← Oklahoma

Tap water quality report

Creek Co Rwd # 7

EPA monitoring tested this supplier for 51 contaminants and detected 19. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

51
contaminants tested
19
detected
2,100
people served
701
health-based violations
Water source
Surface water
Ownership
Local government
Counties served
Creek

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

701
health-based violations
791
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Archived 2025-07-01 → 2025-09-30
MCL Health-based Archived 2025-07-01 → 2025-09-30
MCL Health-based Archived 2025-07-01 → 2025-09-30
MCL Health-based Archived 2025-07-01 → 2025-09-30
MCL Health-based Archived 2025-07-01 → 2025-09-30
MCL Health-based Archived 2025-07-01 → 2025-09-30
MCL Health-based Archived 2025-07-01 → 2025-09-30
MCL Health-based Archived 2025-07-01 → 2025-09-30
MCL Health-based Archived 2025-04-01 → 2025-06-30
MCL Health-based Archived 2025-04-01 → 2025-06-30

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Chlorite
993.9 µg/L 99%
of the EPA limit 1000 µg/L
worst single sample: 1430 µg/L
199/240 SYR4 2012–2019
Chloroform
156.3 µg/L
No EPA limit set
worst single sample: 203 µg/L
47/49 SYR4 2012–2019
TTHM
187.6 µg/L 234%
of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 224 µg/L
43/45 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
67.88 µg/L 113%
of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 193 µg/L
43/45 SYR4 2012–2019
Dichloroacetic Acid
30.48 µg/L
No EPA limit set
worst single sample: 87.2 µg/L
42/45 SYR4 2012–2019
Trichloroacetic Acid
45.1 µg/L
No EPA limit set
worst single sample: 102 µg/L
36/45 SYR4 2012–2019
Bromodichloromethane
31.23 µg/L
No EPA limit set
worst single sample: 34.2 µg/L
35/49 SYR4 2012–2019
Dibromochloromethane
13.95 µg/L
No EPA limit set
worst single sample: 15.5 µg/L
30/49 SYR4 2012–2019
Copper
170.8 µg/L 13%
of the EPA limit 1300 µg/L
worst single sample: 199 µg/L
25/40 SYR4 2012–2019
Lead
0.0019 mg/L 13%
of the EPA limit 0.0150 mg/L
17/17 LCR 2025
Dibromoacetic Acid
3.113 µg/L
No EPA limit set
worst single sample: 3.12 µg/L
15/45 SYR4 2012–2019
Monochloroacetic Acid
7.972 µg/L
No EPA limit set
worst single sample: 8.9 µg/L
9/45 SYR4 2012–2019
Bromoform
1.515 µg/L
No EPA limit set
worst single sample: 1.53 µg/L
7/49 SYR4 2012–2019
Nitrate-Nitrite
260 µg/L 2.6%
of the EPA limit 10000 µg/L
4/16 SYR4 2012–2019
Combined Radium (-226 And -228)
0.5682 pCi/L 11%
of the EPA limit 5 pCi/L
worst single sample: 0.5800 pCi/L
2/2 SYR4 2012–2017
Gross Beta Particle Activity
3.2835 pCi/L
No EPA limit set
worst single sample: 3.32 pCi/L
2/2 SYR4 2012–2017
Lead
9.03 µg/L 60%
of the EPA limit 15 µg/L
worst single sample: 9.1 µg/L
2/40 SYR4 2012–2019
Barium
8 µg/L 0.4%
of the EPA limit 2000 µg/L
1/1 SYR4 2015
Gross Alpha, Excl. Radon And U
0.0541 pCi/L 0.4%
of the EPA limit 15 pCi/L
1/2 SYR4 2012–2017
32 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-Dichloroethane1,2-DichloropropaneAntimony, TotalArsenicBenzeneBeryllium, TotalChlorobenzeneCadmiumCarbon TetrachlorideChromiumCombined UraniumDichloromethaneEthylbenzeneFluorideMercuryMonobromoacetic AcidSeleniumStyreneTetrachloroethyleneThallium, TotalTolueneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
CREEK CO RWD # 7
Phone
918-827-6575
Email
[email protected]

Frequently asked questions about Creek Co Rwd # 7

Is Creek Co Rwd # 7 tap water safe to drink?

EPA monitoring detected 19 contaminants in Creek Co Rwd # 7's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Creek Co Rwd # 7's water?

EPA monitoring detected Chlorite, Chloroform, TTHM, Total Haloacetic Acids (HAA5), Dichloroacetic Acid, and others. The full list with the level and data source for each is above.

How many people does Creek Co Rwd # 7 serve?

Creek Co Rwd # 7 reports serving 2,100 people in Oklahoma, per its EPA record.

Has Creek Co Rwd # 7 had any water quality violations?

The EPA has 791 violations on file for Creek Co Rwd # 7, of which 701 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.