Authority

EPA monitoring tested this supplier for 104 contaminants and detected 30. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

104
contaminants tested
30
detected
55,083
people served
162
health-based violations
Water source
SWP
Ownership
Local government
Counties served
Cleveland

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

162
health-based violations
458
violations on file
0
still open
ViolationTypeStatusPeriod
TT Health-based Resolved 2024-10-17
TT Health-based Resolved 2024-10-17
MCL Health-based Archived 2024-10-01 → 2024-12-31
MCL Health-based Archived 2024-10-01 → 2024-12-31
MCL Health-based Archived 2024-10-01 → 2024-12-31
MCL Health-based Resolved 2023-01-01 → 2023-03-31
MCL Health-based Resolved 2023-01-01 → 2023-03-31
MCL Health-based Resolved 2023-01-01 → 2023-03-31
MCL Health-based Resolved 2023-01-01 → 2023-03-31
MCL Health-based Resolved 2022-10-01 → 2022-12-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Chloroform
54 µg/L
No EPA limit set
worst single sample: 69 µg/L
173/239 SYR4 2012–2019
Bromodichloromethane
14.655 µg/L
No EPA limit set
worst single sample: 16.1 µg/L
170/239 SYR4 2012–2019
Nitrate-Nitrite
816 µg/L 8.2%
of the EPA limit 10000 µg/L
worst single sample: 6210 µg/L
158/185 SYR4 2012–2019
Dibromochloromethane
2.872 µg/L
No EPA limit set
worst single sample: 3.36 µg/L
155/239 SYR4 2012–2019
TTHM
71.465 µg/L 89%
of the EPA limit 80 µg/L
worst single sample: 77.6 µg/L
128/128 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
44.75 µg/L 75%
of the EPA limit 60 µg/L
worst single sample: 53.2 µg/L
127/128 SYR4 2012–2019
Nitrate
734 µg/L 7.3%
of the EPA limit 10000 µg/L
worst single sample: 850 µg/L
114/132 SYR4 2012–2019
Dichloroacetic Acid
25.215 µg/L
No EPA limit set
worst single sample: 29.8 µg/L
100/100 SYR4 2013–2019
Trichloroacetic Acid
20.8 µg/L
No EPA limit set
worst single sample: 23.6 µg/L
100/100 SYR4 2013–2019
Copper
471 µg/L 36%
of the EPA limit 1300 µg/L
worst single sample: 839 µg/L
81/364 SYR4 2014–2019
Gross Beta Particle Activity
5.2844 pCi/L
No EPA limit set
worst single sample: 7.076 pCi/L
77/86 SYR4 2012–2019
Gross Alpha, Excl. Radon And U
10.322 pCi/L 69%
of the EPA limit 15 pCi/L
worst single sample: 18.3 pCi/L
69/86 SYR4 2012–2019
Combined Uranium
17.24 µg/L 57%
of the EPA limit 30 µg/L
worst single sample: 19 µg/L
57/87 SYR4 2012–2019
Barium
382 µg/L 19%
of the EPA limit 2000 µg/L
worst single sample: 398 µg/L
48/48 SYR4 2013–2019
Fluoride
701.5 µg/L 18%
of the EPA limit 4000 µg/L
worst single sample: 750 µg/L
48/48 SYR4 2013–2019
Lithium
24.8 µg/L
No EPA limit set
40/48 UCMR-5 2024
Combined Radium (-226 And -228)
1.774 pCi/L 35%
of the EPA limit 5 pCi/L
worst single sample: 2.6 pCi/L
29/87 SYR4 2012–2019
Chromium
60.45 µg/L 60%
of the EPA limit 100 µg/L
worst single sample: 67 µg/L
28/48 SYR4 2013–2019
Arsenic
20.125 µg/L 201%
of the EPA limit, at the 95th percentile of samples — 10 µg/L
worst single sample: 34 µg/L
26/160 SYR4 2012–2019
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
23/23 LCR 2025
Monochloroacetic Acid
5.44 µg/L
No EPA limit set
worst single sample: 5.88 µg/L
21/100 SYR4 2013–2019
Dichloromethane
1.806 µg/L 36%
of the EPA limit 5 µg/L
worst single sample: 2.22 µg/L
19/139 SYR4 2012–2019
Selenium
36.405 µg/L 73%
of the EPA limit 50 µg/L
worst single sample: 38.7 µg/L
18/50 SYR4 2013–2019
Lead
278.5 µg/L 1857%
of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 324 µg/L
14/364 SYR4 2014–2019
Dibromoacetic Acid
1.2 µg/L
No EPA limit set
worst single sample: 1.24 µg/L
11/100 SYR4 2013–2019
Nitrite
385 µg/L 39%
of the EPA limit 1000 µg/L
worst single sample: 420 µg/L
6/69 SYR4 2012–2019
Di(2-ethylhexyl) Phthalate
9.695 µg/L 162%
of the EPA limit, at the 95th percentile of samples — 6 µg/L
worst single sample: 10.1 µg/L
3/150 SYR4 2018–2019
Monobromoacetic Acid
1.363 µg/L
No EPA limit set
worst single sample: 1.37 µg/L
3/100 SYR4 2013–2019
Toluene
4.783 µg/L 0.5%
of the EPA limit 1000 µg/L
worst single sample: 5.22 µg/L
3/139 SYR4 2012–2019
Dalapon
1.32 µg/L 0.7%
of the EPA limit 200 µg/L
1/152 SYR4 2018–2019
74 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalBromoformChlorobenzeneCyanideCadmiumCarbon TetrachlorideDi(2-ethylhexyl) AdipateDinosebDiquatEndrinEthylbenzeneGlyphosateHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorNetfosaaNfdhaNmefosaaPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneThallium, TotalTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
MOORE
Phone
405-793-5085
Email
[email protected]

Frequently asked questions about Moore Public Works Authority

Is Moore Public Works Authority tap water safe to drink?

EPA monitoring detected 30 contaminants in Moore Public Works Authority's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Moore Public Works Authority's water?

EPA monitoring detected Chloroform, Bromodichloromethane, Nitrate-Nitrite, Dibromochloromethane, TTHM, and others. The full list with the level and data source for each is above.

How many people does Moore Public Works Authority serve?

Moore Public Works Authority reports serving 55,083 people in Oklahoma, per its EPA record.

Has Moore Public Works Authority had any water quality violations?

The EPA has 458 violations on file for Moore Public Works Authority, of which 162 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.