Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Archived | 2025-10-01 → 2025-12-31 |
| MCL | Health-based | Archived | 2025-10-01 → 2025-12-31 |
| MCL | Health-based | Archived | 2025-10-01 → 2025-12-31 |
| MCL | Health-based | Archived | 2025-10-01 → 2025-12-31 |
| MCL | Health-based | Archived | 2025-10-01 → 2025-12-31 |
| MCL | Health-based | Archived | 2025-10-01 → 2025-12-31 |
| MCL | Health-based | Archived | 2025-07-01 → 2025-09-30 |
| MCL | Health-based | Archived | 2025-07-01 → 2025-09-30 |
| MCL | Health-based | Archived | 2025-07-01 → 2025-09-30 |
| MCL | Health-based | Archived | 2025-07-01 → 2025-09-30 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Chlorite | 602 µg/L 60% of the EPA limit 1000 µg/L
worst single sample: 903 µg/L | 81/273 | SYR4 | 2012–2019 |
| Bromoform | 76.95 µg/L No EPA limit set
worst single sample: 100 µg/L | 59/66 | SYR4 | 2012–2019 |
| Dibromochloromethane | 83.675 µg/L No EPA limit set
worst single sample: 149 µg/L | 58/66 | SYR4 | 2012–2019 |
| Bromodichloromethane | 57.225 µg/L No EPA limit set
worst single sample: 65.6 µg/L | 56/66 | SYR4 | 2012–2019 |
| Chloroform | 49.595 µg/L No EPA limit set
worst single sample: 65.9 µg/L | 54/66 | SYR4 | 2012–2019 |
| TTHM | 220.76 µg/L 276% of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 320.1 µg/L | 53/53 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 29.65 µg/L No EPA limit set
worst single sample: 31.3 µg/L | 51/52 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 69.9 µg/L 117% of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 80.2 µg/L | 51/52 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 7290 µg/L 73% of the EPA limit 10000 µg/L
worst single sample: 10900 µg/L | 40/42 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 29.095 µg/L No EPA limit set
worst single sample: 33.1 µg/L | 38/51 | SYR4 | 2012–2019 |
| Monobromoacetic Acid | 25.85 µg/L No EPA limit set
worst single sample: 28.6 µg/L | 31/52 | SYR4 | 2012–2019 |
| Copper | 649.4 µg/L 50% of the EPA limit 1300 µg/L
worst single sample: 1190 µg/L | 29/29 | SYR4 | 2013–2019 |
| Trichloroacetic Acid | 20.5 µg/L No EPA limit set
worst single sample: 23.5 µg/L | 27/52 | SYR4 | 2012–2019 |
| Combined Uranium | 8.415 µg/L 28% of the EPA limit 30 µg/L
worst single sample: 8.59 µg/L | 15/16 | SYR4 | 2012–2019 |
| Lead | 0.0052 mg/L 35% of the EPA limit 0.0150 mg/L | 14/14 | LCR | 2025 |
| Gross Beta Particle Activity | 12.485 pCi/L No EPA limit set
worst single sample: 13.2 pCi/L | 12/17 | SYR4 | 2012–2019 |
| Lead | 17.74 µg/L 118% of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 24.5 µg/L | 9/28 | SYR4 | 2013–2019 |
| Gross Alpha, Excl. Radon And U | 7.249 pCi/L 48% of the EPA limit 15 pCi/L
worst single sample: 9.07 pCi/L | 7/17 | SYR4 | 2012–2019 |
| Combined Radium (-226 And -228) | 0.6590 pCi/L 13% of the EPA limit 5 pCi/L
worst single sample: 0.6760 pCi/L | 5/16 | SYR4 | 2012–2019 |
| Tetrachloroethylene | 0.7640 µg/L 15% of the EPA limit 5 µg/L
worst single sample: 0.7700 µg/L | 5/28 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 9.49 µg/L No EPA limit set
worst single sample: 9.7 µg/L | 4/52 | SYR4 | 2012–2019 |
| Barium | 107.8 µg/L 5.4% of the EPA limit 2000 µg/L
worst single sample: 109 µg/L | 2/2 | SYR4 | 2012–2019 |
| Fluoride | 297 µg/L 7.4% of the EPA limit 4000 µg/L
worst single sample: 300 µg/L | 2/2 | SYR4 | 2012–2019 |
| Arsenic | 2.4 µg/L 24% of the EPA limit 10 µg/L | 1/2 | SYR4 | 2012–2018 |
| Selenium | 18.5 µg/L 37% of the EPA limit 50 µg/L | 1/2 | SYR4 | 2012–2019 |
28 contaminants tested, none detected
Utility contact
Frequently asked questions about Snyder Public Works Authority
Is Snyder Public Works Authority tap water safe to drink?
EPA monitoring detected 25 contaminants in Snyder Public Works Authority's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Snyder Public Works Authority's water?
EPA monitoring detected Chlorite, Bromoform, Dibromochloromethane, Bromodichloromethane, Chloroform, and others. The full list with the level and data source for each is above.
How many people does Snyder Public Works Authority serve?
Snyder Public Works Authority reports serving 1,509 people in Oklahoma, per its EPA record.
Has Snyder Public Works Authority had any water quality violations?
The EPA has 1196 violations on file for Snyder Public Works Authority, of which 800 are health-based (a contaminant limit or required treatment was breached) and 11 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.